The Honeywell TC-ODD321 is a 24 VDC digital output module for the Experion chassis I/O platform. It features 32 non-isolated output channels configured into two groups with 16 points per common ground. Designed to drive field devices such as solenoids, relays, and indicators, the device processes digital control signals from Experion C200/C200E controllers with fast, solid-state response.
Features
32 Output Points: Arranged into 2 distinct groups with 16 points per common connection.
Linear Derating: Supports full current loads up to 50 degC with controlled linear thermal derating up to 60 degC.
Fast Switching Response: On/off signal delay times are capped at 1.0 ms maximum.
Configurable Channel States: Individual channels can be configured to hold their last state or default to ON or OFF during fault conditions or program mode.
Hot-Swappable Operation: Supports Removal and Insertion Under Power (RIUP) in non-hazardous area installations.
Applications
Driving 24 VDC industrial solenoids and actuator coils
Operating interposing control relays and contactors
Controlling field indicator lights and annunciator panels
Interface automation outputs to external subsystem logic
Technical Specifications
Parameter
Specification
Manufacturer
Honeywell
Model
TC-ODD321
Product Type
Discrete Output Module
Number of Outputs
32 (16 points/common)
Output Voltage Range
10 to 31.2 VDC @ 50 degC (Linear derating), 10 to 28 VDC @ 60 degC
Output Current Rating (Per Point)
0.5 A max @ 50 degC (Linear derating), 0.35 A max @ 60 degC
Output Current Rating (Per Module)
16 A max @ 50 degC (Linear derating), 10 A max @ 60 degC
Surge Current
1 A for 10 ms each, repeatable every 2 s @ 60 degC
Minimum On-State Load Current
3.0 mA per output
Maximum On-State Voltage Drop
1 VDC @ rated current per point (3 VDC for IEC 1131-2)
Maximum Off-State Leakage Current
0.5 mA per point (1 mA per point IEC 1131-2 for 0.25 A output)
Output Delay Time (Off-to-On / On-to-Off)
1.0 ms maximum
Power Dissipation
6.1 W
Fusing Protection
Not protected (Fused terminal block/IFM recommended)
Reverse Polarity Protection
None (Wiring incorrectly may damage module)
Isolation Voltage (Group to Group)
100% tested at 2546 VDC for 1 s (250 VAC max continuous)
Isolation Voltage (User to System)
100% tested at 2546 VDC for 1 s
Terminal Block Connector
TC-TBCH (36-position terminal block)
Connections/Interfaces
Terminal Connection
Function
Connection Type
TC-TBCH 36-Position Removable Terminal Block
Cable Assembly Option
Pre-wired 1492-HWCAB or 1492-CABLE system
Remote Interface Option
Compatible with Allen-Bradley 1492-IFM / 1492-XIM series RTPs
Installation Guidelines
Polarity Warning: The module does not feature reverse polarity protection; ensure correct wiring polarity to avoid damaging internal output circuits.
External Circuit Protection: Outputs are not internally fused. Use fused Remote Terminal Panels (RTPs) or interface modules to guard individual channels against overcurrent conditions.
Thermal Management: Maintain appropriate chassis clearance inside enclosures to ensure proper natural convection cooling across specified operating temperature limits.
Hazardous Location RIUP: Do not remove or insert modules under power if the surrounding atmosphere is classified as a hazardous location.
Compliance and Certifications
UL: UL 508 Industrial Control Equipment
Hazardous Locations: Class I, Div 2, Groups A, B, C & D Hazardous and Ordinary locations
EMC Directives: 89/336/EEC EMC Directive, EN 50081-2 (Emissions), EN 50082-2 (Immunity)
C-Tick: Compliant with Australian Radiocommunications Act of 1992
FAQ
What happens to the outputs if communication is lost with the controller?
Each channel can be independently configured via software to either maintain its last known state, default to ON, or default to OFF when a fault occurs.
Does the module feature built-in electrical protection against short circuits?
No, the module does not have internal short-circuit protection or fuses. Using external fused terminal blocks or fused remote termination modules is recommended.
Can this module be replaced while the chassis power is turned on?
Removal and Insertion Under Power (RIUP) is permitted in ordinary, non-hazardous areas. However, hot-swapping is strictly prohibited in hazardous locations.
A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.
A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.
A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.
A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.
Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...