Description
Designed for reliable analog-to-digital conversion within the Sysmac automation platform, the NX-AD3203 current input module offers precise signal processing for modern industrial environments. This 4-point analog input unit connects directly to the NX-series I/O system, allowing seamless integration with EtherCAT or EtherNet/IP couplers. Featuring single-ended inputs tailored for standard 4 to 20 mA process loops, the module is engineered for applications demanding rapid measurement capabilities and stable data transmission.
The unit functions using a free-run refreshing cycle and delivers a fast conversion speed of 250 microseconds per point. It translates analog process signals into digital values with a resolution of 1/8000, ensuring highly accurate monitoring of field instruments. Equipped with a 12-terminal screwless clamping block, the unit facilitates rapid wiring and exceptional vibration resistance in demanding machinery setups.
Features
- Four independent, single-ended analog current input channels.
- Standard 4 to 20 mA input range compatible with most process transmitters.
- Fast conversion speed of 250 microseconds per point for high-speed loop control.
- 1/8000 resolution delivers fine-grained measurement data.
- Free-run refreshing mechanism for consistent synchronous backplane updates.
- Screwless clamping terminal block with 12 points simplifies installation and reduces maintenance overhead.
- Compact 12 mm width design optimizes space utilization on the DIN rail.
Applications
- Process manufacturing systems involving flow, level, temperature, and pressure monitoring.
- Machine control units demanding high-speed sensor integration.
- Water and wastewater processing instrumentation setups.
- Factory automation and packaging machinery integrated via EtherCAT networks.
Technical Specifications
Manufacturer
| Omron |
Part Number / Model
| NX-AD3203 |
Series
| NX Series |
Module Type
| Analog Input Unit |
Number of Inputs
| 4 points |
Input Range
| 4 to 20 mA |
Resolution
| 1/8000 |
Input Method
| Single-ended input |
Conversion Time
| 250 microseconds per point |
I/O Refreshing Method
| Free-run refreshing |
Input Impedance
| 250 ohms |
External Connection
| Screwless clamping terminal block (12 terminals) |
Dimensions (H x W x D)
| 10 cm x 1.2 cm x 7.1 cm |
Weight
| 0.07 kg |
Installation Guidelines
- Ensure the system power is completely shut off before mounting or removing the module from the NX-bus unit alignment.
- Mount the unit securely onto a standard 35 mm DIN rail, verifying that the DIN rail locking hooks are fully engaged.
- Strip field cables to the manufacturer-specified length before inserting them into the screwless clamping terminals to prevent short circuits.
- Use shielded, twisted-pair cables for all analog 4 to 20 mA current loops to minimize electromagnetic interference.
- Ground the cable shields at a single point in the control panel to protect the low-voltage analog signals from ground loop noise.