Description
The PLX31-EIP-MBS4 is an industrial-grade communication gateway designed to establish bi-directional data exchange between EtherNet/IP networks and Modbus Serial protocols. By acting as a protocol converter, this module permits EtherNet/IP-enabled controllers, such as Rockwell Automation Logix processors, to seamlessly read and write data to Modbus Serial devices. The gateway features four isolated serial ports, allowing independent configuration for RS-232, RS-422, or RS-485 electrical interfaces. This flexibility enables high-density integration of field instruments, power meters, drives, and flow controllers into modern control systems.
Engineered for demanding industrial environments, this interface module supports both EtherNet/IP Class 1 I/O connections for real-time control and Class 3 messaging for diagnostic data transfer. The dynamic data mapping capabilities allow engineers to optimize throughput, ensuring minimal latency between networks.
Features
- Four fully independent, isolated serial ports supporting RS-232, RS-422, and RS-485 configurations.
- Supports up to 5 EtherNet/IP Class 3 server connections and 8 Class 1 I/O connections.
- Bi-directional data mapping between EtherNet/IP and Modbus Serial networks.
- Configurable serial parameters including baud rate, parity, stop bits, and handshaking.
- Diagnostics and monitoring available via web-based configuration tools.
- Wide operating temperature range suited for unconditioned control cabinets.
Applications
- SCADA and HMI integration with legacy Modbus field devices.
- Power distribution networks integrating Modbus RTU power meters.
- Oil and gas flow metering system communication.
- Water and wastewater remote telemetry integration.
- Industrial manufacturing assembly line automation.
Technical Specifications
Parameter
Specification
| Manufacturer |
ProSoft Technology |
| Part Number / Model |
PLX31-EIP-MBS4 |
| Product Type |
EtherNet/IP to Modbus Serial Gateway |
| Number of Serial Ports |
4 (isolated) |
| Serial Interface Types |
RS-232, RS-422, RS-485 |
| EtherNet/IP Class 3 Connections |
5 |
| EtherNet/IP Class 1 I/O Connections |
8 |
| I/O Connection Size |
248 / 248 bytes |
| Max Requested Packet Interval (RPI) |
5 ms per connection |
| Nominal Input Voltage |
24 VDC |
| Allowed Input Voltage Range |
10 to 36 VDC |
| Current Load (Nominal) |
300 mA @ 24 VDC |
| Current Load (Maximum) |
610 mA @ 10 to 36 VDC |
| Operating Temperature |
-25 degC to 70 degC |
| Storage Temperature |
-40 degC to 80 degC |
| Shipping Weight |
3 kg |
Connections and Interfaces
Interface Port
Physical Connection Type
Supported Protocols
| Ethernet Port |
RJ45 (10/100 Mbps) |
EtherNet/IP, TCP/IP |
| Serial Port 1 |
RJ45 (RS-232/422/485) |
Modbus RTU / ASCII |
| Serial Port 2 |
RJ45 (RS-232/422/485) |
Modbus RTU / ASCII |
| Serial Port 3 |
RJ45 (RS-232/422/485) |
Modbus RTU / ASCII |
| Serial Port 4 |
RJ45 (RS-232/422/485) |
Modbus RTU / ASCII |
| Power Input |
3-position terminal block |
Positive, Negative, GND |
Installation Guidelines
-
Mounting: Install on standard 35mm DIN rails. Verify the locking mechanism is secure.
-
Grounding: Connect the dedicated ground terminal on the power connector directly to the panel functional ground using low-impedance copper wire.
-
Wiring: Route communication cabling (Ethernet and Serial) away from high-voltage AC lines to prevent electromagnetic interference.
-
Clearance: Maintain at least 50mm of clearance at the top and bottom of the module to support proper convective cooling.
Compliance and Certifications
- CE Mark
- UL/cUL Class I, Division 2
- ATEX Zone 2