Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks
Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.
Manufacturer: Honeywell
Product No.: 10100/2/1
Country of origin:United States
Product Type: Bus Driver Module
Payment: T/T, Western Union
Weight: 110g
Shipping port: Xiamen
Warranty: 12 months
The Honeywell 10100/2/1 is a Horizontal Bus Driver (HBD) used in the I/O racks of Honeywell Fail Safe Control (FSC) systems. It provides the connection between the vertical bus from the Central Part (CP) and the horizontal bus serving the I/O modules within a rack.
The HBD assembly consists of the 10100/2/1 electronic module and an A1, A21, or A22 flatcable. The vertical bus connects to the module through rear connector CN1, while the flatcable extending from the front connects to the horizontal bus above the I/O rack. Address selection lines are routed to the horizontal bus through connector CN3.
Depending on the selected flatcable, the same electronic module supports non-redundant I/O, redundant I/O with one rack per HBD, or redundant I/O with two racks per HBD.
| Manufacturer | Honeywell |
| Part Number | 10100/2/1 |
| Type Number | 10100/2/1 10900 |
| Product Type | Horizontal Bus Driver (HBD) |
| System | Fail Safe Control (FSC) |
| Software Compatibility | FSC Version 3.00 or later |
| Supply Voltage | 5 VDC |
| Current with A1 Cable | 35 mA |
| Current with A21 Cable | 35 mA |
| Current with A22 Cable | 65 mA |
| Supply Ripple | < 50 mV p-p |
| Space Requirements | 4 TE, 3 HE (4 HP, 3U) |
| Weight | 0.11 kg |
| Approvals | CE, TÜV, UL |
| Module Key Coding | Holes A5, A7 |
| Rack Key Coding | Large pins A5, A7 |
The 10100/2/1 uses one of three flatcable arrangements according to the FSC I/O architecture.
| Flatcable | I/O Configuration | Current at 5 VDC |
|---|---|---|
| A1 | Non-redundant I/O | 35 mA |
| A21 | Redundant I/O, one rack per HBD | 35 mA |
| A22 | Redundant I/O, two racks per HBD | 65 mA |
The flatcable selection must correspond to the installed rack arrangement. The A22 configuration requires more supply current than the A1 and A21 configurations.
The 10100/2/1 is used with FSC rack backplanes that provide the vertical bus interface and HBD rack-address configuration. Applicable backplane models include:
The HBD rack address is programmed using jumpers RA0 to RA3 on the corresponding backplane. The manufacturer provides address settings for HBD1 through HBD10. Correct address assignment is necessary for identifying the I/O rack within the FSC configuration.
For non-redundant I/O backplane arrangements, the HBD is installed in rack position 21. Redundant I/O arrangements can use HBD positions 20 and 21, depending on the backplane configuration.
The Honeywell hardware manual permits replacement of the 10100/2/1 with power applied, but specifically warns that the Central Part will shut down if the HBD is safety-related. Replacement procedures must therefore account for the system's safety configuration and operating state.
Technical reference: Honeywell Fail Safe Control Hardware Manual, PM.MAN.8048, Revision 02. Refer to Section 4, pages 4-103 through 4-107, for the 10100/2/1 module description, connector arrangement, rack addressing, flatcable routing, and technical specifications.
Global Express Shipping
Returns & Warranty



Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Color pattern |
Green
Greyish White
|
| Country of origin |
United States
|
| Power source |
DC Power
|