1 จาก 1

BECKHOFF EL4011 EtherCAT Terminal 1-Channel Analog Output 0-20 mA

BECKHOFF EL4011 EtherCAT Terminal 1-Channel Analog Output 0-20 mA

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL4011

  • Country of origin:เยอรมนี

  • Product Type: EtherCAT Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

ปริมาณ
ดูรายละเอียดทั้งหมด

Product Overview

The EL4011 (EL4011) is a high-performance 1-channel analog output terminal designed for the EtherCAT I/O system, delivering precise current signals ranging from 0 to 20 mA. Engineered for demanding industrial environments such as automotive assembly lines, advanced wastewater treatment plants, and precision chemical processing, this module provides a 12-bit resolution to ensure accurate control of actuators, valves, and frequency converters. By leveraging the EtherCAT Distributed Clocks (DC) technology, the EL4011 achieves synchronization precision of less than 1 microsecond, effectively minimizing jitter in high-speed motion control loops. Its compact 12 mm housing optimizes cabinet space while the short-circuit proof design and 500 V electrical isolation significantly reduce system downtime caused by electrical faults or signal interference.

Technical Configuration

The EL4011 architecture is built upon the E-bus communication interface, ensuring seamless integration with Beckhoff EK series couplers. The hardware features a 3-wire single-ended connection technology, which simplifies wiring for active current loops. A critical engineering advantage of this terminal is the integrated watchdog function; in the event of a fieldbus communication interruption, the output can be configured to a predefined safety value or follow a specific ramp, preventing unpredictable mechanical behavior. The internal process image utilizes a 1 x 16-bit AO output format, allowing for straightforward mapping within TwinCAT or other EtherCAT masters. The module’s polycarbonate housing includes signal LEDs for immediate local diagnostics of power and communication status.

Technical Specifications

Feature Specification
Model EL4011
Brand BECKHOFF
Origin Germany
Output Type 1-channel analog output, current 0-20 mA
Resolution 12 bit
Conversion Time approx. 100 microseconds
Output Error < 0.1 percent (relative to end value)
Distributed Clocks Yes, precision << 1 microsecond
Power Supply 24 VDC via power contacts
Current Consumption (E-bus) typ. 140 mA
Electrical Isolation 500 V (E-bus/signal voltage)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Operating Temperature -25 to +60 deg C
Weight 0.06 kg

Technical FAQs

How does the EL4011 handle output values during a loss of communication?

The terminal includes an optional user-specific watchdog. You can configure the device to hold the last valid value, go to a predefined safety value, or follow a controlled ramp to 0 mA to protect sensitive downstream equipment.

Can the EL4011 drive a load higher than 500 Ohms?

The specified maximum load is 500 Ohms. Exceeding this limit may prevent the terminal from maintaining the required 20 mA current due to voltage compliance limits, potentially resulting in signal clipping or error states.

What is the difference between the EL4011 and the ES4011?

The EL4011 uses standard permanent wiring terminals, whereas the ES4011 features a pluggable wiring level, allowing for faster module replacement without disconnecting individual signal wires.


Engineering & Installation Guide

  • Shielding and Noise Mitigation: For high-precision 12-bit analog signals, always use shielded twisted-pair (STP) cabling. Ensure the shield is grounded at the entry point of the control cabinet using a low-impedance shield clip. Avoid routing 0-20 mA signal lines parallel to high-voltage AC motor cables to prevent electromagnetic induction.

  • Heat Dissipation and Mounting: While the module supports variable installation positions, vertical mounting on a 35 mm DIN rail is recommended to facilitate natural convection. Maintain at least 10 mm of clearance above and below the terminal row if the ambient temperature consistently exceeds 50 deg C.

  • Wiring Precision: Use ferrules for flexible conductors to ensure a gas-tight connection within the spring-loaded terminals. The stripping length must be strictly 8 to 9 mm; exposed copper increases the risk of short circuits between adjacent 24 VDC power contacts.

 

การจัดส่งด่วนทั่วโลก

  • การจัดส่งมาตรฐาน: 4-6 วันทำการ ผ่าน DHL, FedEx และ UPS
  • จัดส่งด่วน: จัดส่งในวันเดียวกันสำหรับคำสั่งซื้อที่มีในสต็อกและสั่งก่อนเวลา 14:00 น. (GMT+8)
  • ครอบคลุมทั่วโลก: ให้บริการมากกว่า 150 ประเทศ รวมถึงการจัดส่งด่วนไปยังซาอุดีอาระเบียและสหรัฐอาหรับเอมิเรตส์

การคืนสินค้าและการรับประกัน

  • การรับประกัน 30 วัน: รับคืนสินค้าที่มีในสต็อกในบรรจุภัณฑ์เดิมที่ปิดผนึกจากโรงงาน
  • การรับประกัน 12 เดือน: อะไหล่อุตสาหกรรมทุกชิ้นได้รับการรับประกันทางเทคนิคจากผู้เชี่ยวชาญของเรา

คำสั่งซื้อจะถูกดำเนินการและจัดส่งในวันจันทร์ถึงวันศุกร์ (ไม่รวมวันหยุดราชการ)


สำหรับคุณสมบัติครบถ้วน ค่าธรรมเนียมการเติมสินค้าใหม่ และรายละเอียดการคืนสินค้าระหว่างประเทศ กรุณาดูที่เว็บไซต์อย่างเป็นทางการของเรา นโยบายการคืนเงินและการคืนสินค้า .

TECHNICAL SPECIFICATIONS

Color pattern
สีขาวอมเทา
Country of origin
เยอรมนี

สินค้าที่ดูล่าสุด

ความรู้ทางเทคนิค

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...