1 de 1

Omron E5AC-RX2ASM-000 E5AC Series Digital Temperature Controller

Omron E5AC-RX2ASM-000 E5AC Series Digital Temperature Controller

Apenas 2 item(ns) restante(s) em estoque
  • Fabricante: Omron

  • Nº do Produto: E5AC-RX2ASM-000

  • País de origem:Japão

  • Tipo de Produto: Digital Temperature Controllers

  • Pagamento: T/T, Western Union

  • Peso: 3000g

  • Dimensões: 120 mm x 120 mm x 110 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Managing thermal profiles with high precision, the Omron E5AC-RX2ASM-000 serves as a high-density, 1/4 DIN process controller engineered for demanding industrial environments. This unit integrates a high-contrast, white PV display with a fast 50 ms sampling rate to deliver rapid, reliable closed-loop control. Designed for standard panel-mount configurations, it accommodates universal sensor inputs and features dual relay outputs to handle primary control loops and critical process alarms without requiring auxiliary transmitter modules.

Features

  • High-Visibility White LCD Display: 25 mm high process value characters offer exceptional legibility from long distances and wide viewing angles.
  • Ultra-Fast Sampling Rate: 50 ms sampling period provides the response speed required for rapid temperature fluctuations in dynamic thermal processes.
  • Universal Sensor Input: Direct connection support for thermocouple, platinum resistance thermometer (Pt100/JPt100), and analog current/voltage signals.
  • Dual Auxiliary Relay Outputs: Two independent SPST-NO auxiliary outputs configurable for alarms, safety interlocks, or event states.
  • Compact Shallow Depth: A 60 mm depth behind the front panel minimizes spatial requirements inside space-constrained electrical cabinets.

Applications

  • Plastic extrusion systems and injection molding equipment temperature zones.
  • Industrial heat-treating furnaces, ovens, and ceramic kilns.
  • High-speed packaging machinery sealing bars and hot-melt adhesive applicators.
  • Environmental simulation chambers and biological incubation systems.

Technical Specifications

Specification Parameter Technical Value
Manufacturer Omron
Model / SKU E5AC-RX2ASM-000
Front Panel Size 96 x 96 mm (1/4 DIN)
Supply Voltage 100 to 240 VAC, 50/60 Hz
Power Consumption 9.0 VA max.
Control Output 1 Relay output (SPST-NO, 250 VAC, 3 A resistive load)
Control Output 2 None
Auxiliary Outputs 2 SPST-NO relays (250 VAC, 2 A resistive load)
Input Sensor Compatibility Thermocouple (K, J, T, E, L, U, N, R, S, B, W, PL II), RTD (Pt100, JPt100), Analog (4-20 mA, 0-20 mA, 1-5 V, 0-5 V, 0-10 V)
Sampling Period 50 ms
Control Method ON/OFF control or 2-PID control (with auto-tuning)
Terminal Connection Screw terminal block (M3) with integrated terminal cover
Operating Temperature -10 to 55 degC (no icing or condensation)
Country of Origin Japan
Shipping Weight (Calculated) 0.45 kg
Package Dimensions (Calculated) 120 mm x 120 mm x 110 mm

Terminal Map and Interface Assignments

Terminal Number Functional Circuit Assignment
1 & 2 Operating Power Supply Input (100 to 240 VAC, non-polarized)
3 & 4 Control Output 1 (Relay, SPST-NO)
7 & 8 Auxiliary Output 1 (Relay, SPST-NO)
9 & 10 Auxiliary Output 2 (Relay, SPST-NO)
21, 22, 23 Universal Sensor Input (RTD Phase A/B/B' or TC / Voltage / Current)

Empirical Engineering Insights

Alternative Models & Compatibility

The E5AC-RX2ASM-000 is a direct 1/4 DIN successor to legacy E5AN models. Unlike older iterations, this unit features a drastically reduced panel-mount depth of 60 mm, allowing installation in shallow enclosures. Note that while its parameter structure is highly aligned with legacy platforms, register map shifts may require verification if adapting existing Modbus communication loops via external gateways.

Application Pitfalls & Engineering Notes

When utilizing the integrated 50 ms fast sampling mode, high-frequency electromagnetic fields from surrounding variable frequency drives (VFDs) can cause sensor value jitter or premature sensor-break errors (S.ERR). To prevent unstable process feedback, the input digital filter parameter (dFL) should be incrementally increased from the default 0.0 seconds to approximately 1.0 or 2.0 seconds in electrically noisy environments.

Commissioning & Wiring Tips

For initial thermal commissioning, configure the controller’s auto-tuning (AT) command only after the system has stabilized at room temperature. Executing auto-tuning from a hot state may cause the controller to calculate inaccurate PID gains, leading to cyclic overshoot. If wiring thermocouple inputs, always use the matching alloy-compensated extension wire directly to terminals 21 and 22 to prevent secondary cold-junction errors.

Installation Guidelines

CRITICAL WARNING: De-energize all primary and auxiliary power lines before commencing installation or terminal wiring. Do not touch terminal screws 1 and 2 while mains power is active. Failure to strictly follow electrical isolation protocols can result in severe shock hazard, equipment destruction, or unexpected process startup.
1
Insert the E5AC process controller directly through the standard 92 mm x 92 mm panel cutout from the front of the electrical panel.
2
Slide the two mounting adapters over the top and bottom of the unit casing from behind the panel until they click firmly into place against the inner panel face.
3
Wire the input sensor using shielded pair cables to terminals 21-23, ensuring shield drain wire is properly grounded only at the system's single star-ground point.
4
Secure the power supply (100 to 240 VAC) to terminals 1 and 2, verify connection tightness to a torque of 0.43 to 0.58 N-m, and snap on the safety terminal cover.
Loading product navigation…

What does the 'S.ERR' code indicate on the E5AC controller's display?

An 'S.ERR' (Sensor Error) indicates that the input sensor signal is broken, disconnected, or wired with incorrect polarity. Check the connections at terminals 21 and 22, and verify that the selected input type parameter (CN-t) matches the physical sensor connected.

Does this model support Modbus RS-485 serial communication?

The base E5AC-RX2ASM-000 model does not include RS-485 serial communication options out of the box. Serial communications require optional auxiliary boards or specialized suffix models featuring communication terminals.

What is the contact rating for the auxiliary outputs on this temperature controller?

The two auxiliary relay outputs on this unit are rated for a maximum resistive load of 2 A at 250 VAC. Inductive loads should utilize external suppression networks or interposing relays to protect the internal contacts from wear.

Can this unit be configured for cooling-only or dual heating/cooling control?

Yes, the controller supports heating/cooling control. However, since this unit has only one physical control output (Relay Output 1), the cooling control must be assigned to one of the auxiliary relay outputs via internal parameter routing.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Japão

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...