Integrating high-speed motion and sequence control into a unified database engine, the Omron NJ301-1100 serves as a high-performance central processing unit within the Sysmac NJ automation platform. This controller is designed to manage up to 4 synchronized axes and up to 15 total axes (including virtual), making it highly suitable for compact to mid-sized machine automation projects. Operating with a rapid 0.5 ms primary task cycle time and featuring 2.5 MB of variables memory, the unit ensures responsive, deterministic execution of complex logic and motion profiles. Standard built-in communication interfaces include EtherCAT Master, EtherNet/IP, and USB, facilitating seamless vertical integration and robust field-level device communication.

Features

  • Unified Control Engine: Integrates logic, motion, and vision control into a single, synchronized processor.
  • Multi-Axis Management: Supports precise control of 4 synchronized physical axes and up to 15 total axes.
  • High-Speed Execution: Delivers a consistent, deterministic 0.5 ms primary task cycle time.
  • Flexible Expansion: Connects directly to CJ-series I/O modules via the built-in CJ I/O Bus, supporting up to 40 expansion units.
  • Robust Connectivity: Equipped with onboard EtherCAT and EtherNet/IP ports for synchronized device networks and enterprise-level factory integration.

Applications

  • Primary packaging and cartoning systems requiring coordinated multi-axis motion.
  • Pick-and-place assembly stations utilizing delta or SCARA robotics.
  • Automated material handling, sorting systems, and conveyor line control.
  • High-speed test stands requiring deterministic sensor-to-actuator latency.

Technical Specifications

Parameter Specification
Manufacturer Omron
Model / SKU NJ301-1100
Controller Series Sysmac NJ3
Functional Capabilities Motion Control, Sequence Control
Synchronous Axes (Max) 4
Total Axes (Max, incl. Virtual) 15
Primary Task Cycle Time 0.5 ms
Variables Memory Capacity 2.5 MB
Onboard Communication Ports EtherCAT Master, EtherNet/IP, USB (Type-B)
Local Expansion Bus System CJ I/O Bus (Supports up to 40 expansion units)
Remote I/O Node Capacity Up to 192 nodes
Unit Dimensions (L x W x H) 90 mm x 90 mm x 90 mm
Unit Weight 530 g (0.53 kg)
Shipping Weight (Calculated) 2.00 kg

Connections and Interfaces

Port / Interface Physical Connector Function / Assignment
EtherCAT Port RJ45 (Shielded) Real-time network master for servo drives, variable speed drives, and remote I/O terminal modules.
EtherNet/IP Port RJ45 (Shielded) Host communications, programming, HMIs, peer-to-peer PLC data exchange, and tag data link connections.
USB Port USB 2.0 Type-B Direct local connection point for Sysmac Studio engineering software.

Empirical Engineering Insights

Alternative Models & Compatibility

The NJ301-1100 CPU integrates legacy CJ-series physical form factors while running the modern Sysmac NJ firmware architecture. Note that while CJ-series I/O modules are physically compatible and mount directly on the local bus, they must be registered in the Sysmac Studio configuration tool rather than legacy CX-Programmer. Programs developed for CJ1/CJ2 PLCs cannot be directly downloaded and must undergo conversion within Sysmac Studio before execution.

Application Pitfalls & Engineering Notes

When utilizing the CJ I/O Bus expansion units alongside high-density communication modules or high-current analog units, calculate the total current consumption across the internal 5 VDC and 24 VDC rails carefully. Ensure your chosen Power Supply Unit (PSU) can supply the calculated current. Also, maintain a minimum of 20 mm clearance above and below the rack assembly to permit adequate convective cooling; failures to provide sufficient thermal headroom can lead to localized heat buildup and memory corruption or watchdog errors.

Commissioning & Wiring Tips

Always use Category 5e (or better) Double-Shielded Twisted Pair (STP) cables for both EtherCAT and EtherNet/IP connections. To prevent ground-loop noise on the communication lines, ground the functional ground (FG) terminal of the power supply unit and CPU rack using a heavy-gauge conductor tied to a dedicated low-resistance grounding block (less than 100 ohms). Verify that the EtherCAT cable shields make complete, continuous contact with the RJ45 metallic shell connectors.

Installation Guidelines

CRITICAL WARNING

Disconnect all electrical supply sources before physically mounting, wiring, or swapping any components. Never insert or extract CJ-series I/O modules from the system bus while the CPU is powered on. Failure to comply can damage the internal bus drivers of both the CPU and adjacent expansion modules.

1

Mount the CPU unit and adjacent power supply module firmly to standard 35 mm DIN rail or directly to the backplane panel using the integrated mounting brackets.

2

Slide the side connectors together until the locks click into place, securing the CPU module to the power supply unit on its left and any CJ-series modules on its right.

3

Terminate the industrial communication network cables in their dedicated RJ45 ports (EtherCAT and EtherNet/IP), ensuring appropriate strain relief and shielding configurations.

4

Connect the main functional ground to the dedicated rack ground lug, then apply primary supply voltage and verify successful boot sequences via the LED diagnostics on the front faceplate.

Loading product navigation…

Can I use standard CJ-series I/O units directly with the NJ301-1100 CPU?

Yes, the NJ301-1100 features a built-in CJ I/O Bus on its backplane, allowing you to connect and configure up to 40 CJ-series expansion units directly within Sysmac Studio.

What is the maximum number of synchronized motion axes this CPU can control?

The CPU supports a maximum of 4 synchronized physical axes, and up to 15 total axes including virtual axes, configured via the integrated EtherCAT master port.

Which software platform is used to program the NJ301-1100?

The NJ301-1100 is configured, programmed, and debugged exclusively using Omron's Sysmac Studio software platform; it is not compatible with CX-Programmer.

Does the NJ301-1100 require a memory card to run programs?

No, user program and configuration data are retained in internal non-volatile memory. However, an SD memory card can be used for backup, restore, and logging tasks.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Japão

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...