1 de 1

Módulo de Entrada Digital de 8 canais Beckhoff IP1012-B730 Fieldbus Box

Módulo de Entrada Digital de 8 canais Beckhoff IP1012-B730 Fieldbus Box

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: IP1012-B730

  • País de origem:Alemanha

  • Tipo de Produto: Módulos de Caixa Fieldbus

  • Pagamento: T/T, Western Union

  • Peso: 2000g

  • Dimensões: 30 mm x 175 mm x 26.5 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Decentralized digital signal acquisition in harsh production environments is managed via the Beckhoff IP1012-B730, a rugged IP67-rated Modbus fieldbus module featuring integrated screw-type connections. This distributed I/O device enables the direct acquisition of up to eight digital sensor signals near the process machinery, minimizing field cabling runs and reducing control cabinet footprint. Operating on the Modbus RTU/ASCII protocol over an RS485 transmission medium, it supports adjustable data transfer rates from 150 to 38,400 baud. Built with a high-durability polyamide housing, this fieldbus box is optimized for industrial installations requiring resistance to wet, dusty, or high-vibration environments without requiring an additional protective enclosure.

Features

  • 8 Digital Inputs: Accommodates standard 24 V DC sensors with an integrated 0.2 ms input filter to suppress signal contact bounce.
  • Modbus RTU/ASCII Interface: Multi-drop RS485 physical layer with a highly configurable address range using physical rotary switches.
  • Sub-Millisecond Response: Exceptionally fast internal processing with a tight 0.2 ms signal propagation and filtering pipeline.
  • Industrial Protection Class: Certified IP65, IP66, and IP67 ingress protection, safeguarding internal electronics against dust and direct water jets.
  • Robust M12/M8 Connections: Standardized thread connections ensure gas-tight, vibration-proof electrical contacts under extreme structural strain.

Applications

  • Conveyor and Material Handling Systems: Direct mounting on transport rails for proximity sensor, photoelectric gate, and limit switch integration.
  • Automotive Assembly Lines: Decentralized pneumatic valve monitoring and tooling sensor tracking in high-vibration robotic work cells.
  • Packaging and Food Processing Machinery: Splash-resistant field I/O placement for washdown-tolerant wash steps and sorting systems.
  • Municipal Water & Infrastructure: Distributed remote telemetry units for flow switches, pressure alerts, and valve status reporting over RS485.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Reference IP1012-B730
Protocol Support Modbus RTU / Modbus ASCII
Data Transfer Rates 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 baud
Number of Digital Inputs 8 channels
Nominal Input Voltage 24 V DC (-15% / +20%)
Input Filter Time 0.2 ms
"0" Signal Voltage -3 to +5 V DC (EN 61131-2, Type 2)
"1" Signal Voltage 11 to 30 V DC (EN 61131-2, Type 2)
Input Current Typical 6 mA per channel (EN 61131-2, Type 2)
Sensor Power Supply Max 0.5 A total (short-circuit proof) derived from control voltage
Power Supply Connections 1 x M8 male socket (4-pin feed), 1 x M8 female socket (4-pin downstream)
Box Current Consumption 45 mA (excluding sensor current load)
Electrical Isolation Control voltage to fieldbus: Yes; Channels to control voltage: No
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
Operating Temperature Range 0 to +55 degC
Storage Temperature Range -25 to +85 degC
Housing Material PA6 (Polyamide), non-reinforced
Physical Dimensions 30 mm x 175 mm x 26.5 mm (W x H x D)
Mounting Options 2 x 3.5 mm diameter fixing holes for M3 structural fasteners
Country of Origin Germany
Shipping Weight (Calculated) 2.0 kg (including export transit protective packaging)

Connections and Interfaces

Port Reference Connector Type Pin / Wire Allocation & Function
Bus Interface 1 x M12 socket, 5-pin, B-coded Modbus RS485 communication lines (TxD/RxD-A, TxD/RxD-B, Shield connection)
Digital Inputs (0-7) 8 x M12 screw type M12 input sockets mapping directly to 8 process image bits. Dedicated sensor voltage feed.
Power Feed 1 x M8 male connector, 4-pin Primary 24 V DC control voltage (Us) and peripheral load voltage (Up) supply input
Power Downstream 1 x M8 female connector, 4-pin Daisy-chain pass-through routing of Us and Up to subsequent downstream Fieldbus Box modules

Empirical Engineering Insights

Alternative Models & Compatibility

The IP1012-B730 belongs to the legacy Beckhoff Modbus RTU product line. When migrating or integrating this hardware into newer EtherCAT structures, you can use the EK1100 coupler combined with EL1008 terminals as an in-cabinet equivalent. If a direct IP67 field-mount form factor is required under an EtherCAT architecture, the EP1008-0002 serves as a drop-in physical equivalent, though it requires re-routing the communications protocol from Modbus RTU to EtherCAT.

Application Pitfalls & Engineering Notes

A common failure point in wet-field installations is localized internal condensation. While the PA6 polyamide housing holds an IP67 rating, this is only true if all unused M12 and M8 ports are sealed with industrial-grade protective caps tightened to the specified torque. Unprotected open threads will allow moisture ingress under temperature cycles due to pressure equalization, which can lead to premature logic-side failures.

Commissioning & Wiring Tips

When configuring the Modbus node address, ensure that you adjust the built-in rotary switches prior to powering up the system; the IP1012-B730 only reads the hardware switch address during the initial boot sequence. If using long RS485 trunk lines (approaching the 1200-meter maximum), always install an external 120-Ohm terminal resistor on the final downstream device's B-coded M12 interface to prevent signal reflections and packet collision errors.

Installation Guidelines

CRITICAL SAFETY WARNING Disconnect all primary control voltage and secondary load power sources before terminating or servicing any physical connectors. High transient fields or live connection actions can cause terminal arc flashover, disrupting the local communication bus and leading to potential hardware degradation on adjacent field devices. Verify zero voltage potential with an electrical tester prior to maintenance.
1

Position the fieldbus box on a flat mounting surface and secure it using two M3 bolts through the pre-drilled 3.5 mm structural mounting eyelets. Apply a maximum tightening torque of 0.8 Nm to prevent cracking the polyamide housing.

2

Set the network ID by removing the protective screw cap covering the rotary address switches. Carefully set the desired Modbus node value, then re-secure the cap tightly to maintain the IP67 physical rating.

3

Connect the B-coded M12 fieldbus cable to the dedicated network socket. For the final network node on the RS485 loop, install a dedicated 120-Ohm M12 termination plug.

4

Wire the M8 power connectors. Terminate the male feed connector first, followed by the downstream daisy-chain connector if cascading multiple modules. Keep total sensor current below the 0.5 A threshold.

Loading product navigation…

What is the total sensor power supply limit for the IP1012-B730?

The module provides a maximum total sensor supply current of 0.5 A across all eight channels. This supply is derived from the control voltage and features complete integrated short-circuit protection.

How do I set the Modbus node address on this device?

The address is set manually using the physical rotary address switches located beneath the protective screw cap. Note that the module only registers address changes upon a cold system reboot.

Can I use this module directly in an washdown environment?

Yes, the IP1012-B730 features an IP67-rated PA6 polyamide housing, making it highly resistant to dust and water jets. All unused ports must be sealed with threaded protective caps to preserve this rating.

What is the physical connection interface for the Modbus network?

The fieldbus network interfaces via a single 5-pin, B-coded M12 socket. It relies on a standard RS485 physical layer with baud rates configurable up to 38,400 baud.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...