1 de 1

IE2808 BECKHOFF 16-Channel High-Density Digital Output Extension Box

IE2808 BECKHOFF 16-Channel High-Density Digital Output Extension Box

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: IE2808

  • Country of origin:Alemanha

  • Product Type: Extension Box

  • Payment: T/T, Western Union

  • Weight: 500g

  • Dimensions: 30 mm x 126 mm x 26.5 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantidade
Ver informações completas

Product Overview

The IE2808 (IE2808) is a ruggedized, high-density Extension Box designed for decentralized I/O expansion in harsh industrial environments. Engineered for cabinet-free installation, this module provides 16 digital outputs in a compact IP67-rated polyamide housing. It is specifically designed to interface with Beckhoff Fieldbus Box modules via the high-speed IP-Link communication system. By utilizing a 25-pin D-sub connection for signal distribution, the IE2808 allows for the rapid connection of complex valve manifolds, indicator banks, or sensor-actuator clusters, making it a critical component for B2B applications in automotive assembly, robotic end-effectors, and food processing lines where space and wash-down resistance are mandatory.

Hardware Architecture and Power Management

The IE2808 architecture is optimized for space efficiency and reliable power distribution. It features two M8 connectors for power: one male socket for incoming feed and one female socket for downstream daisy-chaining of additional Extension Boxes. This "feed-through" design simplifies cabling in modular machine layouts.

With a total of 16 channels, the module supports a maximum sum current of 4 A ($\sum 4 A$), with each individual channel capable of delivering 0.5 A. The outputs are designed to handle ohmic, inductive, and lamp loads, and are individually short-circuit proof. A sophisticated error-handling protocol is integrated, where a fault on any channel must be acknowledged by the master controller (PLC) before the output can be reactivated, ensuring that mechanical faults are addressed before system operation resumes.

Technical Specifications

Attribute Specification Details
Model IE2808
Brand BECKHOFF
Number of Outputs 16 Channels
Output Connection 25-pin D-sub socket (UNC4-40)
Nominal Voltage 24 V DC (-15 % / +20 %)
Max Output Current 0.5 A per channel
Sum Current ($\sum$) Max. 4.0 A
Short-Circuit Current Max. 1.5 A
Power Connection 2 x M8 (Male Feed / Female Downstream)
Communication IP-Link (via Coupling Box)
Protection Rating IP65 / IP66 / IP67
Operating Temperature 0 to +55 Celsius
Dimensions (W x H x D) 30 mm x 126 mm x 26.5 mm
Material PA6 Polyamide

Technical FAQs

How do the diagnostics work on the IE2808?

The module optionally provides a 16-bit input process image dedicated to diagnostics. This allows the TwinCAT master to monitor each output for short circuits or overloads. If a fault occurs, the corresponding diagnostic bit is set, and the master must send a fault acknowledgement to clear the error.

What is the benefit of the D-sub 25 connection?

The 25-pin D-sub allows for the consolidation of 16 signals into a single shielded cable. This is significantly more space-efficient than using 16 separate M8 or M12 connectors, which is essential for high-density end-of-arm tooling on robots or small-scale machine modules.

Does this module require a Coupler Box to function?

Yes. As an Extension Box, the IE2808 does not connect directly to a Fieldbus (like EtherCAT or Profibus). It must be connected to a Fieldbus Box (Coupler) via the IP-Link fiber optic or copper connection to be visible on the control network.


Engineering & Installation Guide

  • Sealing and IP Rating: To maintain the IP67 rating, ensure that the 25-pin D-sub connector is fitted with a sealed industrial hood. Any unused M8 power sockets must be capped with the appropriate protective plugs to prevent moisture and dust ingress.

  • Current Limitation Planning: While each channel can handle 0.5 A, the total current for the module cannot exceed 4 A. When designing your load distribution, ensure that the simultaneous switching of all 16 channels does not exceed this 4 A thermal limit to prevent internal overheating.

  • Mechanical Mounting: The housing features two 3.5 mm holes for M3 mounting screws. Install the module on a flat, vibration-resistant surface. The PA6 polyamide material is highly resistant to chemical agents, but avoid over-torquing the mounting screws to prevent stress fractures in the plastic.

Engineering Advantages

The IE2808 is a premier choice for "on-machine" I/O expansion. Its slim 30 mm width and low-profile design allow it to be tucked into machine frames where standard I/O blocks would not fit. The electrical isolation between the control voltage and the fieldbus (via IP-Link) ensures that electrical noise from high-power field actuators does not interfere with the master control communication. With high vibration and shock resistance (conforming to EN 60068-2-6/27), the IE2808 is built for the physical rigors of 24/7 industrial production, providing a reliable, high-density output solution that maximizes machine uptime.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Preto
Country of origin
Alemanha
Power source
Energia CC

Recently Viewed Products

Technical knowledge

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...

Programando Ciclos de Movimento de Eixo Único em um Servo Drive CMZ

Este tutorial examina como a funcionalidade PLC integrada dentro de um servo drive CMZ SBD pode executar programas de movimento autônomos, incluindo lógica de referência, controle de posição e...

Configuração de Controle de Movimento de Eixo Único com Drives Servo CMZ

Este tutorial explora a comissionamento de um sistema de movimento servo de eixo único usando um drive CMZ SBD, abrangendo a configuração de hardware, escala do eixo, configuração de homing e...