1 -ın, -in, -un, -ün (bağlama göre değişir) 1

Beckhoff IL2300-B400 Fieldbus Box Coupler Module

Beckhoff IL2300-B400 Fieldbus Box Coupler Module

Stokta sadece 10 adet kaldı
  • Üretici: BECKHOFF

  • Ürün No.: IL2300-B400

  • Menşei ülke:Almanya

  • Ürün Türü: Fieldbus Coupler Modules

  • Ödeme: T/T, Western Union

  • Ağırlık: 500g

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Designed to manage high-speed industrial communications within rugged environments, the Beckhoff IL2300-B400 establishes a direct interface between the Lightbus system and decentralized IP67 Extension Box modules. This coupler box allows for efficient modular expansion directly on the machinery, eliminating the need for protective control cabinets. By converting Lightbus telegrams into the internal Extension Box protocol, the device ensures near-instantaneous I/O updates. Its robust construction guarantees superior mechanical stability, making it highly reliable in demanding manufacturing and process automation layouts.

Features

  • Supports up to 120 decentralized extension modules for flexible system scalability.
  • Handles up to 512 digital inputs and 512 digital outputs per fieldbus node.
  • Manages up to 28 analog inputs and 28 analog outputs for complex instrumentation integration.
  • Full configuration, commissioning, and parameter setting via the KS2000 software tool.
  • Heavy-duty M23 and M8 connections engineered for severe industrial environments.

Applications

  • Cabinet-free, decentralized machine control architectures.
  • Automotive assembly lines utilizing high-speed Lightbus configurations.
  • Material handling and packaging equipment requiring dense distributed I/O points.
  • Wet or dusty environments requiring IP67 ingress protection.

Technical Specifications

Parameter Value / Specification
Manufacturer Beckhoff
Model Number IL2300-B400
Fieldbus Protocol Lightbus
Max Extension Modules 120 (max. 64 byte input / 64 byte output data)
Digital Peripherals Capacity Max. 512 inputs and 512 outputs
Analog Peripherals Capacity Max. 28 inputs and 28 outputs
Configuration Interface Via KS2000 software
Bus Connection Ports 1 x M23 female 9-pin socket, 1 x M23 male 9-pin socket
Power Supply (Control) 24 V DC (Permissible range: 20 to 29 V DC)
Power Supply (Load) Determined by connected Extension Box I/O types
Power Feed Interface 1 x M8 male socket, 4-pin
Downstream Power Interface 1 x M8 female socket, 4-pin
Current Consumption (Box Supply) 85 mA + sensor loads (max. 0.5 A total)
Electrical Isolation Control voltage/fieldbus: None; Control voltage/I/O: By I/O type
Ingress Protection Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Net Unit Weight 350 g
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Connector Type Pin Configuration Functional Assignment
M23 Fieldbus In 9-pin Female Socket Incoming Lightbus signals and diagnostic feedback loop
M23 Fieldbus Out 9-pin Male Socket Downstream Lightbus extension to adjacent field nodes
M8 Power Input 4-pin Male (Feed) Pin 1: +24 V DC Control; Pin 2: +24 V DC Load; Pin 3: GND Control; Pin 4: GND Load
M8 Power Output 4-pin Female (Downstream) Loop-through control and load voltages to next Extension Box

Alternative Models & Compatibility

The IL2300-B400 is specifically dedicated to Beckhoff Lightbus architectures. If your installation requires transition to alternative fieldbus networks, the Beckhoff IP67 Fieldbus Box range features alternative options, such as the IL2300-B310 (PROFIBUS) or the IL2300-B510 (CANopen). For modern Industrial Ethernet networks, migrate to the EtherCAT EP series modules. Note that configuration files and mapping configurations compiled in KS2000 for Lightbus cannot be migrated directly to other protocols without hardware profile reconfiguration.

Application Pitfalls & Engineering Notes

To maintain the specified IP67 protection rating, all unused M23 and M8 connectors must be sealed using industrial-grade protective caps. The internal box supply current is limited to 0.5 A for connected sensors. In applications where sensors require higher current draws, run auxiliary external power lines rather than powering directly through the module. Pay close attention to the bend radius of the Lightbus fiber optic cables; tight bends can lead to data attenuation and intermittent fieldbus communication drops.

Commissioning & Wiring Tips

When connecting the device, use separate wire routing for control voltage and high-current AC lines to prevent electromagnetic coupling. Use shielded M23 and M8 cables for communication lines to preserve signal integrity against high-frequency noise. During initial software configuration in KS2000, ensure the hardware addresses mapped in your PLC config tool match the physical physical nodes in sequence, particularly when managing maximum I/O extension counts.

Installation Guidelines

CRITICAL WARNING:

Ensure all control and load power supplies are fully disconnected before beginning installation, wiring modifications, or maintenance. High transient voltages or sudden machine activation during installation may cause electrical shock or severe damage to sensitive electronic components.

1
Mount the coupler module securely to the machinery frame using the integrated mounting holes. Ensure the installation surface is flat to prevent torque stress on the housing.
2
Connect the incoming Lightbus fiber optic lines to the M23 female input socket and the downstream loop to the M23 male socket. Fully hand-tighten the coupling rings.
3
Attach the M8 4-pin feed cable to supply the 24 V DC control and load voltages. If cascading power to further Extension Boxes, connect the M8 downstream cable.
4
Fit heavy-duty dust caps onto any open or unused M8 or M23 ports to ensure watertight performance. Perform software diagnostics via KS2000 prior to machine commissioning.
Loading product navigation…

How many extension modules can be linked to the IL2300-B400 coupler?

You can connect up to 120 decentralized Extension Box modules, supporting a maximum capacity of 64 bytes of input and 64 bytes of output data.

Which software is used to parameterize and configure this module?

Configuration, parameter adjustments, and troubleshooting are completed using the Beckhoff KS2000 software interface.

What are the protection ratings of this device?

This module features an IP65, IP66, and IP67 rating when all mating M23 and M8 connectors are securely mated or capped, allowing direct machine mounting.

What is the maximum digital I/O capacity of the IL2300-B400?

It can support up to 512 digital inputs and 512 digital outputs per fieldbus node.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Almanya

Son Görüntülenen Ürünler

Teknik bilgi

Akışkan Güç Sistemlerinin Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Pratik Bir Endüstriyel Otomasyon Rehberi

Bu makale, SMC’nin e-Actuator serisi gibi entegre elektrikli aktüatörlerin, geleneksel pnömatik ve hidrolik sistemlerin yerini alarak endüstriyel hareket kontrolünü nasıl dönüştürdüğünü...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...