Description

The Honeywell CC-PCNT02 (part number 51454551-275) is a C300 Controller node operating within the Experion PKS (Process Knowledge System) architecture. It executes the Control Execution Environment (CEE) software infrastructure to deliver process control, regulatory execution, logic, sequential operations, and model-based controls across industrial process networks.

Designed for process control applications, this C300 controller processes control strategies and manages communication across Fault Tolerant Ethernet (FTE) supervisory control networks and local I/O links. Operating on an IOTA platform, the CC-PCNT02 supports extended functionality firmware including Ethernet Interface Module (EIM) and Profit Controller integration, replacing the legacy CC-PCNT01 model in process automation installations.

Features

  • Operates the Control Execution Environment (CEE) supporting base execution periods of 50 ms and 20 ms.
  • Features dual I/O links supporting Series C I/O (750 Kbaud) and PMIO links (375 Kbaud).
  • Configurable for deterministic redundant controller pairs using Ethernet STP cabling.
  • Integrates directly with Level 1 FTE control networks via Control Firewall (CF9) units.
  • Supports PTPv2 and SNTP time synchronization protocols with a 1-minute SNTP update period.
  • Provides 14,852 MUs (Memory Units) of total available CEE user memory.
  • Accommodates up to 4095 tagged blocks per CEE instance.

Applications

  • Process automation and plant supervisory control
  • Continuous regulatory and logic control
  • Automated sequential and batch process execution
  • Turbomachinery control applications (20 ms CEE execution mode)
  • Third-party DCS integration via PCDI Modbus TCP architecture

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model CC-PCNT02
Part Number 51454551-275
Controller Series Experion PKS C300 Controller
Base Execution Periods 50 ms CEE / 20 ms CEE
Total Available CEE User Memory 14,852 MU (1 MU = 1024 bytes)
Maximum Tagged Blocks Per CEE 4095
Maximum Component Blocks per CM 100
Maximum Component Blocks per SCM/RCM/MR 400
Supported I/O Links 2 Links
I/O Link Speeds 750 Kbaud (Series C I/O), 375 Kbaud (PMIO Link, 50 ms CEE only)
Network Interface Fault Tolerant Ethernet (FTE) via Control Firewall
Time Synchronization SNTP (1 min update period), PTPv2 (30 sec update period)
Maximum I/O Units (50 ms CEE) 64 (up to 80 for PM IOPs or Series C IOMs only)
Maximum I/O Units (20 ms CEE) 12
Peer Connection Units (PCUs) 30 (50 ms CEE) / 53 (20 ms CEE)
Redundancy Interruption Switchover Time 500 ms (50 ms CEE) / 200 ms (20 ms CEE)
IOTA Size 6 inches

Installation Guidelines

  • Mount the controller module onto a compatible 6-inch IOTA (Input Output Termination Assembly).
  • Connect every C300 controller node directly to a dedicated Control Firewall (CF9) on the FTE network.
  • For redundant configurations, install two controllers on individual IOTAs using Ethernet STP redundancy cabling with approved lengths (36, 48, 60, or 84 inches).
  • Configure device index addresses using an odd index n for the primary node and n+1 for the redundant partner node.
  • Ensure proper cable routing and shielding across L1 FTE Control Network connections to mitigate electromagnetic interference.

FAQ

What is the primary difference between the 50 ms and 20 ms CEE execution modes on this controller?

The 50 ms CEE mode supports full DCS process control, PMIO, Series C I/O, and advanced applications like Profit Controller. The 20 ms CEE mode is optimized specifically for high-speed turbomachinery control applications with dedicated Series C I/O limits.

How is redundancy configured between two controller modules?

Redundancy requires two modules on separate IOTAs connected via Ethernet STP redundancy cables. The primary module is assigned an odd device index n, and the partner node is assigned index n+1.

Does this controller model replace older hardware versions in existing systems?

Yes, model CC-PCNT02 replaces model CC-PCNT01 for new installations and field replacements, providing support for extended functionality firmware images.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell CC-PCNT02 51454551-275 Experion PKS C300 Controller

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 15 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White Silver
Country of origin
United States
Power source
DC Power

Technical knowledge

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.

AKS 33 vs AKS 3000: Checks Before Replacing a Pressure Transmitter

A field checklist for distinguishing Danfoss 060G2105, 060G1323 and 060G2109 by pressure range, fitting, loop signal and controller scaling.

Diagnosing DeltaV SE5009 Power Problems Before Replacement

A field checklist for separating 24 VDC input, carrier bus, output derating and alarm-contact faults before replacing an Emerson SE5009.

Commissioning Quantum Inputs with the 140XSM00200 Simulator

A controlled commissioning method for using the 140XSM00200 simulator to verify Modicon Quantum input mapping and interlocks before reconnecting field wiring.

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.