Description

Designed for direct field deployment without a control cabinet, the Beckhoff ER3184-0002 EtherCAT Box provides high-precision processing of up to four analog input signals in harsh environments. This module enables software-parameterizable selection between voltage (-10/0 to +10 V) and current (0/4 to 20 mA) measurements on a per-channel basis. Housed in a robust, zinc die-cast shell with an IP67 protection rating, it processes signals with a 16-bit resolution and fast conversion times, making it ideal for distributed machinery and process loops requiring high noise immunity.

Features

  • Four single-ended, individually configurable analog inputs.
  • 16-bit analog-to-digital resolution (including sign) for high signal fidelity.
  • Robust IP65/66/67 physical encapsulation, eliminating the need for protective field enclosures.
  • High-speed conversion rate of approximately 100 microseconds per channel.
  • Support for Distributed Clocks (DC) to ensure tight synchronization across the entire EtherCAT network.
  • Configurable input filter limit frequency up to 5 kHz.
  • Standardized M12 input connections alongside reliable M8 EtherCAT communication ports.

Applications

  • Cabinet-free on-machine sensor consolidation in automotive and manufacturing assembly lines.
  • Distributed process parameters monitoring, including flow, temperature, and pressure transmitters.
  • Automated materials handling and conveyor systems operating in wet or dusty processing plants.
  • High-speed parameter recording systems utilizing TwinCAT-based distributed clocks.

Technical Specifications Table

Parameter Specification
Manufacturer Beckhoff Automation
Model Number ER3184-0002
Number of Inputs 4 (single-ended)
Signal Ranges -10 to +10 V | 0/4 to 20 mA (parameterizable per channel)
Resolution 16 bits (including sign)
Conversion Time ~ 100 microseconds
Internal Resistance > 200 kOhm (voltage) | typ. 85 Ohm + diode voltage (current)
Common-Mode Voltage (UCM) Max. 35 V
Measurement Uncertainty < ±0.3 % (relative to full scale value)
Distributed Clocks (DC) Supported, high-precision synchronization
Input Filter Configurable, limit frequency 5 kHz
Nominal Power Supply 24 V DC (-15% / +20%)
Current Consumption 120 mA from US
Electrical Isolation 500 V
IP Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Weight Approx. 265 g
Standards & Approvals CE, UL

Connections and Interfaces

Connector / Pin Functional Assignment
M8 Bus Sockets (2 x Shielded) EtherCAT IN / EtherCAT OUT
M12 Socket Pin 1 +24 V DC sensor supply (derived from UP)
M12 Socket Pin 2 Analog input + (Voltage / Current)
M12 Socket Pin 3 GND (Sensor supply ground)
M12 Socket Pin 4 Analog input - (Signal ground)
M12 Socket Pin 5 Shield / Functional Earth (FE)

Empirical Engineering Insights

Alternative Models & Compatibility

The ER3184-0002 serves as a ruggedized, field-mounted alternative to the cabinet-based EP3184-0002 EtherCAT Box. Both modules feature identical electronic behavior and parameterization registers via TwinCAT. However, the ER3184 housing is fabricated from heavy-duty zinc die-cast, whereas EP-series modules utilize lighter plastic housings. Direct firmware drop-in compatibility is maintained from TwinCAT 2.11 Build 2040 and TwinCAT 3.x onwards.

Application Pitfalls & Engineering Notes

When configuring channels for current mode (0 to 20 mA or 4 to 20 mA), the internal input pathway pathways route through an 85 Ohm shunt in series with a protection diode. System designers must ensure that the driving sensor has sufficient compliance voltage to overcome this diode forward drop under full-scale current loops, especially when powering passive loop-powered devices.

Commissioning & Wiring Tips

To guarantee IP67 sealing and maintain shielding performance, all unused M12 and M8 connections must be sealed using authentic Beckhoff protective caps. Ground the zinc housing directly to the machine bed through a dedicated low-impedance earthing strap. This prevents ground loops and ensures high-frequency noise is successfully shunted away from the sensitive 16-bit A/D converters.

Installation Guidelines

CRITICAL WARNING: De-energize all primary field power supplies (US and UP) before mounting or connecting the EtherCAT Box. Ground potential differences between physical nodes can cause instantaneous destruction of the logic interface or damage sensor inputs if connections are hot-plugged.
1

Mount the ER3184-0002 to a flat metal surface using two M3 screws through the integral mounting holes to establish a robust mechanical and thermal interface.

2

Attach the M8 EtherCAT communication cables (IN and OUT ports) using a torque wrench calibrated to 0.4 Nm to maintain ingress protection integrity.

3

Connect the analog sensor cables to the appropriate M12 channels. Ensure you apply the proper pinout configuration for active versus passive current loop requirements.

4

Supply 24 V DC to the M8 power inlet (US and UP). Open TwinCAT, scan the EtherCAT loop, and configure the CoE (CAN over EtherCAT) variables to match the sensors' voltage or current profiles.

Loading product navigation…

How do I switch between voltage and current modes on the ER3184-0002?

Channel modes are software-configured using the TwinCAT System Manager via CoE (CAN over EtherCAT) directory parameterization. No physical wiring changes or module disassembly are needed.

What is the difference between US and UP power supply lines on this EtherCAT Box?

The US line supplies power to the internal EtherCAT module logic and bus communication, whereas UP supplies power directly to the sensor terminals on the M12 interfaces.

Does the ER3184-0002 support Distributed Clocks (DC)?

Yes, it supports high-precision Distributed Clocks, allowing highly synchronized analog input sampling across the entire EtherCAT segment down to the sub-microsecond level.

What happens if an analog input exceeds the operational range?

The module triggers overrange status bits inside the TwinCAT process image, notifying the control loop of potential sensor saturation without knocking the fieldbus connection offline.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Almanya

Son Görüntülenen Ürünler

Teknik bilgi

Akışkan Güç Sistemlerinin Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Pratik Bir Endüstriyel Otomasyon Rehberi

Bu makale, SMC’nin e-Actuator serisi gibi entegre elektrikli aktüatörlerin, geleneksel pnömatik ve hidrolik sistemlerin yerini alarak endüstriyel hareket kontrolünü nasıl dönüştürdüğünü...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...