1 of 3

GE Multilin UR-8AH / UR8AH UR Series CT/VT Module

GE Multilin UR-8AH / UR8AH UR Series CT/VT Module

Only 8 item(s) left in stock
  • Manufacturer: General Electric

  • Product No.: UR-8AH

  • Country of origin:Canada

  • Product Type: CT/VT Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1160g

  • Dimensions: 15cm L x 18cm W x 4cm H

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The GE Multilin UR-8AH is an analog AC measurement interface module developed for the Universal Relays platform that provides three 1A/5A Phase CTs, one 1A/5A Ground CT, and 4 VTs to step down primary electrical grid signals into precise secondary values. This configuration allows the hosting relay chassis to sample, meter, and monitor crucial utility parameters including current, voltage, active power, energy, frequency, and circuit demand factors.

The primary function of the UR-8AH is to act as an isolated instrument transformer interface, converting high-magnitude high-voltage system lines into lower operational signals that can be recognized and modulated by the internal processing logic. As a legacy hardware option, it is engineered to operate on legacy equipment tiers carrying firmware version 3.5x or earlier, establishing standard 4CT/4VT matching layouts. This module provides critical safety isolation between secondary instrument circuits and ground, delivering accurate data streams used by protection loops to isolate faulted primary components. All parameter adjustments, calibration thresholds, and trend logs are interfaced using General Electric Multilin's EnerVista UR workstation software.

Features

  • Standard 4CT/4VT Interface Layout: Features three 1A/5A phase current inputs, one 1A/5A ground current input, and 4 voltage transformer paths.
  • Legacy Firmware Support: Optimized for legacy UR installations running firmware version 3.5x or lower.
  • High-Accuracy Parameter Metering: Delivers secondary sensing resolution for voltage, current, power, energy, and grid frequency metrics.
  • EnerVista Software Configuration: Combines with EnerVista UR interfaces for streamlined data export, trending, and graphical parameter review.

Applications

  • Substation Feeder Monitoring: Deployed inside traditional utility panels to capture current and voltage waveforms across key distribution circuits.
  • Legacy Protective Relay Upgrades: Installed within retrofitted configurations to replace faulty analog acquisition cards in legacy UR relay groups.
  • Industrial Electrical Plant Safeguards: Measures transformer and large electrical distribution loops to supply continuous utility data to central automation networks.

Technical Specifications

Parameter Specification
Manufacturer GE Multilin
Model UR-8AH
Product Series UR Series (Universal Relay)
Module Type CT/VT Module
Phase Current Transformer Channels 3 Channels (1A/5A Dual Rated)
Ground Current Transformer Channels 1 Channel (1A/5A Dual Rated)
Voltage Transformer Channels 4 Channels (VTs)
Firmware Compatibility Version 3.5x or earlier
Configuration Tool EnerVista UR
Manufacturing Location Ontario, Canada
Dimensions approx. 15cm L x 18cm W x 4cm H
Weight 2 lb, 9 oz (approx. 1.16 kg)

Installation Guidelines

  • Primary Circuit Isolation: Prior to removing or installing the module, disconnect and isolate all primary and secondary power lines from the relay case. Short-circuit all external CT secondary lines to avoid high-voltage transients.
  • Electrostatic Grounding Procedures: Technicians must utilize a grounded ESD wrist strap when inserting or removing this analog instrumentation card to safeguard embedded analog-to-digital processing components.
  • CPU Hardware Co-linking: Ensure this legacy card is paired with compatible legacy processing components such as the UR-9A, UR-9C, or UR-9D CPU cards.
  • Chassis Attachment: Slide the assembly straight along the dedicated enclosure chassis guide slots until the analog terminal headers align properly with the rear backplane assembly. Fasten faceplate locking screws tightly.
Key Features:

What firmware range is supported by the UR-8AH module configuration?

This legacy analog interface card is designed to accept and operate with relay firmware version 3.5x or earlier.

Which specific CPU models should be paired with the UR-8AH analog card?

The module should be matched with legacy version Multilin CPU cards, including the UR-9A, UR-9C, or UR-9D modules.

What is the secondary current input rating for the CT paths on this module?

The current transformer input ports are dual-rated, accepting either a 1A or 5A secondary instrument connection.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
Canada

Recently Viewed Products

Technical knowledge

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...

Single-Axis Motion Control Setup with CMZ Servo Drives

This tutorial explores the commissioning of a single-axis servo motion system using a CMZ SBD drive, covering hardware setup, axis scaling, homing configuration, and safe motion verification for...

Mitsubishi FX PLC Integration With FR-D700 VFD and HMI Control

This tutorial explains how Mitsubishi FX PLCs integrate with FR-D700 VFDs and HMI panels for forward/reverse motor control. It covers wiring logic, parameter configuration, ladder programming, and...