1 de 1

BECKHOFF EL3062-0030 EtherCAT Terminal 2-channel Analog Input Terminal

BECKHOFF EL3062-0030 EtherCAT Terminal 2-channel Analog Input Terminal

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: EL3062-0030

  • País de origem:Alemanha

  • Tipo de Produto: Analog Input Terminals

  • Pagamento: T/T, Western Union

  • Peso: 1500g

  • Dimensões: 10 cm x 1.5 cm x 7 cm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Processing standard single-ended analog signals in industrial automation systems is efficiently handled by the EL3062-0030. This robust analog input terminal operates within the 0 V to +10 V voltage range, digitizing incoming signals with a high-performance 12-bit resolution for transmission to the master control system. Engineered for seamless integration with the Beckhoff EtherCAT Terminal system, it combines high-speed communication via the internal E-bus with galvanic safety features. Compact and highly reliable, it is ideal for standard control applications requiring fast, noise-immune signal acquisition.

Features

  • Dual single-ended analog inputs configured for 0 V to +10 V signal ranges.
  • Digitization resolution of 12 bits with a 16-bit representation format.
  • Typical conversion time of 0.625 ms using the default 50 Hz internal filter.
  • Galvanic electrical isolation rated at 500 V between the E-bus and the field circuit.
  • Integrated 1 kHz input limit filter for high-frequency noise suppression.
  • Excellent electromagnetic compatibility complying with industrial emission and immunity standards.

Applications

This 2-channel analog input terminal is widely implemented across heavy industrial and manufacturing environments, including:

  • Machine control and process automation.
  • Continuous monitoring of industrial sensors and transmitters.
  • Factory automation lines requiring reliable 0-10 V analog data acquisition.
  • Test bench and laboratory instrumentation setups.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model EL3062-0030
Product Type 2-channel Analog Input Terminal
Number of Inputs 2 (single-ended)
Signal Voltage Range 0 V to +10 V
Internal Resistance > 130 kOhm
Resolution 12 bit (16 bit presentation)
Conversion Time Typical 0.625 ms (default 50 Hz filter setting)
Input Filter Limit Frequency 1 kHz
Measuring Error (Full Range) < ± 0.30% (at 0 degC to +55 degC, relative to full scale); < ± 0.5% (extended temperature range)
Current Consumption via E-Bus Typical 130 mA
Electrical Isolation 500 V (E-bus / field voltage)
Dielectric Strength Max. 30 V
Permissible Relative Humidity 95%, non-condensing
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Class IP20
Dimensions (H x W x D) Approx. 10 cm x 1.5 cm x 7 cm
Shipping Weight 1.5 kg

Installation Guidelines

For safe and optimal performance of the terminal block, adhere to the following installation standards:

  • DIN Rail Mounting: Snap the terminal securely onto a standard 35 mm DIN rail (EN 60715). Ensure the locking mechanism engages properly with adjacent terminals.
  • Shielding and Grounding: To minimize high-frequency electromagnetic interference, use shielded signal cables and connect the shield directly to the mounting rail or grounding terminal.
  • Environmental Protection: Ensure the installation enclosure provides an IP54 or higher rating if operating in harsh, dust-heavy, or wet industrial environments, as the module itself is rated IP20.
  • Ventilation: Maintain standard vertical clearance above and below the terminal assembly to prevent thermal buildup and ensure reliable operation.

Compliance and Certifications

  • CE
  • EN 61000-6-2 (Electromagnetic compatibility - Immunity for industrial environments)
  • EN 61000-6-4 (Electromagnetic compatibility - Emission standard for industrial environments)

What is the signal voltage range of the Beckhoff EL3062-0030?

The EL3062-0030 analog input terminal accepts single-ended signals ranging from 0 V to +10 V.

What is the electrical isolation capability of this terminal?

It provides galvanic electrical isolation of up to 500 V between the internal E-bus and the external field voltage.

Does the EL3062-0030 include input filtering?

Yes, it features an integrated input filter with a limit frequency of 1 kHz and a default 50 Hz filter configuration.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...