1 of 1

Honeywell CC-TAIX01 Experion C300 Analog Input Module

Honeywell CC-TAIX01 Experion C300 Analog Input Module

Only 7 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: CC-TAIX01

  • Country of origin:United States

  • Product Type: DCS I/O Modules

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 22.0 x 15.0 x 8.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Providing the critical physical and electrical link between field instruments and the system controller, the Honeywell CC-TAIX01 serves as a high-density 16-channel Analog Input Input-Output Termination Assembly (IOTA) for the Experion C300 Series C platform. This module distributes loop power to process transmitters, collects continuous 4-20mA signals, and routes them to active C300 processing modules. Designed for high reliability in process automation architectures, it ensures clean signal integrity and robust physical cable termination in industrial control panels.

Key Features

  • High Density Channel Support: Terminations for up to 16 analog input channels configured in differential or single-ended modes.
  • Integrated Loop Power: Built-in 24 VDC distribution with short-circuit and current-limiting protections per channel.
  • Modular Assembly: Facilitates redundant or non-redundant configurations with compatible active analog input modules.
  • Secure Physical Termination: Industrial-grade screw clamp terminals provide strong resistance to mechanical vibration.
  • Integrated Carrier Mounting: Clips directly to standard DIN rail mounting arrangements for simplified installation.

Industrial Applications

  • Petrochemical & Refining: Interfacing pressure, flow, and temperature transmitters with the central Honeywell DCS.
  • Power Generation: Continuous analog monitoring of auxiliary process variables and feedback loops.
  • Water Treatment Facilities: Level, flow, and analytical chemistry transmitter integrations.
  • Pulp & Paper Mills: Interfacing process instruments in high electrical noise environments.

Technical Specifications

Specification Parameter Value / Standard
Manufacturer Honeywell
Part Number CC-TAIX01
Platform Series Experion C300 / Series C
Module Type Input Output Termination Assembly (IOTA)
Number of Channels 16 Analog Input Channels
Input Range 4 to 20 mA / 1 to 5 VDC
Rated Loop Power Voltage 24 VDC nominal
Operating Temperature 0 to 60 degC
Relative Humidity 5% to 95% RH (non-condensing)
Country of Origin United States
Shipping Weight (Calculated) 2.0 kg
Package Dimensions (Calculated) 22.0 x 15.0 x 8.0 cm

Wiring and Interface Connections

Terminal Range Functional Assignment
Terminals 1 - 16 (Positive) Channels 1 through 16 Positive Signal / Loop Transmitter Power Output
Terminals 17 - 32 (Negative) Channels 1 through 16 Analog Return Ground / Signal Return Input
Ground Bus Bar Shield / Drain Wire Terminations for Field Cable Assemblies

Empirical Engineering Insights

Alternative Models & Compatibility

The CC-TAIX01 is a non-conformal coated assembly. For deployment in environments with corrosive atmospheric contaminants, specifying the conformal coated alternative (CC-TAIX11) is required to meet ISA G3 standards. This termination assembly is designed specifically to host the CC-PAIX01 or CC-PAIX02 active Series C modules and cannot accept Series A or other legacy input modules.

Application Pitfalls & Engineering Notes

When mixing 2-wire (loop-powered) and 4-wire (externally-powered) instruments on the same assembly, incorrect grounding can lead to common-mode voltage saturation. For 4-wire configurations, ensure that signal-minus (-) paths are not left floating; connect them directly to the common ground plane of the enclosure power supply to prevent erroneous drift readings.

Commissioning & Wiring Tips

To eliminate high-frequency electromagnetic noise interference, always terminate the shielding drain wire of input cables on the dedicated chassis ground bus of the CC-TAIX01 IOTA. Never ground the shield at both the field transmitter end and the IOTA termination end simultaneously, as this can introduce destructive ground loops.

Installation & Field Deployment Guidelines

CRITICAL WARNING:

Isolate and lock out all auxiliary 24 VDC power networks prior to mounting or completing any wiring terminations on the assembly. Hot-wiring transmitter loops on an energized assembly can blow on-board terminal protective fuses or disrupt active controller communication backplanes.

1
Mount the CC-TAIX01 board directly onto the 35mm DIN rail inside the enclosure, ensuring the carrier locks are fully engaged.
2
Connect the system safety ground strap to the designated low-impedance ground point on the carrier.
3
Route field cables through clean, non-obstructive wiring ducts and strip lead wires back exactly 7 mm before inserting into the clamp terminals.
4
Torque the terminal clamp screws to a maximum rating of 0.5 Nm to prevent physical thread damage on the termination block.
Loading product navigation…

What is the primary difference between the CC-TAIX01 and CC-TAIX11 models?

The CC-TAIX01 is the standard non-conformal coated termination board, whereas the CC-TAIX11 is the conformal-coated version designed to protect internal electronics against G3 class harsh industrial gases and chemicals.

Does this board support both 2-wire and 4-wire transmitter configurations?

Yes, but special care must be taken with the wiring loops. The IOTA supplies 24 VDC to 2-wire loop-powered instruments, while external power configurations for 4-wire devices require correct common-ground references to avoid common-mode voltage drift.

Which active Honeywell modules plug into this termination assembly?

The CC-TAIX01 is designed to accept Honeywell Series C Analog Input modules, specifically CC-PAIX01 and CC-PAIX02 modules.

What is the rated channel capacity of this assembly?

This module features physical termination and routing channels for up to 16 analog input field signals.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...