1 из 1

BECKHOFF IP2041-B518 Fieldbus Box 8-Channel Digital Output Module

BECKHOFF IP2041-B518 Fieldbus Box 8-Channel Digital Output Module

Остался только 10 товар(ы) на складе
  • Производитель: BECKHOFF

  • Номер продукта: IP2041-B518

  • Страна происхождения:Германия

  • Тип продукта: Fieldbus Box Modules

  • Оплата: Т/Т, Western Union

  • Вес: 2000г

  • Размеры: 30 mm x 210 mm x 26.5 mm

  • Порт отгрузки: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

Description

Decentralized industrial environments require rugged, high-performance I/O routing directly at the machine interface. The BECKHOFF IP2041-B518 is an IP67-rated Fieldbus Box designed to distribute 8 digital output signals over a high-speed CANopen network. Operating at a nominal 24 V DC, this module offers robust switching capabilities, delivering up to 2 A per individual channel with short-circuit protection, making it ideal for commanding valves, actuators, and contactors directly in harsh environments without an electrical cabinet.

Equipped with an integrated T-connector for the CANopen bus line, the IP2041-B518 simplifies linear network topology by allowing incoming and outgoing fieldbus lines to be daisy-chained without additional external splitters. Its M8 connection interface ensures tight, vibration-resistant connections for digital signals, while its polyamide housing stands up to moisture, dust, and mechanical stress in demanding physical plants.

Features

  • 8 independent 24 V DC digital outputs rated at 2 A per channel (12 A cumulative limit).
  • Built-in CANopen physical interface via integrated M12 T-connector.
  • Automatic baud rate detection from 10 kbaud up to 1 Mbaud.
  • Short-circuit proof outputs with individual diagnostics.
  • IP65/66/67 environmental protection for direct machine mounting.
  • Standard M8 screw-type connection interfaces for reliable field signaling.

Applications

  • Decentralized packaging machinery and sorting lines.
  • Automobile assembly plants and robotic welding stations.
  • Material handling conveyor lines.
  • Pneumatic valve manifold control.

Technical Specifications

Manufacturer BECKHOFF
Model / Part Number IP2041-B518
Fieldbus Interface CANopen (1 x M12 plug, 5-pin; 1 x M12 socket, 5-pin with integrated T-connector)
Number of Outputs 8 digital outputs
Output Voltage 24 V DC (-15% / +20%)
Max. Output Current 2 A per channel (individually short-circuit proof; total maximum current 12 A)
Load Types Supported Ohmic, inductive, lamp load
I/O Connection Type M8 screw type
Power Feed Connection 2 x M8 male socket, 4-pin (no downstream connection)
Box Supply Current 45 mA + sensor current (max. 0.5 A)
Isolation (Control Voltage/Fieldbus) 500 V
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Enclosure Protection Class IP65, IP66, IP67 (conforming to EN 60529)
Housing Material Polyamide (PA6)
Dimensions (W x H x D) 30 mm x 210 mm x 26.5 mm
Shipping Weight 2 kg

Connections and Interfaces

Interface Type Connector Configuration Function
Bus Interface (IN/OUT) 1 x M12 plug (5-pin) / 1 x M12 socket (5-pin) CANopen network daisy-chaining with integrated T-piece
Digital Outputs (0 to 7) M8 screw connectors Connection of digital actuator loads (2 A max)
Power Supply Input 2 x M8 male sockets, 4-pin Control voltage and load voltage feed

Installation Guidelines

  • Mount the module directly to flat machinery frames using the 2 pre-molded mounting holes (3.5 mm diameter, compatible with M3 screws).
  • Ensure all unused M8 and M12 interfaces are fitted with matching protective caps to maintain the integrity of the IP67 moisture seal.
  • Verify that overall power consumption does not exceed the maximum aggregate limit of 12 A across all output channels.
  • Observe standard shielding practices for the CANopen trunk line, using shielded copper cables designed for high-noise industrial sectors.

Compliance and Certifications

  • CE
  • UL
  • EMC Immunity: Conforms to EN 61000-6-2
  • EMC Emission: Conforms to EN 61000-6-4
  • Vibration/Shock Resistance: Conforms to EN 60068-2-6 / EN 60068-2-27
Loading product navigation…

What is the maximum current rating per output on the Beckhoff IP2041-B518?

Each digital output channel can drive up to 2 A individually. However, the cumulative total current across all channels must not exceed 12 A.

Does the IP2041-B518 require an external T-connector for CANopen daisy-chaining?

No, the module features an integrated T-connector inside the housing, featuring one M12 plug and one M12 socket for direct, inline CANopen daisy-chain connections.

What protection class is the housing rated for?

It is rated IP65, IP66, and IP67 in compliance with EN 60529, meaning it is protected against dust and water immersion, enabling direct machine mounting without an enclosure.

What tools are needed to configure the module parameters?

Configuration can be achieved directly via the CANopen controller through Service Data Objects (SDOs) or by using Beckhoff's KS2000 software.

What types of electrical loads can this module switch?

The outputs are rated to switch ohmic, inductive, and lamp loads operating at 24 V DC.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской запечатанной упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашим официальным Политика возврата и возврата средств .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Недавно просмотренные товары

Технические знания

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий (OT), защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От клеевых систем, вдохновленных гекконами, и мягких захватов пищевого класса до инструментов на базе ИИ...

Воспоминание: как ранние электродвигатели изменили подземную добычу полезных ископаемых

От компрессоров с приводом от каната до аккумуляторных вагонеток — ранние горные работы стали поворотным моментом в индустриальной электрификации. В этой статье рассматривается, как электродвигатели...

Factory I/O: современный инструмент моделирования ПЛК для обучения промышленной автоматизации

Factory I/O меняет обучение ПЛК, предоставляя погружающие 3D промышленные симуляции для студентов, инженеров и команд технического обслуживания. Платформа сокращает разрыв между теорией и практикой...