Designed to operate directly in harsh industrial environments without a control cabinet, the Beckhoff ER2338-0001 enables decentralized routing of bidirectional digital control signals. This EtherCAT Box module features 8 digital channels that are individually and freely configurable as either inputs or outputs. By supporting dynamic configuration, this module simplifies field I/O layout adjustments and reduces the overall hardware footprint in complex processing lines. Each channel is processed with high temporal precision, offering integrated input filtering and short-circuit protection for connected sensors.

Key Features

  • Flexible I/O Configuration: 8 digital channels that can be configured independently as inputs or outputs.
  • Robust Industrial Housing: Fully cast zinc die-cast construction with IP65, IP66, and IP67 ingress ratings.
  • High-Speed Communication: Dual M8 shielded, screw-type EtherCAT interfaces for direct line topology.
  • Sensor and Load Protection: Short-circuit-proof sensor supply up to 0.5 A total and thermal overload output protection.
  • Standard M8 Connections: A-coded 3-pin M8 sockets provide standard industrial physical interfaces.

Industrial Applications

  • Automotive Assembly Lines: Decentralized sensor and actuator routing on robotic arms and welding cells.
  • Food and Beverage Processing: Washdown zones requiring robust environmental protection without enclosure housing.
  • Conveyor and Material Handling: Localized distribution of photoelectric sensors, solenoid valves, and pneumatic switches.

Technical Specifications

Technical Parameter Specification Value
Manufacturer Beckhoff
Model Number ER2338-0001
Protocol EtherCAT
Bus Interface 2 x M8 socket, shielded, screw type
Number of Channels 8 digital inputs or outputs, freely configurable
I/O Connections M8 x 1, 3-pin, A-coded
Input Filter Time 10 microseconds
"0" Signal Voltage Range -3 to +5 V
"1" Signal Voltage Range 11 to 30 V, 6 mA input current (EN 61131-2, type 3)
Sensor Supply From load supply voltage, max. 0.5 A total, short-circuit proof
Supported Load Types Ohmic, inductive, lamp load
Rated Load Voltage 24 V DC (-15% / +20%)
Max. Output Current 0.5 A per channel
Switching Times typ. TON: 50 microseconds, typ. TOFF: 100 microseconds
Current Consumption (US) 120 mA
Auxiliary Power Current typ. 20 mA + load
Power Supply Interface Feed: 1 x M8 male 4-pin; Downstream: 1 x M8 female 4-pin
Electrical Isolation 500 V
Protection Rating IP65/IP66/IP67 (conforms to EN 60529)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Physical Module Weight approx. 265 g
Shipping Weight (Calculated) 2.0 kg

Port and Wiring Configurations

Interface Type Connector Form Factor Assignment & Purpose
EtherCAT Bus Input/Output 2 x M8 socket, shielded, screw-type EtherCAT communication downstream/upstream linking.
Digital I/O Channels (0-7) 8 x M8 female socket, 3-pin, A-coded Configurable digital signal and sensor supply. Pin 1: +24 V DC sensor supply, Pin 3: GND, Pin 4: Input/Output signal.
Power Supply Feed 1 x M8 male socket, 4-pin System/sensor voltage (Us) and peripheral load voltage (Up).
Power Supply Downstream 1 x M8 female socket, 4-pin Feed-through power to adjacent EtherCAT Box modules.

Empirical Engineering Insights

Alternative Models & Compatibility

The ER2338-0001 features fully configurable channels, which makes it an ideal, high-efficiency spare part replacing either pure digital input (ER1008) or pure digital output (ER2008) units in machine modifications. Note that TwinCAT ESI (EtherCAT Slave Information) configurations must specifically define the operational profile (Input vs. Output mode) for each channel to match the physical wiring.

Application Pitfalls & Engineering Notes

Thermal management inside completely enclosed, non-ventilated routing channels must be monitored closely. Although rated up to +60 degC ambient, driving all 8 outputs at their maximum 0.5 A inductive rating simultaneously causes significant localized heating within the cast housing. Ensure proper spacing or metallic surface heat sinking is utilized if cumulative output current exceeds 3.0 A.

Commissioning & Wiring Tips

During commissioning, verify that the Us (system power) and Up (load power) loops are isolated appropriately if safety relays are installed. A common fault is tying Us and Up to the same field supply line, which overrides safety-related external output de-energization loops. Always torque all M8 connectors to exactly 0.4 Nm to preserve environmental sealing.

Installation Guidelines

CRITICAL WARNING: Prior to wiring, mounting, or performing maintenance on the module, ensure all 24 V DC control power (Us) and peripheral load power (Up) sources are completely de-energized. Verify the absence of voltage using a calibrated test instrument. Failure to isolate power lines can result in hardware damage or unexpected device actuation, leading to equipment damage or personal injury.
1
Mechanical Mounting: Secure the physical chassis directly to the machine frame or mounting profile using two M3 screws. Ensure the mounting surface is clean to optimize thermal conduction.
2
EtherCAT and Power Cabling: Connect the shielded M8 EtherCAT cabling to the IN and OUT ports. Connect the 4-pin M8 power cable supplying 24 V DC to the input feed port. Secure unused ports with IP67 protective caps to prevent ingress of moisture or particulates.
3
Software Configuration: Power up the system, scan the EtherCAT network in TwinCAT, and import the relevant XML (ESI) file. Map the individual channels as inputs or outputs within your PLC project prior to system logic execution.
Loading product navigation…

Can every channel on this module be configured as either an input or an output simultaneously?

Yes. Each of the 8 channels on this module is freely configurable. You can define any mix of inputs and outputs through the TwinCAT configuration software to match your field wiring needs.

What is the maximum current capacity for the sensor power supply?

The sensor supply provides a maximum total current of 0.5 A across all channels. It is fully protected against short-circuits. If individual sensor consumption is high, verify the total draw stays below this 0.5 A threshold.

How does the module signal a short circuit on an output channel?

Outputs are short-circuit protected. In the event of an overload, the module shuts down the output and communicates the fault status back to the controller via the cyclical EtherCAT process data.

Do I need special tools to maintain the IP67 sealing during installation?

Yes, we highly recommend utilizing a calibrated torque wrench for M8 connectors, tightening to exactly 0.4 Nm. Under-tightening allows moisture ingress, while over-tightening can crack the inner connector threads.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Almanya

Son Görüntülenen Ürünler

Teknik bilgi

Akışkan Güç Sistemlerinin Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Pratik Bir Endüstriyel Otomasyon Rehberi

Bu makale, SMC’nin e-Actuator serisi gibi entegre elektrikli aktüatörlerin, geleneksel pnömatik ve hidrolik sistemlerin yerini alarak endüstriyel hareket kontrolünü nasıl dönüştürdüğünü...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...