1 -ın, -in, -un, -ün (bağlama göre değişir) 1

BECKHOFF EQ3314-0002 EtherCAT Box 4-Channel Thermocouple Input Module

BECKHOFF EQ3314-0002 EtherCAT Box 4-Channel Thermocouple Input Module

Stokta sadece 10 adet kaldı
  • Üretici: BECKHOFF

  • Ürün No.: EQ3314-0002

  • Menşei ülke:Almanya

  • Ürün Türü: EtherCAT I/O Modules

  • Ödeme: T/T, Western Union

  • Ağırlık: 500g

  • Boyutlar: 39 mm x 160 mm x 43 mm

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Designed for direct connection of thermocouples in harsh environments, the EQ3314-0002 EtherCAT Box provides high-precision temperature measurement with a robust, washdown-compatible enclosure. This industrial I/O module features four analog input channels that support a wide range of thermocouple sensor types, enabling linear temperature curve evaluation and cold junction compensation directly within the unit. The mechanical design features a high-grade stainless steel housing specifically engineered for hygienic applications, food and beverage processing, and chemical environments requiring frequent high-pressure cleaning.

The EQ3314-0002 interfaces directly with EtherCAT networks via dual M8 connections, processing signals with high resolution and transmitting digitized temperature values back to the controller. Configurable input filtering and adjustable conversion times allow industrial automation engineers to optimize measurement performance for dynamic thermal processes or high-noise electrical environments.

Features

  • Four independent analog channels for thermocouple or mV signal measurement.
  • Compatible with thermocouple types J, K, L, B, E, N, R, S, T, and U (default: Type K).
  • IP69K protection rating for suitability in wet, high-pressure washdown zones.
  • Hygienic design housed in durable, corrosion-resistant stainless steel.
  • Configurable input filtering with five distinct variants.
  • Integrated cold junction compensation for reliable thermal accuracy.
  • Efficient connection system using standard M12 sensor connectors and M8 bus/power ports.

Applications

  • Food, beverage, and packaging industries.
  • Pharmaceutical production plants.
  • Chemical processing installations.
  • Industrial ovens, furnaces, and thermal processing chambers.

Technical Specifications

  • Manufacturer Beckhoff Automation
    Part Number / Model EQ3314-0002
    Protocol EtherCAT
    Number of Inputs 4
    Signal Type Thermocouple, mV measurement
    Sensor Types Types J, K, L, B, E, N, R, S, T, U
    Measuring Range Sensor-dependent (Type K default: -100 to +1370 degC)
    Resolution 0.1 degC per digit
    Measurement Error < ±0.3 % for Type K (relative to full scale value)
    Conversion Time 20 ms to 2.5 s (default: approx. 250 ms)
    Nominal Supply Voltage 24 V DC (-15 % / +20 %)
    Current Consumption (from US) 120 mA
    Electrical Isolation 500 V
    Housing Material Stainless steel (Hygienic Design)
    Protection Rating IP69K (conforms to EN 60529)
    Operating Temperature -25 to +60 degC
    Storage Temperature -40 to +85 degC
    Dimensions (W x H x D) 39 mm x 160 mm x 43 mm
    Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
    EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4

    Connections and Interfaces

    Interface Type Connector Style Function
    Bus Interface 2 x M8 socket, shielded, screw-type EtherCAT input and output ports
    Sensor Connection 4 x M12 screw-type (2-wire connection) Thermocouple analog inputs
    Power Feed 1 x M8 male socket, 4-pin Control voltage supply input
    Power Downstream 1 x M8 female socket, 4-pin Power distribution to next module

    Installation Guidelines

    • Mount the module directly to the machinery or structural frame using the 2 integrated fixing lugs designed for M5 screws.
    • Ensure correct grounding of the stainless steel housing to minimize electromagnetic interference and ensure safe operation.
    • Use only fully shielded M8 cables for the EtherCAT network to maintain communication integrity in noisy environments.
    • Verify that all unused M12 and M8 ports are sealed with compatible IP69K-rated protective caps to prevent moisture ingress.
    • Route sensor wiring away from high-power AC cables or motor drives to limit inductive noise coupling.

    Compliance and Certifications

    • CE
    • UL
    Loading product navigation…

    What types of thermocouples are compatible with the EQ3314-0002?

    The EQ3314-0002 supports thermocouple types J, K, L, B, E, N, R, S, T, and U. It can also perform raw mV voltage measurements.

    What is the default sensor setting for the module out of the box?

    The default sensor configuration is set for Type K thermocouples with a preset range of -100 to +1370 degC.

    Is the EQ3314-0002 suitable for food and beverage washdown areas?

    Yes, the module is built with a stainless steel housing in a hygienic design and features an IP69K protection rating, making it highly resistant to aggressive cleaning agents and high-pressure water jets.

    What connector style is used for the sensor inputs?

    The sensor inputs use 4 x M12 screw-type connectors, providing secure 2-wire connections for the thermocouples.

    Küresel Ekspres Kargo

    • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
    • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
    • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

    İadeler ve Garanti

    • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
    • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

    Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


    Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

    TECHNICAL SPECIFICATIONS

    Country of origin
    Almanya

    Son Görüntülenen Ürünler

    Teknik bilgi

    Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

    Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

    FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

    Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

    PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

    Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

    Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

    Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

    Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

    Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...

    Geçmişe Dönüş: Erken Elektrikli Motorlar Yeraltı Madenciliğini Nasıl Değiştirdi

    Halatla çalışan DC kompresörlerden bataryalı maden arabalarına kadar, erken madencilik faaliyetleri endüstriyel elektrifikasyonda bir dönüm noktası oldu. Bu makale, elektrik motorlarının modern...