Description
The Bently Nevada 323174-01 is a high-performance, triple-redundant processing module designed for the 3701/55 ADAPT ESD Emergency Shutdown Device system. Operating as part of a standalone safety PLC, it serves as the core processing engine to execute safety critical logic for the emergency shutdown of rotating machinery, including steam, gas, and hydro turbines, expanders, and general process equipment. In a typical triple modular redundant (TMR) architecture, three processing modules operate in parallel to deliver exceptional system reliability and fault tolerance.
The 323174-01 module monitors an expansive array of 32 discrete inputs and 12 process variable analog inputs, ensuring all critical system variables are synchronized across the TMR framework. Each individual processing module directly handles two unique speed inputs, enabling a cumulative system capacity of six speed channels. Field-level application configurations are delivered securely via the Bently Nevada Monitor Configuration software. The module optimizes input-to-output logic solving with a 2ms nominal logic processing time and an 8ms relay toggle time, effectively minimizing the duration between an emergency event detection and system shutdown. Maintenance operations are simplified as all embedded firmware on the module can be fully upgraded without physical system disassembly.
Features
- Employs Triple Modular Redundancy (TMR) processing architecture to maximize machinery safety and uptime.
- Concurrently monitors and processes 32 discrete inputs and 12 analog inputs across all three CPU modules.
- Dedicated handling of 2 speed inputs per module, supporting up to 6 speed input channels per system.
- Includes redundant dual Ethernet interfaces on each CPU module to establish separate communication subnets.
- Supports a comprehensive logic capacity of up to 500 graphic logic blocks.
- High-speed decision execution providing 2ms nominal logic processing time and 8ms relay transition time.
- Field-upgradable embedded code allowing software maintenance without hardware disassembly.
- Equipped with onboard diagnostic LED indicators for module status, network activity, power, and alarm states.
Applications
- Steam Turbine Emergency Shutdown Systems
- Gas Turbine Protection and Overspeed Detection
- Hydro Turbine Safety Controls
- Industrial Turbo-Expanders
- Process Equipment Emergency Isolation and Safety PLC Interfacing
Ordering Information
| Part Number |
Description |
| 323174-01 |
ADAPT ESD CPU Module |
Technical Specifications
| Parameter |
Specification / Value |
| Manufacturer |
Bently Nevada (A Baker Hughes Company) |
| Module Type |
Processing Module (CPU) |
| Part Number |
323174-01 |
| System Compatibility |
3701/55 ADAPT ESD Emergency Shutdown Device |
| Logic Processing Blocks |
Up to 500 blocks |
| Nominal Logic Processing Time |
2 ms |
| Relay Toggle / Transition Time |
8 ms |
| Network Communication Ports |
2 Ports per CPU module (10/100 Mbps Ethernet, TCP/IP) |
| IP Addressing Protocols |
Static IP and DHCP |
| Time Synchronization |
NTP |
| Configuration Security |
Password Protected |
| Recorder Outputs |
Two internally powered 4-20 mA outputs per CPU module |
| Operating Temperature |
-30 degC to +65 degC (-22 Fahrenheit to +149 Fahrenheit) |
| Storage Temperature |
-45 degC to +85 degC (-49 Fahrenheit to +185 Fahrenheit) |
| Relative Humidity |
0% to 95% Non-condensing |
| Vibration Tolerance |
3 g @ 3-57 Hz (Per IEC 60068-1) |
| Mechanical Shock Resistance |
5 g @ 57-500 Hz (Per IEC 60068-1); 15 g for 11 ms Operational & Non-operational (Per IEC 60068-2) |
| Module Weight |
1.2 kg (2.6 lb) |
| Module Dimensions (L x W x H) |
15.8 x 6.1 x 15.8 cm (6.2 x 2.4 x 6.2 in) |
Installation Guidelines
Orientation and Clearance
The system terminal base must be mounted vertically with the power supply terminal exiting horizontally to guarantee proper heat dissipation. Maintain a minimum enclosure depth of nine inches (9 in).
Network Isolation
Configure the dual Ethernet ports of the module onto two independent subnets to create distinct, redundant data pathways.
Enclosure Protection
For environments containing condensing liquids, moisture, rain, or airborne particles, the system must be installed within an appropriately rated NEMA grade enclosure to safeguard internal hardware from overheating and thermal stress.
Grounding Connection
Grounding protocols must adhere strictly to Bently Nevada Application Note 013 when linking the chassis and system power supplies to earth ground.
Firmware Maintenance
Firmware adjustments and system modifications can be safely applied via network ports without unseating or disassembling the module from its chassis housing.
Compliance and Certifications
Functional Safety
Certified as a SIL 3 safety device under IEC 61508 Parts 1-7 and IEC 62061-1 standards.
Electrical Safety
CAN/CSA-C22.2 No. 61010-1-12, UL 61010-1, EU Low Voltage Directive 2014/35/EU, and EN 61010-1.
Electromagnetic Compatibility (EMC)
EU Directive 2014/30/EU, EU 61326-3-1, EN 61000-6-2, and EN 61000-6-4.
Hazardous Area Approvals
cNRTLus Class I, Zone 2: AEx nA nC IIC T4 Gc / Class I, Zone 2: AEx ec nC IIC T4 Gc / Class I, Division 2, Groups A, B, C, D (T4 @ Ta = -30 degC to +65 degC when installed per drawing 100M1872). ATEX/IECEx II 3 G Ex nA nC IIC T4 Gc / Ex ec nC IIC T4/T5 Gc.
Machinery Safety
EU Directive 2006/42/EC (Machinery Directive).
Maritime Applications
ABS 2009 Steel Vessels Rules.
Environmental & General Regulation
RoHS Directive 2011/65/EU and FCC Part 15 Class compliance.