Description

Actuating as a dedicated integration link, the Beckhoff KS6771 Bus Terminal enables direct, bidirectional communication between a K-bus coupler and Belimo MP-Bus HVAC field devices. This module functions as an MP-Bus master, coordinating data acquisition and control command distribution over a single channel. The KS6771 design features a pluggable wiring level, allowing swift module swaps without disconnecting field-level wiring harnesses. Integration is fully managed via standard TwinCAT PLC function blocks, streamlining commissioning across complex commercial and industrial air handling architectures.

Features

  • Multi-Device Topologies: Controls up to 16 MP-Bus devices (maximum 8 drives and 8 sensors) over a single fieldbus drop.
  • Pluggable Wiring Interface: Uses tension-clamp connection terminals that can be detached as a single block for expedited terminal replacement.
  • Galvanic Isolation: Provides robust 500 V isolation between the internal K-bus and the external MP-Bus circuitry to suppress common-mode electrical noise.
  • Efficient Process Image: Maps directly into the controller configuration utilizing 12 bytes of input data and 12 bytes of output data.
  • Standardized Diagnostics: Fully compatible with the TwinCAT PLC MP-Bus software library for fast system integration and continuous error reporting.

Applications

  • HVAC Variable Air Volume (VAV) Systems: Direct control of volumetric flow controllers, damper actuators, and temperature sensors.
  • Industrial Environmental Controls: Closed-loop control of pressure relief valves and air-handling units within cleanrooms or pharmaceutical laboratories.
  • Building Management Systems (BMS): Integration of distributed Belimo valve actuators and auxiliary sensors into high-level Ethernet/IP or EtherCAT backbones.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff Automation
Model Number KS6771
Interface Type MP-Bus Master (1 Channel)
Data Transfer Rate 1200 baud
Bus Access Protocol Polling
Nominal System Voltage 24 V DC (-15% / +20%)
K-Bus Current Consumption Typically 55 mA
Power Contact Consumption Typically 10 mA + actuator load
Maximum Power Contact Load 10 A
Isolation Voltage 500 V (K-bus to MP-Bus line)
Process Image Width 12 bytes input, 12 bytes output
Connection Cross-Section 0.08 to 1.5 mm² (AWG 28...16 solid/stranded; AWG 26...16 flexible)
Wire Stripping Length 9 to 10 mm
Environmental Rating IP20 (with variable installation orientation)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95% non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Explosion Protection Marking II 3 G Ex nA IIC T4 Gc (ATEX Zone 2)
Housing Material Polycarbonate (terminal housing with pluggable wiring)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Product Net Weight Approximately 85 g
Shipping Weight (Calculated) 1.5 kg

Connections and Interfaces

Terminal Pin Number Signal Assignment Description
1 MP-Bus Line Bidirectional communications line to Belimo slave actuators.
2 24 V DC (Power Contact) Power feed to drive units (internally bridged to power contact).
5 GND (MP-Bus Reference) Common reference potential for MP-Bus communication.
6 0 V DC (Power Contact) Negative power rail reference (internally bridged to power contact).

Empirical Engineering Insights

Alternative Models & Compatibility

The KS6771 is direct operational equivalent to the standard KL6771 Bus Terminal. The critical difference lies in the "KS" terminal housing design, which includes a pluggable wiring block. From a software perspective, the TwinCAT hardware configuration treats the KS6771 identically to the KL6771, enabling seamless drop-in replacements in existing PLC programs without necessitating code modifications or IO mapping updates.

Application Pitfalls & Engineering Notes

When deploying the KS6771, engineers must monitor total current consumption on the external 24 V DC supply loop. The terminal relies on internal power contacts rated for a maximum of 10 A. If several heavy damper drives are powered directly through the bus terminal, ensure the combined peak inrush currents do not exceed this threshold. For installations spanning long physical distances, use shielded twisted-pair cables to mitigate inductive noise coupling, which can disrupt the 1200-baud polling cycles.

Commissioning & Wiring Tips

To configure the bus terminal within the TwinCAT environment, the Tc2_MPBus library must be integrated into the PLC project. When addressing Belimo devices, remember that the MP-Bus allows 8 active control drives and 8 passive sensors. When inserting stranded field conductors, use the pluggable tension-clamp release slot with a standard flat-head screwdriver (3.0 mm blade size) to avoid damaging the polycarbonate terminal guide locks.

Installation Guidelines

CRITICAL WARNING: Prior to installing, removing, or wiring the KS6771 terminal, completely de-energize the main system controller and all auxiliary 24 V power feeds. Failure to isolate power may cause communication bus disruption or permanent damage to the solid-state K-bus interface electronics.
1
Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715, ensuring the lock mechanism snaps firmly into place.
2
Slide adjacent terminals together, using the integrated double slot and key connection for side-by-side electrical contact.
3
Prepare field wires by stripping insulation precisely to 9–10 mm, avoiding loose strands that could cross-contact neighboring terminals.
4
Insert field wiring into the pluggable tension clamps, using a spring-release screwdriver tool to lock each wire securely into position.
Loading product navigation…

What is the primary difference between the Beckhoff KS6771 and KL6771 terminals?

The KS6771 features a pluggable wiring level, enabling the field wiring block to be removed and plugged back on as a single assembly. The KL6771 uses fixed, non-removable terminal block connections.

How many Belimo actuator drives can I connect to a single KS6771 module?

The terminal supports a maximum of 16 MP-Bus devices, which is architecturally split into up to 8 drives and 8 sensors.

What software library is required to program this terminal in TwinCAT?

Integration requires the TwinCAT PLC MP-Bus library (typically Tc2_MPBus for TwinCAT 3), which provides dedicated function blocks for communication and device polling.

Is the KS6771 rated for use in hazardous locations?

Yes, it has ATEX approval with marking II 3 G Ex nA IIC T4 Gc, making it suitable for installation in Zone 2 hazardous areas.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашей официальной Политика возврата и возмещения .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Недавно просмотренные товары

Технические знания

Электрические приводы, разработанные для замены гидравлических систем: практическое руководство по промышленной автоматизации

В этой статье объясняется, как интегрированные электрические приводы, такие как серия e-Actuator от SMC, преобразуют промышленное управление движением, заменяя традиционные пневматические и...

Математические операции с использованием OpenPLC для промышленных автоматизированных систем

В этой статье объясняется, как системы ПЛК выполняют основные математические операции, такие как сложение, вычитание, умножение, деление, взятие остатка и возведение в степень в рамках промышленной...

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий, защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От систем с клеящими поверхностями, вдохновлёнными гекконами, и мягких захватов пищевого класса до...