Description

Designed for integration into SattCon 200 and SattLine control architectures, the ABB 200-CPU30/10 is a high-performance 32-bit single-board central processing unit optimized for demanding process control tasks. This module features an integrated math co-processor (FPU) for accelerated floating-point calculation performance and a built-in SattBus supervisor interface to facilitate seamless industrial network communication. Equipped with 2 MByte of RAM system memory and a real-time clock backed by a long-life lithium battery, this unit provides reliable, deterministic execution of automation programs. Normal operation requires a stable power-fail signal input from the companion power supply module, ensuring immediate, safe shut-down and data preservation in the event of voltage drops.

Features

  • 32-Bit Processing: Powered by a Motorola MC68020 microprocessor running at 16.7 MHz.
  • Mathematical Acceleration: Integrated floating-point math co-processor (FPU) for high-speed mathematical computations.
  • Dual Serial Communication: Two independent RS232 serial channels supporting baud rates from 75 to 19200 bps.
  • Integrated SattBus: One dedicated supervisor channel for reliable peer-to-peer and supervisory control communication.
  • Robust Memory Retention: 2 MByte system and application RAM backed by an easily replaceable 3.6 V lithium battery.
  • Diagnostic Diagnostics: Front-panel green LEDs for power, SattBus, and serial status, alongside red LEDs for system faults and program stops.

Applications

  • SattCon 200 system control configurations.
  • SattLine process automation networks.
  • Continuous monitoring and process control in heavy manufacturing.
  • Water and wastewater treatment plant control architectures.

Technical Specifications

Parameter Specification
Manufacturer ABB
Model Series Advant Controller 250
Processor Type Motorola MC68020 (16.7 MHz) with Math Co-Processor
System Memory 2 MByte RAM
Supply Voltage 24 V DC (19.2 to 30 V DC) with max 5% ripple
Internal Current Consumption Max 0.6 A
Serial Interfaces 2x RS232 Channels (Baud rates: 75 to 19200 bps, Max 15 m)
Network Interfaces 1x SattBus supervisor channel
Backup Battery Lithium 3.6 V, 1.75 Ah (Type AA/R6/UM-3), 3-year life
Backplane Key Code 5
Operating Temperature +5 degC to +55 degC
Non-Operating Temperature -25 degC to +70 degC
Humidity Range Max 90% relative humidity, non-condensing
Protection Rating IP20
Certifications and Approvals CE, EMC Directive 89/336/EEC, LVD 73/23/EEC, UL Listed (US/Canada), Class I Div 2
Dimensions (H x W x D) 163 mm x 45 mm x 91 mm (excluding connectors/snap locks)
Net Weight 0.43 kg

Connections and Interfaces

Port / Terminal Interface Type & Function
Front D-Connector 9-pin female D-type connector for direct programming and serial diagnostic interfacing
Base Connector One 200-BPP screw terminal block interface
Backplane Interface Direct ground connection and system power routing via the 200-BPN backplane

Empirical Engineering Insights

Alternative Models & Compatibility

The 200-CPU30/10 acts as an upgrade path for standard CPU30 series cards within the Advant Controller 250 family. It uses backplane key code 5; verify keyway compatibility on the 200-BPN backplane prior to insertion to prevent mechanical interference or pin damage. Ensure that system software configurations (SattCon or SattLine) are updated to match this specific hardware version to resolve potential addressing conflicts.

Application Pitfalls & Engineering Notes

A common point of operational failure is the omission of the power-fail line signal. The 200-CPU30/10 requires active power fail signals routed from the 200-PSMG/PSSG power supply units. If these lines are severed or improperly configured, the controller will fail to execute application programs, displaying a permanent Stop state. Always measure voltage stability and verify the integrity of the 24 V DC supply under full I/O load conditions.

Commissioning & Wiring Tips

During initial commissioning, verify the physical position of the front-panel start-mode switch before powering up the assembly. This switch dictates how the program space loads on boot. To ensure maximum noise immunity for the RS232 serial links, ensure they do not exceed 15 meters and are routed in grounded, shielded conduits isolated from high-current AC cabling.

Installation Guidelines

CRITICAL WARNING

Disconnect all power sources from the backplane assembly before mounting, removing, or wiring the processor module. Static discharge can permanently damage delicate internal CMOS logic. Wear an approved, grounded ESD wrist strap during handling. Ensure the system backplane ground terminal is bonded to the main earth ground.

1
Inspect the 200-BPN backplane connector for debris and verify that the physical mechanical keying pin aligns perfectly with Key Code 5 on the module.
2
Align the module carefully with the guide rails on the backplane, and push firmly until the snap locks engage securely on the DIN rail or mounting chassis.
3
Plug in the 200-BPP screw terminal blocks and secure the front-panel communication cables to the 9-pin serial ports, torqueing screws to nominal spec.
4
Install the fresh 3.6 V lithium backup battery into its dedicated slot, verifying correct polarity, and perform the initial power-up verification sequence.
Loading product navigation…

What causes the CPU to remain in a persistent Stop or Fail LED state during startup?

This is commonly caused by a missing power-fail signal from the power supply module (e.g., 200-PSMG) or a low backup battery. Ensure the power supply is functional and the 3.6V battery is fully charged.

How often should the backup battery be replaced on this system?

The lithium battery (3.6 V, 1.75 Ah) should be replaced every 3 years under normal operating conditions to prevent loss of RAM system memory and application code during power outages.

Can the RS232 serial channels be used for long-distance communication?

No, the RS232 interfaces have a maximum physical cable length limitation of 15 meters. For longer distances, interface converters or SattBus networking should be utilized.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Suécia

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...