1 of 1

EL3152 BECKHOFF 2-Channel Analog Input Terminal 4–20 mA

EL3152 BECKHOFF 2-Channel Analog Input Terminal 4–20 mA

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL3152

  • Country of origin:Germany

  • Product Type: EtherCAT Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Overview

The EL3152 (EL3152) is a high-precision 2-channel analog input terminal designed for the EtherCAT I/O system, specifically engineered to process standard 4 to 20 mA current signals. With a high 16-bit resolution, it provides the granular detail required for demanding B2B industrial applications such as pressure sensing, flow monitoring, and temperature regulation in process engineering. The EL3152 utilizes single-ended technology, meaning the inputs share a common internal ground, which optimizes terminal density while maintaining a slim 12 mm profile. Integrated Distributed Clocks (DC) support ensures that measurements across the EtherCAT network are synchronized with a precision of << 1 µs, enabling high-speed deterministic control loops.

Technical Configuration (Deep Dive)

The EL3152 is built for both speed and signal purity. It offers a standard conversion time of ~60 µs, which can be accelerated to ~40 µs in "Fast Mode" for high-dynamic applications. To combat industrial electrical noise, the terminal features software-activatable FIR (Finite Impulse Response) and IIR (Infinite Impulse Response) filters.

For safety and reliability, the terminal includes limit value monitoring, allowing the PLC to trigger alarms or emergency stops if a signal exceeds or falls below predefined thresholds. The 500 V galvanic isolation between the signal level and the E-bus protects the internal controller logic from field-side voltage spikes. Furthermore, the unit is extensively certified for global use in hazardous environments with ATEX, IECEx, and cFMus approvals.

Technical Specifications

Attribute Specification Details
Model EL3152
Brand BECKHOFF
Number of Inputs 2 (Single-ended)
Signal Range 4 to 20 mA
Resolution 16 bit (High-resolution)
Distributed Clocks Yes (Precision << 1 µs)
Conversion Time ~60 µs (Fast Mode: ~40 µs)
Input Filter Frequency 5 kHz
Measuring Error < ±0.3 % (relative to full scale)
Internal Resistance Typ. 85 Ω + diode voltage
Current Consumption (E-bus) Typ. 170 mA
Electrical Isolation 500 V (E-bus / Signal voltage)
Operating Temp -25 to +60 Celsius
Approvals CE, UL, ATEX, IECEx, cFMus

Technical FAQs

What is the benefit of "Single-Ended" technology in the EL3152?

Single-ended inputs use a common reference point for both channels. This allows Beckhoff to provide 2 high-resolution channels in a compact 12 mm width, which is highly efficient for cabinets where multiple 4–20 mA sensors share a common 24 V DC power source.

Can I monitor for a broken wire with this terminal?

Yes. Since the signal range is 4–20 mA, any current reading significantly below 4 mA (typically < 3 mA) can be interpreted by the PLC as a "Wire Break" or sensor fault, providing an inherent diagnostic advantage over 0–10 V systems.

Is this terminal suitable for use in North American hazardous zones?

Yes. With cFMus Class I, Division 2 certification, the EL3152 is approved for use in North American explosive atmospheres, as well as European Zone 2 areas via its ATEX and IECEx ratings.


Engineering & Installation Guide

  • Wiring for Accuracy: For high-precision 16-bit measurements, use shielded twisted-pair cabling. The shield should be grounded to the functional earth (FE) via a shield bus or low-impedance clamp as close to the terminal as possible to minimize EMI interference.

  • Filter Selection: Use the FIR filter for stable measurements in environments with high-frequency noise. Use the IIR filter if you require faster response times with a slight trade-off in noise suppression. These settings are easily adjusted via the TwinCAT "CoE - Online" tab.

  • Thermal Planning: The EL3152 consumes approximately 170 mA from the E-bus. Ensure your Bus Coupler (e.g., EK1100) or power feed terminal provides sufficient current for the entire segment. Maintain vertical installation on the DIN rail to allow for natural convection cooling.

Engineering Advantages

The EL3152 is a premier choice for engineers seeking a balance between high-speed data acquisition and industrial-grade stability. Its 16-bit resolution ensures that even the smallest fluctuations in current are captured, while the 5 kHz limit frequency filter provides a clean signal for PID control loops. The inclusion of ES series pluggable wiring facilitates rapid maintenance and module replacement without re-wiring. For B2B machine builders, the EL3152 provides a robust, globally-certified analog interface that simplifies the bridge between field instrumentation and sophisticated EtherCAT-based control systems.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
Germany

Recently Viewed Products

Technical knowledge

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...