The Honeywell 8C-PAIH54 (Part Number 51307070-275) is a conformal coated Differential Analog Input Module with HART designed for process measurement and monitoring in Experion LX Series 8 control systems. Operating within the Series 8 I/O architecture, the module interfaces differential 4-20 mA DC transmitter signals and HART digital communications directly to the C300 controller across the system I/O Link.

The module provides 16 differential input channels and features a factory-applied conformal coating (8C- prefix) to protect electronic circuitry against moisture, dust, chemical contaminants, and environmental harshness. It mounts directly onto an Input Output Termination Assembly (IOTA), eliminating the need for a separate electronic card chassis. Field wiring is landed on removable two-level terminal blocks on the IOTA, which also handles internal field power distribution.

The 8C-PAIH54 supports both non-redundant and hardware-redundant control configurations when combined with the appropriate IOTA board (8C-TAIDA1 or 8C-TAIDB1). Redundancy is implemented directly on the IOTA base without external switchover logic or special interconnect cables by attaching a second IOM. Secondary and tertiary HART variables along with device diagnostic status are transferred continuously to support process execution and asset maintenance.

Features

  • 16 differential analog input channels handling standard 4-20 mA DC currents and HART digital protocol communications.
  • Conformal coated circuit board assembly (8C- series designation) for severe environment protection.
  • Direct plug-in mounting onto Series 8 Input Output Termination Assemblies (IOTA), bypassing card cages.
  • Support for non-redundant (8C-TAIDA1) and redundant (8C-TAIDB1) termination assemblies.
  • Short-circuit protected input channel architecture to shield electronics against field wiring faults.
  • On-board field power distribution routed through the IOTA board to reduce external marshalling terminals.
  • Visual status indicator area on the front cover for quick operational checks.
  • Vertically mounted enclosure with an angled heat-dissipation layout for thermal management in dense cabinets.

Applications

  • Differential pressure, flow, and level transmitter measurement loops in continuous process control.
  • HART smart field device monitoring for real-time asset management and secondary variable collection.
  • Signal acquisition in harsh atmospheric environments where conformal coating is mandated.
  • Redundant analog input monitoring for critical control execution in Experion LX architectures.

Ordering Information

Component Description Option / Variant
8C-PAIH54 Differential Analog Input Module with HART, Coated Standard IOM Module
8C-TAIDA1 Differential AI IOTA, Non-Redundant, Coated (9 in / 228 mm) Optional Base Termination
8C-TAIDB1 Differential AI IOTA, Redundant, Coated (12 in / 304 mm) Optional Base Termination

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Model Number 8C-PAIH54
Part Number 51307070-275
System Platform Experion LX Series 8
Module Type Analog Input with HART - Differential
Coating Conformal Coated
Channel Capacity 16 Channels
Input Signal Differential 4-20 mA DC / HART

Electrical

Parameter Specification
Supply Voltage 24 VDC maximum
Current Draw (Non-Redundant with 8C-TAIDA1) 710 mA total @ 24 VDC (310 mA System / 400 mA Field)
Current Draw (Redundant with 8C-TAIDB1) 1020 mA total @ 24 VDC (620 mA System / 400 mA Field)
Maximum Field Supply Current 400 mA @ 24 VDC
Channel Protection Short-circuit protected input circuits

Environmental

Parameter Specification
Operating Temperature 0 degC to +60 degC (32 degF to +140 degF)
Storage Temperature -40 degC to +85 degC (-40 degF to +185 degF)
Relative Humidity 5% to 95% (non-condensing)
Sinusoidal Vibration 10-57 Hz at 0.075 mm, 57-150 Hz at 1 G acceleration (3 axes)
Shock Resistance 15 G peak, 11 ms duration (3 axes)
Enclosure Protection Class IP54 minimum for wet/outdoor areas; IP4X for protected areas

Compliance and Certifications

Parameter Specification
FM Approval Class I, Division 2, Groups A, B, C, D; T4 / Class I, Zone 2, AEx/Ex nA IIC T4 Gc
CSA Certification Class I, Division 2, Groups A, B, C, D; T4 / Class I, Zone 2, Ex nA IIC T4 Gc
ATEX Marking II 3G Ex nA IIC T4 Gc

Connections / Interfaces

Interface Function
IOTA Base Connector Mates directly to 8C-TAIDA1 or 8C-TAIDB1 IOTA boards for power and I/O bus interface
Field Terminations Two-level detachable screw terminal blocks on the IOTA for 4-20 mA device wiring

Installation Guidelines

  1. Confirm that system power is disconnected before installing or servicing modules in hazardous locations.
  2. Secure the compatible IOTA assembly (8C-TAIDA1 or 8C-TAIDB1) vertically to the cabinet channel.
  3. Ensure the enclosure chassis is grounded using at least #8 AWG solid copper conductor.
  4. Align the rear connectors of the 8C-PAIH54 module with the standard receptacle on the IOTA and push firmly.
  5. Tighten the two mounting screws on each side of the module cover to secure it to the IOTA board.
  6. Observe proper electro-static discharge (ESD) handling procedures, including grounding wrist straps.

Configuration and Commissioning Recommendations

  1. Define channel parameters, differential ranges, and HART variable assignments within Control Builder software.
  2. Verify transmitter loop power connections and polarity against the IOTA field terminal layout.
  3. Save controller configuration and parameter backups prior to module insertion or hardware swapping.
  4. Verify signal readings and HART communication status for each active input channel prior to process startup.
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What is the function of the Honeywell 8C-PAIH54 differential analog input module?
The Honeywell 8C-PAIH54 is a 16-channel differential analog input module with HART capabilities used in Experion LX Series 8 control systems. It converts 4-20 mA differential analog signals from field transmitters into process data for the C300 controller while passing HART diagnostic and variable data.
Which termination assemblies are compatible with the Honeywell 8C-PAIH54 module?
The Honeywell 8C-PAIH54 module installs on either the 8C-TAIDA1 non-redundant coated IOTA or the 8C-TAIDB1 redundant coated IOTA. The module plugs directly onto the termination assembly without requiring a separate card rack or chassis.
Can the Honeywell 8C-PAIH54 module be removed under power in hazardous locations?
The Honeywell 8C-PAIH54 module must not be removed or inserted under power in Division 2 or Zone 2 hazardous locations unless the area is confirmed to be non-hazardous. System power should be disconnected prior to module replacement to prevent sparking.
What does the 8C prefix signify on the Honeywell 8C-PAIH54 module?
The 8C prefix in the Honeywell 8C-PAIH54 model number designates that the module features conformal coating on its electronic circuit boards. This coating protects internal components against airborne contaminants, moisture, and corrosive atmospheric conditions.
Reviews

8C-PAIH54 51307070-275

Stock & lead time on request

Call
1 of 5

Honeywell 8C-PAIH54 51307070-275 Experion LX Series 8 Differential Analog Input Module with HART

Only 3 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: 8C-PAIH54 51307070-275

  • Country of origin:United States

  • Product Type: Differential Analog Input Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 75 x 150 x 120 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Honeywell 8C-PAIH54 (Part Number 51307070-275) is a conformal coated Differential Analog Input Module with HART designed for process measurement and monitoring in Experion LX Series 8 control systems. Operating within the Series 8 I/O architecture, the module interfaces differential 4-20 mA DC transmitter signals and HART digital communications directly to the C300 controller across the system I/O Link.

The module provides 16 differential input channels and features a factory-applied conformal coating (8C- prefix) to protect electronic circuitry against moisture, dust, chemical contaminants, and environmental harshness. It mounts directly onto an Input Output Termination Assembly (IOTA), eliminating the need for a separate electronic card chassis. Field wiring is landed on removable two-level terminal blocks on the IOTA, which also handles internal field power distribution.

The 8C-PAIH54 supports both non-redundant and hardware-redundant control configurations when combined with the appropriate IOTA board (8C-TAIDA1 or 8C-TAIDB1). Redundancy is implemented directly on the IOTA base without external switchover logic or special interconnect cables by attaching a second IOM. Secondary and tertiary HART variables along with device diagnostic status are transferred continuously to support process execution and asset maintenance.

Features

  • 16 differential analog input channels handling standard 4-20 mA DC currents and HART digital protocol communications.
  • Conformal coated circuit board assembly (8C- series designation) for severe environment protection.
  • Direct plug-in mounting onto Series 8 Input Output Termination Assemblies (IOTA), bypassing card cages.
  • Support for non-redundant (8C-TAIDA1) and redundant (8C-TAIDB1) termination assemblies.
  • Short-circuit protected input channel architecture to shield electronics against field wiring faults.
  • On-board field power distribution routed through the IOTA board to reduce external marshalling terminals.
  • Visual status indicator area on the front cover for quick operational checks.
  • Vertically mounted enclosure with an angled heat-dissipation layout for thermal management in dense cabinets.

Applications

  • Differential pressure, flow, and level transmitter measurement loops in continuous process control.
  • HART smart field device monitoring for real-time asset management and secondary variable collection.
  • Signal acquisition in harsh atmospheric environments where conformal coating is mandated.
  • Redundant analog input monitoring for critical control execution in Experion LX architectures.

Ordering Information

Component Description Option / Variant
8C-PAIH54 Differential Analog Input Module with HART, Coated Standard IOM Module
8C-TAIDA1 Differential AI IOTA, Non-Redundant, Coated (9 in / 228 mm) Optional Base Termination
8C-TAIDB1 Differential AI IOTA, Redundant, Coated (12 in / 304 mm) Optional Base Termination

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Model Number 8C-PAIH54
Part Number 51307070-275
System Platform Experion LX Series 8
Module Type Analog Input with HART - Differential
Coating Conformal Coated
Channel Capacity 16 Channels
Input Signal Differential 4-20 mA DC / HART

Electrical

Parameter Specification
Supply Voltage 24 VDC maximum
Current Draw (Non-Redundant with 8C-TAIDA1) 710 mA total @ 24 VDC (310 mA System / 400 mA Field)
Current Draw (Redundant with 8C-TAIDB1) 1020 mA total @ 24 VDC (620 mA System / 400 mA Field)
Maximum Field Supply Current 400 mA @ 24 VDC
Channel Protection Short-circuit protected input circuits

Environmental

Parameter Specification
Operating Temperature 0 degC to +60 degC (32 degF to +140 degF)
Storage Temperature -40 degC to +85 degC (-40 degF to +185 degF)
Relative Humidity 5% to 95% (non-condensing)
Sinusoidal Vibration 10-57 Hz at 0.075 mm, 57-150 Hz at 1 G acceleration (3 axes)
Shock Resistance 15 G peak, 11 ms duration (3 axes)
Enclosure Protection Class IP54 minimum for wet/outdoor areas; IP4X for protected areas

Compliance and Certifications

Parameter Specification
FM Approval Class I, Division 2, Groups A, B, C, D; T4 / Class I, Zone 2, AEx/Ex nA IIC T4 Gc
CSA Certification Class I, Division 2, Groups A, B, C, D; T4 / Class I, Zone 2, Ex nA IIC T4 Gc
ATEX Marking II 3G Ex nA IIC T4 Gc

Connections / Interfaces

Interface Function
IOTA Base Connector Mates directly to 8C-TAIDA1 or 8C-TAIDB1 IOTA boards for power and I/O bus interface
Field Terminations Two-level detachable screw terminal blocks on the IOTA for 4-20 mA device wiring

Installation Guidelines

  1. Confirm that system power is disconnected before installing or servicing modules in hazardous locations.
  2. Secure the compatible IOTA assembly (8C-TAIDA1 or 8C-TAIDB1) vertically to the cabinet channel.
  3. Ensure the enclosure chassis is grounded using at least #8 AWG solid copper conductor.
  4. Align the rear connectors of the 8C-PAIH54 module with the standard receptacle on the IOTA and push firmly.
  5. Tighten the two mounting screws on each side of the module cover to secure it to the IOTA board.
  6. Observe proper electro-static discharge (ESD) handling procedures, including grounding wrist straps.

Configuration and Commissioning Recommendations

  1. Define channel parameters, differential ranges, and HART variable assignments within Control Builder software.
  2. Verify transmitter loop power connections and polarity against the IOTA field terminal layout.
  3. Save controller configuration and parameter backups prior to module insertion or hardware swapping.
  4. Verify signal readings and HART communication status for each active input channel prior to process startup.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell 8C-PAIH54 51307070-275 Experion LX Series 8 Differential Analog Input Module with HART

What is the function of the Honeywell 8C-PAIH54 differential analog input module?

The Honeywell 8C-PAIH54 is a 16-channel differential analog input module with HART capabilities used in Experion LX Series 8 control systems. It converts 4-20 mA differential analog signals from field transmitters into process data for the C300 controller while passing HART diagnostic and variable data.

Which termination assemblies are compatible with the Honeywell 8C-PAIH54 module?

The Honeywell 8C-PAIH54 module installs on either the 8C-TAIDA1 non-redundant coated IOTA or the 8C-TAIDB1 redundant coated IOTA. The module plugs directly onto the termination assembly without requiring a separate card rack or chassis.

Can the Honeywell 8C-PAIH54 module be removed under power in hazardous locations?

The Honeywell 8C-PAIH54 module must not be removed or inserted under power in Division 2 or Zone 2 hazardous locations unless the area is confirmed to be non-hazardous. System power should be disconnected prior to module replacement to prevent sparking.

What does the 8C prefix signify on the Honeywell 8C-PAIH54 module?

The 8C prefix in the Honeywell 8C-PAIH54 model number designates that the module features conformal coating on its electronic circuit boards. This coating protects internal components against airborne contaminants, moisture, and corrosive atmospheric conditions.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States
Power source
DC Power

Recently Viewed Products

Technical knowledge

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...

GE Mark VI Function Blocks for Gas Turbine Control Logic

On Frame 5–9 gas turbines, GE Mark VI and Mark VIe run control as function-block application software. This article maps process, protection, and sequencing functions—and what Toolbox ST access...