1 из 4

ABB PM865K01 3BSE031151R1 AC 800M High Integrity Processor Unit

ABB PM865K01 3BSE031151R1 AC 800M High Integrity Processor Unit

Остался только 6 товар(ы) на складе
  • Производитель: ABB

  • Номер продукта: PM865K01 3BSE031151R1

  • Страна происхождения:Швеция

  • Тип продукта: Processor Unit

  • Штрихкод: 8537101190

  • Оплата: Т/Т, Western Union

  • Вес: 1200г

  • Размеры: 119 mm x 186 mm x 135 mm

  • Порт отгрузки: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

The ABB PM865K01 (Product ID: 3BSE031151R1) is a high-integrity central processing unit package engineered for the AC 800M hardware platform. It is certified for use in safety-critical applications up to Safety Integrity Level 3 (SIL3) in accordance with IEC 61508. Operating at 96MHz with 32MB of onboard memory, this processor unit serves as a highly robust control solution capable of running both non-SIL and SIL-classified applications simultaneously when deployed within an AC 800M High Integrity controller configuration.

The PM865K01 provides advanced internal diagnostics, enhanced oscillator supervision, and integrated double over-voltage protection on internal voltages. To comply with strict international safety standards, the module utilizes a dedicated monitoring architecture that requires configuration according to the official ABB Safety Manual. It facilitates expansive industrial connectivity through its built-in electrical and optical ModuleBus interfaces, alongside dual RJ45 Ethernet ports for highly available control network communications.

Features

  • Safety Integrity Level Certification: Fully qualified for SIL3 safety-critical installations when configured with an SM811 safety module.
  • High-Performance Architecture: Equipped with a 96MHz microprocessor and 32MB of robust system and user RAM.
  • Advanced Diagnostics: Built-in hardware-driven double inverted memory handling for real-time bit error detection without cycle delay.
  • Electrical Safety: Integrates double over-voltage protection on internal supply lines and enhanced system watchdog timers.
  • Flexible Communication Expansion: Built-in CEX-Bus interface allows for step-by-step expansion using various fieldbus protocols.
  • Bumpless Redundancy: Supports hot stand-by processor redundancy via an RCU Link, enabling fault changeover in less than 10 ms.
  • Robust Mechanics: Features a slide-and-lock mechanism for secure DIN-rail installation and direct chassis grounding.

Applications

  • Safety Instrumented Systems (SIS): Emergency Shutdown (ESD) and fire and gas protection systems.
  • Distributed Control Systems (DCS): Continuous process control loop operations across large-scale industrial plants.
  • High-Integrity Automation: Critical infrastructure management requiring simultaneous execution of control and safety functions.
  • Boiler and Burner Management Systems (BMS): Safe sequencing and combustion monitoring for heavy utility boilers.

Ordering Information

The PM865K01 product package includes the following verified hardware components:

Item / Model Product ID Component Description
PM865 3BSE031151R1 Safety CPU, 96MHz, 32MB (No license included)
TP830 Baseplate Unit
TB850 CEX-bus Terminator (Male)
TB807 ModuleBus Terminator Plug
TB852 RCU-Link Terminator Plug
4943013-6 Lithium battery for memory backup

Technical Specifications

Parameter Specification
Manufacturer ABB
Product ID 3BSE031151R1
ABB Type Designation PM865K01
Processor Speed 96MHz
Onboard Memory 32MB
Product Net Width 119 mm
Product Net Height 186 mm
Product Net Depth / Length 135 mm
Product Net Weight 1.2 kg
Battery Type Portable Lithium (9 g weight)
Protection Class IP20
Maximum Operating Temperature 40 degC (ambient outside enclosure)
RoHS Compliance Not RoHS 2 2011/65/EU compliant (Spare part rules apply)

Connections/Interfaces

CN1 and CN2 Control Network Ports

Connector Pin Function Description
1 TD+ Transmit Data (plus)
2 TD- Transmit Data (minus)
3 RD+ Receive Data (plus)
4-5 Not used Leave disconnected
6 RD- Receive Data (minus)
7-8 Not used Leave disconnected
Housing Shield Chassis ground connection

COM3 Serial Port (RS-232C with Modem Control)

Connector Pin Function Description
1 RTS Request To Send
2 DTR Data Terminal Ready
3 TD Transmit Data
4 0V Signal ground
5 0V Signal ground
6 RD Receive Data
7 DCD Data Carrier Detect
8 CTS Clear To Send
Housing Shield Chassis ground connection

Installation Guidelines

  • DIN-Rail Mounting: Install horizontally onto a top-hat type TS 35/7.5 DIN-rail. Rotate the baseplate locking device counter-clockwise to the OPEN position before clipping onto the rail.
  • Slide & Interconnect: Once hooked over the upper edge of the rail, move the locking device to the SLIDE position. Slide the module sideways to align carefully and mate its baseplate connectors with adjacent units. Ensure strict pin alignment to prevent physical structural damage.
  • Grounding: Lock the unit into place by turning the locking screw clockwise to the LOCKED position. This engages the internal grounding mechanism firmly against the unpainted metal surface of the DIN-rail.
  • Power Supply Wiring: Connect the 24V DC lines into the screw terminals of the baseplate. To suppress unexpected errors from monitoring links when a single supply is utilized, jump input terminals SA and SB on the unit directly to +24 V DC.
  • Battery Handling: Do not plug the internal lithium battery into its respective slot until the controller has fully powered up normally and the active battery LED begins to flash. Inserting the battery into a powered-down module will instantly exhaust its cell power.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB PM865K01 3BSE031151R1 AC 800M High Integrity Processor Unit

Loading PDF, please wait…

Can the local electrical ModuleBus be utilized in a redundant processor layout?

No. When running in a redundant CPU configuration, the electrical ModuleBus built into the baseplate cannot be used. All S800 I/O connections must interface through the optical ModuleBus via cluster modems.

What is the purpose of the TB852 plug included in the PM865K01 kit?

The TB852 is an RCU Link Termination plug. It must be installed into the RCU Link connector whenever the processor module is deployed in a single (non-redundant) controller configuration.

Why shouldn't I insert the backup battery before powering up the processor?

If the backup battery is placed into the holder before a normal external 24V DC supply is turned on, the CPU memory circuits will immediately begin draining the battery, significantly limiting its field lifespan.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской запечатанной упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашим официальным Политика возврата и возврата средств .

TECHNICAL SPECIFICATIONS

Color pattern
Белый
Country of origin
Швеция
Power source
Постоянный ток (DC)

Недавно просмотренные товары

Технические знания

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий (OT), защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От клеевых систем, вдохновленных гекконами, и мягких захватов пищевого класса до инструментов на базе ИИ...

Воспоминание: как ранние электродвигатели изменили подземную добычу полезных ископаемых

От компрессоров с приводом от каната до аккумуляторных вагонеток — ранние горные работы стали поворотным моментом в индустриальной электрификации. В этой статье рассматривается, как электродвигатели...

Factory I/O: современный инструмент моделирования ПЛК для обучения промышленной автоматизации

Factory I/O меняет обучение ПЛК, предоставляя погружающие 3D промышленные симуляции для студентов, инженеров и команд технического обслуживания. Платформа сокращает разрыв между теорией и практикой...

Программирование циклов одноосевого движения на сервоприводе CMZ

В этом руководстве рассматривается, как встроенный ПЛК внутри серводрайвера CMZ SBD может выполнять автономные программы движения, включая логику поиска нуля, позиционное управление и циклическое...