Description

Processing analog signals directly in harsh field environments is simplified with the EP3162-0002 EtherCAT Box. This IP67-rated decentralized module features two highly flexible, galvanically isolated analog inputs that are software-parameterizable for either voltage (-10/0 to +10 V) or current (-20/0/4 to +20 mA) signals on a per-channel basis. By executing analog-to-digital conversion directly at the sensor location, this module minimizes signal degradation over long wire runs, enabling clean 16-bit measurement resolution across distributed fieldbus networks.

The device features dual-channel isolation to eliminate ground loop issues, making it highly reliable in electrically noisy industrial applications. Connectivity is facilitated through robust, industry-standard M12 connectors for the sensor lines and M8 connectors for the EtherCAT fieldbus and power supply daisy-chaining. With integrated Distributed Clocks (DC) support, the module guarantees precise, synchronized data acquisition across large-scale industrial machinery.

Features

  • Two single-ended, individually parameterizable analog input channels.
  • Supports standard industrial signal ranges: -10 to +10 V, 0 to 10 V, -20 to +20 mA, 0 to 20 mA, and 4 to 20 mA.
  • Complete galvanic isolation between individual input channels for high signal integrity.
  • Fast analog-to-digital conversion time of approximately 100 microseconds per channel.
  • High-precision 16-bit digital resolution (including sign).
  • Distributed Clocks (DC) support for high-fidelity clock synchronization in time-critical tasks.
  • Rugged IP65/66/67 physical housing for direct mounting outside of control cabinets.

Applications

  • Decentralized process instrumentation and sensor monitoring in heavy industrial plants.
  • Hydraulics and pneumatic system pressure, flow, and temperature tracking.
  • Machine-mount data acquisition systems in automotive assembly and packaging lines.
  • Test bench environments requiring high-speed, synchronized analog measurements.

Technical Specifications

Manufacturer Beckhoff Automation
Part Number / Model EP3162-0002
Product Type EtherCAT Box (Analog Input)
Number of Inputs 2 single-ended (galvanically isolated channels)
Signal Type (Voltage) -10/0...+10 V (parameterizable per channel)
Signal Type (Current) -20/0/4...+20 mA (parameterizable per channel)
Resolution 16 bit (including sign)
Internal Resistance > 200 kOhm (voltage) | typ. 85 Ohm + diode voltage (current)
Measurement Error < ±0.3% (relative to full scale value)
Conversion Time ~ 100 microseconds
Input Filter Limit Frequency 5 kHz
Bus Interface Connection 2 x M8 socket, shielded, screw-type
Input Connection Method M12 x 1, 5-pin, A-coded
Nominal Supply Voltage 24 V DC (-15% / +20%)
Power Connection Feed: 1 x M8 male (4-pin); Downstream: 1 x M8 female (4-pin)
Current Consumption (Us) 120 mA
Sensor Supply Us derived from auxiliary voltage, electrically isolated
Electrical Isolation 500 V (fieldbus to signal), 300 V (signal to signal)
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Weight approx. 165 g
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27

Connections and Interfaces

M12 Pin Connection Signal Assignment
Pin 1 +24 V DC Sensor Supply (Us)
Pin 2 Analog Input + (Voltage / Current)
Pin 3 GND Sensor Supply (Us)
Pin 4 Analog Input -
Pin 5 Shield / Functional Earth

Installation Guidelines

  • Mounting: Screw the module directly onto flat machine surfaces using the integrated mounting holes. Ensure the mounting plane is grounded.
  • Shielding: Use fully shielded M12 sensor cables and shielded M8 EtherCAT cabling to preserve signal integrity and prevent electromagnetic interference (EMI).
  • Power Daisy Chaining: When utilizing the downstream M8 power output, verify that the total current draw of downstream modules does not exceed the maximum power bus capacity.
  • Sealing: Unused M12 and M8 ports must be sealed with appropriate IP67 protection caps to maintain environmental integrity.

Compliance and Certifications

  • CE
  • UL
Loading product navigation…

Can the EP3162-0002 measure both voltage and current on different channels simultaneously?

Yes, each of the two analog input channels on the EP3162-0002 can be independently parameterized via TwinCAT software. One channel can be set for voltage measurements (e.g., -10 to +10 V) while the other handles current loops (e.g., 4 to 20 mA).

What is the level of electrical isolation provided between the two input channels?

The EP3162-0002 features galvanic isolation up to 300 V between the individual input channels, as well as 500 V isolation to the EtherCAT fieldbus, minimizing the risk of ground loops.

Does this module require a control cabinet for installation?

No, with its IP65/66/67-rated enclosure, the EP3162-0002 is designed for direct machine mounting in wet, dusty, or harsh environments without needing an electrical enclosure.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашей официальной Политика возврата и возмещения .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Недавно просмотренные товары

Технические знания

Электрические приводы, разработанные для замены гидравлических систем: практическое руководство по промышленной автоматизации

В этой статье объясняется, как интегрированные электрические приводы, такие как серия e-Actuator от SMC, преобразуют промышленное управление движением, заменяя традиционные пневматические и...

Математические операции с использованием OpenPLC для промышленных автоматизированных систем

В этой статье объясняется, как системы ПЛК выполняют основные математические операции, такие как сложение, вычитание, умножение, деление, взятие остатка и возведение в степень в рамках промышленной...

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий, защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От систем с клеящими поверхностями, вдохновлёнными гекконами, и мягких захватов пищевого класса до...