Serving as an interactive visualization node, the NS5-MQ10B-V2 functions within the Omron NS series ecosystem to provide reliable control and monitoring interfaces. This 5.7-inch HMI touchscreen terminal displays process diagnostics and machine parameters on a high-contrast STN monochrome screen. Designed primarily for compact control panels where space optimization is critical, this operator panel features a robust black bezel housing and relies on dedicated serial interfaces for controller communications, keeping configuration straightforward and secure.

The unit integrates smoothly with Sysmac automation platforms, enabling rapid screen design and tag sharing. Its analog resistive touch screen offers flexible layout options without being restricted by traditional matrix grid limitations, providing precise control inputs in challenging industrial environments.

Features

  • 5.7-inch high-contrast STN monochrome liquid crystal display
  • 320 x 240 pixel native graphic resolution
  • Analog resistive touch panel with highly responsive operator feedback
  • Integrated black front bezel suitable for standard industrial enclosures
  • Support for multi-language display configurations and dynamic screen objects
  • Dual serial ports for direct connection to PLCs and temperature controllers

Applications

  • Packaging machinery control stations
  • Water and wastewater monitoring nodes
  • Automotive assembly cell operations
  • Conveyor and material handling dispatch systems

Technical Specifications

Manufacturer Omron
Part Number / Model NS5-MQ10B-V2
Display Type STN monochrome LCD
Display Size 5.7 inches (115.2 x 86.4 mm active area)
Resolution 320 x 240 pixels
Power Supply Voltage 24 VDC
Allowable Voltage Range 20.4 to 27.6 VDC
Power Consumption 15 W maximum
Case Color Black
Ethernet Port None
Serial Ports 1x RS-232C (Port A), 1x RS-232C (Port B)
Operating Temperature 0 to 50 degC
Storage Temperature -20 to 60 degC
Front Panel Protection IP65 equivalent, UL Type 4 (indoor use only)

Connections and Interfaces

Interface Connection Functional Assignment
Serial Port A (RS-232C) Host Link / NT Link communication (9-pin female D-Sub)
Serial Port B (RS-232C) Host Link / NT Link / Barcode Reader connection (9-pin female D-Sub)
USB Slave Port Screen data transfer and programming (Type B connector)
Expansion Interface Reserved for functional extension boards
Power Supply Terminal Block 24 VDC input and functional ground connections

Installation Guidelines

  • Prepare a panel cutout measuring 184.0 mm by 131.0 mm.
  • Ensure the panel thickness of the mounting enclosure is between 1.6 mm and 4.8 mm.
  • Insert the HMI into the cutout and tighten the provided mounting brackets to a torque of 0.5 to 0.6 N-m to achieve a proper environmental seal.
  • Connect a dedicated ground wire of at least 2.0 mm² to the functional ground terminal, keeping ground impedance under 100 ohms.
  • Leave at least 100 mm of clearance space around the terminal to maintain adequate natural convection cooling.

Compliance and Certifications

  • CE Mark
  • cULus Listed (UL508)
  • UL Type 4 (Front panel installation)

FAQ

What is the display size and type of the NS5-MQ10B-V2?

The NS5-MQ10B-V2 features a 5.7-inch STN monochrome LCD display with a resolution of 320 x 240 pixels.

Does this unit have built-in Ethernet capability?

No, the NS5-MQ10B-V2 model is not equipped with an Ethernet port. It uses serial interfaces (RS-232C) for communication.

What voltage is required to power this HMI terminal?

The unit operates on a nominal 24 VDC input voltage, with an allowable operating range of 20.4 to 27.6 VDC.

What is the environmental ingress protection rating of the front panel?

When properly mounted, the front panel of the NS5-MQ10B-V2 provides IP65 and UL Type 4 protection against dust and water spray.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 4 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Technical knowledge

Troubleshooting Industrial Control Cabinets Systematically

A structured control-cabinet troubleshooting method covering safe work, drawings, power paths, branch protection, DC supplies, return circuits, PLC outputs, fault records and repair verification.

Measuring Voltage in Industrial Control Circuits

A practical voltage-testing guide for industrial control panels, covering reference points, meter selection, live-dead-live checks, voltage drop, ghost voltage, stored energy and intermittent faults.

Building a Verifiable Lockout Tagout Procedure

A practical lockout tagout guide covering hazardous-energy identification, isolation, stored-energy control, verification, group work, temporary testing, restoration, inspections and audits.

Designing Compressed-Air Preparation at the Machine

A field guide to point-of-use compressed-air preparation covering filters, regulators, drains, dryers, lubrication, pressure loss, isolation, monitoring, commissioning and leak testing.

Selecting Pneumatic Valve Actuation and Safe States

A practical guide to manual, pilot and solenoid pneumatic valves, covering port functions, monostable and bistable behavior, PLC outputs, safe states, commissioning and fault diagnosis.

Designing Current Shunt Measurements That Stay Accurate

A practical guide to current-shunt measurement covering resistor sizing, high-side and low-side placement, Kelvin sensing, error budgets, thermal effects, protection and commissioning tests.