1 de 2

ABB SF810I-LOS-UVIR-T Uvisor SF810i Multi Fuel Integrated Safe Flame Scanner

ABB SF810I-LOS-UVIR-T Uvisor SF810i Multi Fuel Integrated Safe Flame Scanner

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: ABB

  • Nº do Produto: SF810I-LOS-UVIR-T

  • País de origem:China

  • Tipo de Produto: Flame Scanners

  • Código de barras: 9031809090

  • Pagamento: T/T, Western Union

  • Peso: 1372g

  • Dimensões: 180 mm x 135 mm x 260 mm (W x H x L)

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

The ABB SF810I-LOS-UVIR-T (SF810INT-LOS-UVIR-T-C-W ) is an advanced multi-fuel integrated safe flame scanner belonging to the Uvisor SF810i and Symphony Plus product families. This module acts as an integrated, self-contained intelligent combustion sensor, combining the optical detection assembly and the signal analysis processor within a single rugged enclosure. Engineered for challenging multi-fuel burners, it features dual-sensor detection capability utilizing both Ultraviolet (UV) and Infrared (IR) solid-state sensors to continuously monitor the presence or absence of individual burner flames. Beyond absolute flame discrimination, the device continuously analyzes flame modulation characteristics to compute real-time qualitative combustion stability trends. It features a Line-of-Sight (LOS) optical orientation, an internal termination board with plug-in terminal blocks, and an embedded Modbus RTU RS485 communication link for peripheral integration. Powered by a nominal 24 VDC input, the scanner operates without a separate remote evaluation unit, delivering safety-critical flame relay contacts and analog quality tracking outputs directly from the burner-mounted unit.

Features

  • Integrated all-in-one architecture housing both optical sensors and microprocessing electronics inside the burner head unit.
  • Dual solid-state UV and IR sensor arrangement designed for multi-fuel discrimination and coal, oil, or gas combustion profiling.
  • Line-of-Sight (LOS) optical orientation configuration for direct direct-view flame alignment.
  • Native electronic communication via built-in Modbus RTU over a 2-wire RS485 physical layer.
  • Direct on-board user configuration management accessible via raw Modbus registers or PC-based software utilities.
  • Internal terminal block module layout fitted with an integrated termination board for straightforward field wiring.

Applications

  • Multi-fuel utility burners using independent or simultaneous gas, oil, and pulverized coal firing.
  • Continuous flame supervision and discrimination within industrial steam boilers and power generation furnaces.
  • Real-time qualitative monitoring of flame combustion dynamics and burner performance.
  • Burner Management System (BMS) integration via direct hardwired flame safety relays.

Ordering Information

Detail Value / Description
Product ID SF810I-LOS-UVIR-T
Catalog Description SF810INT-LOS-UVIR-T-C-W
Invoice Description SF810INT-LOS-UVIR-T-C-W
Model Code Structure Integrated (SF810i), Line of Sight (LOS), UV + IR Sensors (UVIR), Terminal Block Termination (T)

Technical Specifications

Parameter Value / Specification
Manufacturer ABB
Product Family Uvisor SF810i Series (Integrated)
System Platform Symphony Plus
Sensing Technology Solid-state Ultraviolet (UV) + Infrared (IR)
Optical Configuration Line-of-Sight (LOS) / Direct View
Termination Type Plug-in terminal blocks via internal termination board
Serial Communication RS-485, 2-wire half-duplex
Communication Protocol Modbus RTU
Input Supply Voltage 24 V DC (Nominal)
Country of Origin China (CN)
Customs Tariff Number 9031809090
Product Net Width 7.087 in (180 mm)
Product Net Height 5.31 in (135 mm)
Product Net Length 10.236 in (260 mm)
Gross Weight 1.372 kg

Connections/Interfaces

Interface Option Function / Assignment
Internal Termination Board Provides plug-in screw terminal blocks for field conductor routing.
Flame Relay Contacts Independent hardwired output for direct safety-critical integration with the BMS.
Analog Output Channel Current loop configuration representing real-time flame signal quality metrics.
RS485 Serial Interface Two-wire connection supporting remote parameter alignment and diagnostic data fetch over Modbus RTU.

Installation Guidelines

  • Unscrew the housing access cover to expose the integrated internal termination board for conductor assignment.
  • Wire the power supply and communication paths to the plug-in terminal blocks, using shielded twisted-pair cables for the 2-wire RS485 Modbus network to minimize transient noise.
  • Mount the device onto the burner sight pipe via its designated Line-of-Sight mechanical flange link, aligning the assembly directly with the target primary combustion zone.
  • Apply low-pressure purging air to the cooling jacket assembly if operating in high thermal environments to protect the solid-state sensor window from soot buildup and overheating.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB SF810I-LOS-UVIR-T Uvisor SF810i Multi Fuel Integrated Safe Flame Scanner

What does the integrated design approach mean for the device installation?

The integrated design combines both the optical sensor array and the signal processing board into a single enclosure, meaning no standalone remote evaluation unit or separate control cabinet module is required.

Which sensor technologies are embedded in this specific model?

The device features a dual solid-state configuration consisting of both Ultraviolet (UV) and Infrared (IR) sensors, allowing accurate flame discrimination on burners firing multiple fuel types.

How are field cables connected inside the scanner enclosure?

Field wiring is handled via an internal termination board that features plug-in terminal blocks, accessible by opening the heavy-duty housing cover.

What local data and network communication protocols does the device support?

The device provides native serial communication supporting the standard Modbus RTU protocol over a 2-wire half-duplex RS-485 interface.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
China

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...