Electromagnetic Induction in Industrial Coils
Understand how industrial coils create magnetic force, induce voltage, generate switching transients, and fail in relays, solenoids, transformers, motors, and proximity sensors. in service.
Manufacturer: Foxboro
Product No.: P0973CN
Country of origin:France
Product Type: Expansion Baseplates
Payment: T/T, Western Union
Weight: 800g
Dimensions: 240.0 mm x 216.0 mm x 30.3 mm (H x W x D)
Shipping port: Xiamen
Warranty: 12 months
The Foxboro P0973CN is a 4-position vertical DIN rail mounted expansion baseplate used in the Foxboro I/A Series DCS. It provides a dedicated hardware platform to house a fault-tolerant pair of FCP270 field control processors in two positions and a redundant pair of FEM100 fieldbus expansion modules in the remaining two positions. Operating on a passive backplane structure, the Foxboro P0973CN delivers high-reliability power routing and communication interconnections across the 2 Mbps Module Fieldbus. Mounting positions are specifically integrated onto the baseplate to accommodate fiber optic splitter/combiners required for fault-tolerant FCP270 processor operations.
| Specification | Value |
|---|---|
| Manufacturer | Foxboro (Invensys) |
| Model | P0973CN |
| System Compatibility | Foxboro I/A Series |
| Mounting Orientation | Vertical DIN Rail |
| Capacity | 4 Module Positions (2x FCP270, 2x FEM100) |
| Input Voltage Range | 24 V dc +5%, -10% (Redundant) |
| Communication Protocol | 2 Mbps HDLC Module Fieldbus |
| Baseplate ID DIP Switch | Not present (Does not require hardwired address) |
| Operating Temperature | -20 to +70 degC (-4 to +158 degF) |
| Storage Temperature | -40 to +70 degC (-40 to +158 degF) |
| Relative Humidity | 5 to 95% (noncondensing) |
| Altitude | -300 to +3,000 m (-1,000 to +10,000 ft) |
| Contamination Class | Class G3 (Harsh) per ISA S71.04; Pollution degree 2 per IEC 664-1 |
| Material | PC and ABS, inflammability UL94 V0 |
| Color | Black |
| Max Cable Length | 60 m (198 ft) total overall Module Fieldbus cabling |
| Connector Pin / Interface | Function |
|---|---|
| Primary Power Connector | Direct 24 V dc primary power input connection from FPS power supply |
| Secondary Power Connector | Direct 24 V dc secondary power input connection from FPS power supply |
| Fieldbus and Time Strobe A/B | Connections for redundant Module Fieldbus (2 Mbps) and optional time strobe signals |
| Dedicated FCP270 Slots | Keyed slots for fault-tolerant FCP270 control processors |
| Dedicated FEM100 Slots | Keyed slots for redundant FEM100 fieldbus expansion modules |
| Splitter/Combiner Mount | Integrated mounting provisions for FCP270 fiber optic splitter/combiners |