1 de 1

Beckhoff ELX3314 EtherCAT Terminal 4-channel Analog Input Module

Beckhoff ELX3314 EtherCAT Terminal 4-channel Analog Input Module

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: ELX3314

  • País de origem:Alemanha

  • Tipo de Produto: EtherCAT Terminals

  • Pagamento: T/T, Western Union

  • Peso: 2000g

  • Dimensões: 12 mm x 100 mm x 68 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver informações completas

Designed for direct connection of thermocouples located in hazardous areas classified Zone 0/20, the Beckhoff ELX3314 processes four high-precision differential analog signals within an intrinsically safe Ex i EtherCAT architecture. This module enables direct temperature measurement from field sensors in explosive atmospheres without requiring additional external safety barriers, optimizing cabinet space and system integration.

Key Features

  • Intrinsically Safe (Ex i) Interfaces: Certified for direct connection to sensors located in Zone 0/20, Zone 1/21, and Zone 2/22 hazardous areas.
  • Multi-Thermocouple Support: Compatible with thermocouple types K, J, L, E, T, N, U, B, R, S, and C (Type K set as default).
  • High-Resolution Digitization: 16-bit analog-to-digital conversion delivering 0.1 degC per digit resolution.
  • Onboard Signal Processing: Integrated limit value monitoring, digital filtering, and sensor characteristic curve linearization.
  • Compact Form Factor: 12 mm housing width with integrated status LEDs for channel diagnostics and run/error states.

Industrial Applications

  • Chemical & Petrochemical Processing: Temperature monitoring of reactors, distillation columns, and storage vessels in hazardous zones.
  • Oil & Gas Refining: Thermal profiling of pipelines, extraction units, and processing facilities.
  • Pharmaceutical Manufacturing: High-precision temperature control in sterile, explosive solvent environments.
  • Combustion & Furnace Control: Direct exhaust gas and burner temperature measurement in hazardous industrial environments.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff
Model / SKU ELX3314
Number of Inputs 4 (differential)
Connection Method 2-wire
Measuring Range Sensor dependent (e.g., Type K: -270 to +1370 degC); Voltage: ±30 to ±75 mV
Resolution 0.1 degC per digit (16-bit)
Measuring Error < ±0.3% (relative to full scale value)
Internal Resistance typ. ≥ 10 kOhm (differential)
Input Filter Limit Frequency typ. 1 kHz (dependent on sensor length, conversion time, and sensor type)
Conversion Time 10 to 5000 ms (adjustable, default: 310 ms)
Supply Voltage Electronics 24 V DC (via power contacts, requires ELX9560 power supply)
Current Consumption Power Contacts typ. 10 mA
Current Consumption E-bus typ. 70 mA
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95%, non-condensing
Protection Rating IP20
Housing Material Polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Net Weight 60 g
Shipping Weight 2.00 kg

Wiring & Connection Specifications

Conductor Type Cross-Section (Metric) Cross-Section (AWG)
Solid Wire (s) 0.08 to 2.5 mm² AWG 28 to 14
Stranded Wire (st) 0.08 to 2.5 mm² AWG 28 to 14
Flexible Wire with Ferrule (f) 0.14 to 1.5 mm² AWG 26 to 16
Stripping Length 8 to 9 mm

Empirical Engineering Insights

Alternative Models & Compatibility

The ELX3314 requires the ELX9560 power supply terminal to feed the power contacts with the necessary intrinsically safe isolation. It cannot be mixed directly with standard non-Ex EL series terminals without the appropriate ELX9560 isolation barrier separating the power rails on the DIN rail assembly.

Application Pitfalls & Engineering Notes

When designing the physical layout, ensure the total current consumption on the E-bus (70 mA) and power contacts (10 mA) does not exceed the maximum output current of the upstream ELX9560 power supply terminal. Maintain strict physical separation between intrinsically safe (Ex i) field wiring and non-intrinsically safe wiring in the control cabinet.

Commissioning & Wiring Tips

Use shielded thermocouple extension wire and ground the shield at the entry point of the control cabinet. Configure the specific thermocouple type and conversion time (10 to 5000 ms) within TwinCAT System Manager to optimize noise rejection (default conversion time is 310 ms).

Installation Guidelines

CRITICAL WARNING: HAZARDOUS AREA SAFETY

De-energize the entire system before installing, removing, or wiring any ELX series terminal. Ensure compliance with local explosion protection regulations (EN 60079-14) and verify that the Ex i parameters of the connected thermocouple match the safety values of the ELX3314.

1

Mount the ELX9560 power supply terminal onto the 35 mm DIN rail (conforming to EN 60715) to establish the Ex i power segment.

2

Slide the ELX3314 terminal onto the DIN rail to the right of the power supply, ensuring the double slot and key connection locks securely with the adjacent module.

3

Strip the thermocouple field wires to 8–9 mm. Insert a flat-blade screwdriver into the spring release slot, insert the wire, and release to secure the connection.

4

Connect the EtherCAT network, apply 24 V DC power to the ELX9560, and verify that the run LED on the ELX3314 turns green.

Loading product navigation…

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...

Programando Ciclos de Movimento de Eixo Único em um Servo Drive CMZ

Este tutorial examina como a funcionalidade PLC integrada dentro de um servo drive CMZ SBD pode executar programas de movimento autônomos, incluindo lógica de referência, controle de posição e...