Honeywell

Honeywell TK-FPDXX2 Chassis Series-A Standard Power Supply Module

SKU TK-FPDXX2

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: TK-FPDXX2

  • Country of origin:United States

  • Product Type: Power Supply Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1140g

  • Dimensions: 145 mm x 112 mm x 140 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

The Honeywell TK-FPDXX2 is a conformal-coated, standard (non-redundant) power supply module designed for Experion Chassis Series-A (CIOM-A) systems. It slides directly onto the left side of the chassis to supply DC power to all installed modules via the backplane without consuming a standard chassis slot position. Featuring a conformal coating, the TK-FPDXX2 is designed to withstand harsh industrial environments meeting Moderate (G2) or Harsh (G3) airborne contaminant conditions.

Features

  • Conformal coating applied for corrosion protection in harsh industrial environments (ANSI/ISA-S71.04-1985 G2/G3 compliant).
  • Direct chassis left-side mounting layout that powers the backplane without consuming an I/O or controller slot position.
  • Accepts 24 VDC input source power for non-redundant system applications.
  • Supplies 1.2 V, 3.3 V, 5.1 V, and 24.0 V DC power directly to the chassis backplane.
  • Integrated soldered non-replaceable fuse for short-circuit fire hazard protection.

Applications

  • Experion C200 / C200E Control Processor Chassis Systems
  • Experion Chassis Series-A (CIOM-A) Remote I/O Racks
  • Industrial Process Control and Automation Systems
  • Harsh chemical or industrial plant environments requiring G2/G3 airborne contaminant resistance

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model TK-FPDXX2
Coating Conformal Coated
Type Standard (non-redundant) Power Supply Module
Input Voltage Range 19.2-32 VDC (Input may drop to 16 V for a maximum of 2 minutes each hour for motor starting)
Input Power 100 W
Maximum Inrush Current 30 A
Frequency Range DC
Total Power Output Maximum 70 W @ 60 degC
Backplane Output Current Maximum

1.5 A @ 1.2 V

4 A @ 3.3 V

10 A @ 5.1 V

2.8 A @ 24.0 V

Output Power Combination Limit Total combined output power across 1.2 V, 3.3 V, 5 V, and 24 V backplane outputs cannot exceed 70 W
Fuse Protection Non-replaceable fuse is soldered in place
Wiring Size #14 AWG (1.4 mm)
Dimensions (L x D x H) 11.2 x 14.5 x 14.0 cm (4.41 x 5.71 x 5.51 in)
Weight Approximate 1.1 kg (2.5 lb.)
Location Left side of chassis (does not consume a slot)
Operating Temperature 0 to 60 degC (32 to 140 degF)
Storage Temperature -40 to 85 degC (-40 to 185 degF)
Relative Humidity 5 to 95% noncondensing (de-rated to 55% above 40 degC to maintain constant moisture content)
Temperature Change Rate <= 1 degC/min. (<= 5 degC/min. storage)
Operating Altitude -300 to +3000 m
Vibration (3 axes) 10 to 60 Hz, 0.5 g max. acceleration, 0.1 inches displacement
Mechanical Shock 5 g max. acceleration, 30 ms max. duration

Installation Guidelines

  • Mounting Position: Install the power supply module directly onto the left side of the Experion Series-A chassis. The power supply module does not occupy a standard module slot position.
  • Wiring Requirements: Use #14 AWG (1.4 mm) copper conductors for the input power connections.
  • Enclosure Requirements: Maintain appropriate physical clearances around the chassis (minimum 15.2 cm / 6.0 in vertical distance to cabinet, 10.2 cm / 4.0 in horizontal distance to cabinet).
  • Thermal Management: Ensure ambient operating temperatures around the unit do not exceed 60 degC to maintain full 70 W total power output capability.

Compliance and Certifications

  • UL: UL 508 Industrial Control Equipment
  • Hazardous Locations: Class I, Div 2, Groups A, B, C & D Hazardous and Ordinary locations
  • EMC Directive: 89/336/EEC
  • Emissions: EN 50081-2, Industrial
  • Immunity: EN 50082-2, Industrial
  • C-Tick: Meets requirements of the Australian Radiocommunications Act of 1992, Section 182, relating to electromagnetic compatibility

FAQ

Does this power supply module consume a slot position in the chassis?

No, the power supply module slides directly onto the left side of the chassis and does not consume any standard module slot positions.

What is the primary difference between TK and TC power supply models?

Models starting with the TK prefix feature conformal coating for corrosion protection in harsh airborne environments, whereas TC models are uncoated.

What is the maximum total output power provided by the device?

The total maximum output power combination across all backplane voltages is 70 W at 60 degC.

What input voltage range does this unit support?

The unit operates on a 19.2 to 32 VDC input voltage range, and can tolerate voltage drops down to 16 VDC for up to 2 minutes per hour.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell TK-FPDXX2 Chassis Series-A Standard Power Supply Module

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 6 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States
Power source
DC Power

Technical knowledge

First TwinCAT PLC Project on a Beckhoff IPC

Build and verify a first TwinCAT PLC project on a Beckhoff IPC. This checklist covers target selection, EtherCAT discovery, I/O mapping, safe activation, restart tests, and commissioning records.

Commissioning OPC UA in KEPServerEX: A Field Checklist

A practical commissioning sequence for KEPServerEX OPC UA connections: define data ownership, test tags locally, configure endpoint and certificate trust, limit access, then verify failure recovery...

Set a PLC Commissioning Laptop IP Without Losing Access

Commissioning an Ethernet-connected PLC often starts with the laptop, not the controller. Learn how to record existing settings, choose a temporary address, test connectivity, and restore the plant...

Designing Automation for Combustible Dust Hazards

Combustible dust controls require more than alarms. Learn how to map dust generation, select instrumentation, design interlocks, handle failed feedback, test safe states, and maintain the full...

Hairpin Stators: Benefits, Limits, and Inspection

Hairpin windings raise slot fill and support compact traction motors, but conductor geometry, AC losses, insulation damage, weld quality, and cooling determine whether the design meets its targets.

Using Ansible for Controlled SCADA Server Changes

Use Ansible to standardize SCADA server changes without expanding OT risk. This guide covers inventories, idempotent playbooks, staged testing, credentials, logging, and practical rollback controls.