Beckhoff KL6201 Bus Terminal AS-Interface Master Terminal

Beckhoff KL6201 Bus Terminal AS-Interface Master Terminal

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: KL6201

  • País de origem:Alemanha

  • Tipo de Produto: Bus Terminals

  • Pagamento: T/T, Western Union

  • Peso: 1000g

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Operating as a dedicated master interface between the internal K-bus backplane and actuator-sensor field networks, the Beckhoff KL6201 enables direct and seamless integration of AS-Interface (AS-i) networks into modular I/O configurations. This single-channel master module processes signals from both digital and analog AS-i slaves, converting field-level communication into K-bus protocols for processing by central controllers. The unit features selectable process image widths to balance data throughput and diagnostic feedback, offering an optimal network expansion interface for medium-to-large industrial control environments.

Features

  • Multi-Specification Compatibility: Supports AS-Interface specifications V2.0 and V2.1, ensuring compatibility with older and current slave generations.
  • Scalable Slave Capacities: Connects up to 31 slaves under V2.0 protocols or up to 62 slaves under V2.1 protocols.
  • Configurable Process Image: Selectable transmission widths of 12, 22, or 38 bytes, with 6 bytes reserved for parameter configuration.
  • Integrated Status Diagnostics: Continuous hardware-level diagnostics for power failures, slave communication drops, and configuration parameters.
  • Flexible Address Assignment: Auto-addressing capabilities directly through the control software interface or manual assignment via KS2000.
  • High Galvanic Isolation: Provides robust 500 V testing isolation between the internal K-bus and the external AS-i field lines.

Applications

  • Automated Conveyor Systems: Distributed sensor and actuator monitoring along long conveyor paths.
  • Pneumatic Valve Manifold Control: Interfacing multi-point industrial solenoid valves to central PLC networks.
  • Hazardous Area Demarcation: Deployment in explosive atmospheres when matched with specific ATEX-certified installation criteria.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Number KL6201
Technology Type AS-Interface Master
Number of Channels 1 AS-i channel
Specification Version AS-Interface V2.0, V2.1
Connected Slaves Capacity Up to 31 (V2.0) / up to 62 (V2.1)
Compatible Slave Types Digital and analog field slaves
Backplane Current Draw (K-bus) Typ. 55 mA
AS-Interface Power Consumption Typ. 60 mA
Cycle Time Max. 5 ms (for 31 connected devices)
Electrical Isolation 500 V (AS-Interface/K-bus backplane)
Power Contacts Through-Bus None (no passive power contact terminals)
Connection Technology 2-wire spring-force connection
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Approvals & Markings CE, UL, ATEX, AS-i Certificate (ZU-No. 125801)
Ex Marking II 3 G Ex nA IIC T4 Gc
Weight Approx. 55 g
Shipping Weight (Calculated) 1.00 kg

Connections and Interfaces

Terminal Connection Point Signal Assignment Functional Description
Terminal 1 AS-i + AS-Interface Positive Terminal (bridged internally to Terminal 5)
Terminal 2 AS-i - AS-Interface Negative Terminal (bridged internally to Terminal 6)
Terminal 3 Shield / FE Functional Earth Shielding connection point
Terminal 5 AS-i + AS-Interface Positive Extension link
Terminal 6 AS-i - AS-Interface Negative Extension link
Terminal 7 Shield / FE Functional Earth Shielding connection point

Empirical Engineering Insights

Alternative Models & Compatibility

The KL6201 shares an identical functional, electrical, and register map configuration with the KS6201. The key distinction lies in the physical hardware termination style: the KS series features a pluggable wiring header block, allowing swap-outs of the terminal block without needing to disconnect separate spring-tension wires. If your site undergoes frequent maintenance cycles or utilizes modular wiring harnesses, upgrading to the KS6201 represents a drop-in physical alternative with zero configuration updates required in the TwinCAT system manager.

Application Pitfalls & Engineering Notes

It is vital to recognize that the KL6201 does not pass power contacts through the module (it features no rear backplane spring power contacts). While it derives its control logic operating current (approx. 55 mA) directly from the K-bus, the actual AS-i bus field line requires excitation from an external, dedicated AS-i power supply (typically 30 VDC with integrated decoupling networks). Attempting to run the AS-i circuit off standard industrial 24 VDC switched power without the matching AS-i filter topology will induce communication noise and trigger constant parameterization and slave-loss diagnostic faults on the master.

Commissioning & Wiring Tips

When configuring the terminal in TwinCAT, selecting the 38-byte process image width is highly recommended if you deploy analog slaves. This avoids multiple-cycle delays when retrieving parameter files or large analog data arrays. If your network consists exclusively of high-speed digital logic, downgrade to the 12-byte map to minimize communication cycle overhead on the main fieldbus coupler (such as PROFIBUS or EtherCAT couplers). Ensure that the Functional Earth terminals (Terminal 3 and 7) are tied directly to a low-impedance ground plane to drain electromagnetic noise away from the AS-i data signal.

Installation Guidelines

CRITICAL WARNING

Isolate all electrical power sources (both the main PLC power supply and the auxiliary external AS-i power supply lines) before mounting, removing, or wiring the KL6201 module. Failure to de-energize circuits prior to physical insertion or extraction can cause capacitive arcing, permanently damaging the internal K-bus line drivers and corruption of adjacent terminal logic profiles.

1
Align the KL6201 on the standard DIN rail (35 mm) next to your Bus Coupler or existing terminal node sequence. Slide and press firmly until the lock release mechanism clicks securely over the DIN rail edge.
2
Ensure that the tongue-and-groove side interlocking tracks are correctly aligned with the adjacent terminals to secure reliable electrical connection through the backplane K-bus.
3
Insert a small flat-bladed screwdriver into the spring release slot, insert the stripped AS-i field wire (+ and -) into the corresponding terminal points (Terminal 1/5 and Terminal 2/6 respectively), and remove the tool to clamp the conductor securely.
4
Connect the functional earth shield wire to Terminal 3 or Terminal 7. Re-verify insulation and correct polarity alignments before energizing the system.
Loading product navigation…

Can the KL6201 operate without an external AS-Interface power supply?

No. The KL6201 requires an external, dedicated AS-i power supply (typically 30 VDC) connected directly to the field network loop. The K-bus connection only powers the logic components of the master module itself, not the field sensors or actuators.

What is the physical connection difference between the KL6201 and the KS6201?

The KL6201 uses fixed, vibration-resistant spring-force connection terminals. The KS6201 version features pluggable connection blocks, allowing the field-wiring block to be removed from the terminal base for quicker service swaps.

How do I clear a parameterization fault on the module?

Verify that your selected configuration byte size (12, 22, or 38 bytes) in TwinCAT matches the physical slave layout and profile on your actual AS-i bus. Incorrect parameter mapping or slave address collisions are the primary causes of this fault.

How many AS-i slaves can I connect to a single KL6201 master?

You can connect up to 31 slaves if utilizing the AS-Interface V2.0 specification, or up to 62 slaves under the extended V2.1 specification, assuming a mixture of compatible digital and analog devices.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...