Description

The Bently Nevada 140471-02 is an I/O module designed for dynamic pressure monitoring applications in the 3500 Machinery Protection System. The module processes signal inputs from high-temperature pressure transducers to perform signal conditioning and pass data to the 3500/64M main monitor board. Featuring internal termination wiring connections, the 140471-02 routes transducer signals, provides transducer power supplies, and outputs proportional +4 to +20 mA recorder signals for external control systems.

Features

  • Direct internal termination connections for 3-wire and 2-wire pressure transducer inputs
  • Integrated transducer power supply routing, providing -24 Vdc for 3-wire transducers and 3.3 mA current source at 22 Vdc nominal for 2-wire transducers
  • Support for 4-channel signal routing to the 3500/64M Dynamic Pressure Monitor
  • Dedicated terminal connections for 4 to 20 mA proportional recorder outputs per channel
  • Configurable internal jumpers for selecting 2-wire or 3-wire transducer field wiring configurations

Applications

  • Gas turbine combustion dynamic pressure monitoring
  • Hydro turbine dynamic pressure measurement
  • Reciprocating compressor cylinder dynamic pressure monitoring
  • Industrial machinery protection and condition monitoring

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Part Number 140471-02
Module Type I/O Module with Internal Termination
Compatible System Bently Nevada 3500 Series (3500/64M Dynamic Pressure Monitor)
Transducer Supplies (3-wire) -24 Vdc
Transducer Supplies (2-wire) 3.3 mA current source @ 22 Vdc (nominal)
Input Impedance (3-wire) 10 kΩ
Input Impedance (2-wire) 1.5 MΩ to 3.5 MΩ typical
Recorder Output Current +4 to +20 mA
Recorder Output Voltage Compliance 0 to +12 Vdc range across load
Recorder Output Load Resistance 0 to 600 Ω
Dimensions (H x W x D) 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Weight 0.20 kg (0.44 lb)

Connections/Interfaces

Terminal / Pin Function
PWR Transducer Power (+ / -24 Vdc supply)
COM/A Common / Signal Line A
SIG/B Signal / Line B
SHLD Cable Shield Connection
INHB Inhibit Control Input
RET1 Return / Reference Connection 1
COM Common Reference
REC1 Channel 1 Recorder Output (+4 to +20 mA)
REC2 Channel 2 Recorder Output (+4 to +20 mA)
REC3 Channel 3 Recorder Output (+4 to +20 mA)
REC4 Channel 4 Recorder Output (+4 to +20 mA)
SHIELD Main Earth Shield Termination

Installation Guidelines

  • Verify internal jumper positions for each channel pair (CH1/CH2 and CH3/CH4) match the connected transducer type (2-wire or 3-wire) prior to wiring.
  • Ensure field wiring is landed securely on the appropriate internal terminal block header (e.g., 8-position, 6-position, or push-in spring type headers).
  • Connect cable shields directly to designated SHLD/SHIELD terminals to maintain electromagnetic shielding performance.
  • Mount the module into the rear slot of the 3500 rack directly behind the corresponding 3500/64M monitor main board.

Compliance and Certifications

Certification / Standard Details
cNRTLus (without internal barriers) Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D; T4 @ Ta = -20degC to +65degC (-4degF to +149degF)
ATEX / IECEx (without internal barriers) II 3 G; Ex nA nC ic IIC T4 Gc; Ex ec nC ic IIC T4 Gc; T4 @ Ta = -20degC to +65degC (-4degF to +149degF)
EMC Directive 2014/30/EU; EN 61000-6-2, EN 61000-6-4
LV Directive 2014/35/EU; EN 61010-1
RoHS Directive 2011/65/EU
China RoHS EFUP 15 years per SJ/T 11364-2024
Maritime DNV GL rules for classification; ABS Rules Part 1
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 140471-02 I/O Module Internal Termination

Which monitor module does the unit connect to in the rack?

The module installs in the rear slot of the 3500 chassis directly behind the 3500/64M Dynamic Pressure Monitor main board.

How are field wiring configurations selected for 2-wire or 3-wire sensors?

Internal physical jumpers on the module board are positioned specifically for 2-wire or 3-wire operation across channel pairs.

What power supply voltage is provided for 3-wire pressure transducers?

The module delivers a nominal -24 Vdc power output directly to connected 3-wire transducers through the internal terminal block.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendemos mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Aceitamos devoluções de produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso site oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Color pattern
Branco Acinzentado
Country of origin
Estados Unidos
Power source
Energia CC

Produtos Visualizados Recentemente

Conhecimento técnico

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

Modernização das IHMs Bailey INFI 90 Symphony executadas no OpenVMS Alpha

Um guia prático para substituir estações de operação Bailey Symphony antigas que rodam no OpenVMS Alpha. Ele compara a emulação de Alpha, a migração para OpenVMS x86, a reimplantação em OPC e a...

Por que os dados de manutenção são essenciais para a confiabilidade industrial

Os dados de manutenção conectam ordens de serviço, sinais de sensores, histórico de ativos, custos e conhecimento dos técnicos. Quando bem utilizados, melhoram o planejamento, a confiabilidade, a...

Atuadores elétricos projetados para substituir sistemas de energia fluida: um guia prático de automação industrial

Este artigo explica como atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações matemáticas usando o OpenPLC para aplicações de automação industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas fundamentais, como adição, subtração, multiplicação, divisão, módulo e exponenciação, na automação industrial. Ele mostra como...