1 -ın, -in, -un, -ün (bağlama göre değişir) 1

BECKHOFF KL6781 Bus Terminal M-Bus Master

BECKHOFF KL6781 Bus Terminal M-Bus Master

Stokta sadece 10 adet kaldı
  • Üretici: BECKHOFF

  • Ürün No.: KL6781

  • Menşei ülke:Almanya

  • Ürün Türü: Bus Terminals

  • Ödeme: T/T, Western Union

  • Ağırlık: 60g

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Designed to facilitate seamless integration of utility metering devices, the Beckhoff KL6781 operates as a single-channel M-Bus master terminal within the standard Beckhoff Bus Terminal system. This module enables direct, bidirectional communication with up to 40 standard M-Bus loads, such as heat, water, electricity, or gas meters, over a single bus segment without requiring external level converters. Operating in master-slave mode via polling, the KL6781 transmits data standard M-Bus physics, enabling consolidated energy management and resource tracking directly from the TwinCAT control environment.

The terminal features a 24-byte process image for inputs and outputs, allowing robust data transfer rates ranging from 300 to 9600 baud. Integration is streamlined through the TwinCAT PLC M-Bus library, which provides specialized function blocks for rapid field configuration. With built-in short-circuit protection and 500 V electrical isolation between the K-bus and the M-Bus physics, the module ensures robust operation and system-wide protection against electrical faults in harsh industrial or commercial environments.

Features

  • Single-Channel Architecture: Dedicated M-Bus interface supporting up to 40 standard M-Bus loads (1.5 mA current consumption per load).
  • Flexible Baud Rates: Configurable data transfer rates from 300 to 9600 baud (default transmission set to 2400 baud).
  • Electrical Isolation: Complete 500 V isolation barrier safeguarding the internal K-bus from the M-Bus network.
  • Integrated Protection: Full short-circuit proof design to prevent module failure during field wiring faults.
  • Software Compatibility: Programmed and configured directly through TwinCAT using official M-Bus PLC function blocks.

Applications

  • Commercial and industrial building automation systems (BAS).
  • Sub-metering networks for monitoring water, gas, steam, and electricity consumption.
  • Energy management systems (EMS) compliant with ISO 5001 standards.
  • District heating stations and utility billing infrastructure.

Technical Specifications

CategoryParameterValue
Administrative Manufacturer Beckhoff Automation
Part Number/Model KL6781
Product Series Bus Terminal System (KL Series)
Communication & Bus Technology M-Bus
Data Transfer Standard M-Bus physics
Number of Channels 1
Maximum Connected Loads 40 standard loads (1.5 mA each)
Data Transfer Rates 300 to 9600 baud (default: 2400 baud)
Bus Access Master-slave mode (polling)
Electrical Data Nominal Voltage 24 V DC (-10% / +8%)
Current Consumption (K-bus) Typically 65 mA
Current Consumption (Power Contacts) Maximum 250 mA
Protection & Safety Short-Circuit Protection Yes
Electrical Isolation 500 V (K-bus / M-Bus)
Process Image Bit Width 24 bytes input / 24 bytes output
Environmental & Mechanical Weight Approx. 60 g
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Relative Humidity 95%, non-condensing
Standards & Approvals Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Certifications & Marks CE, UL

Connections and Interfaces

Terminal Point Signal/Function Description
1 M+ M-Bus Connection (+)
2 Shield Shielding / Functional Ground
3 +24 V DC External Power Supply (+)
5 M- M-Bus Connection (-)
7 0 V DC External Power Supply (0 V)

Installation Guidelines

  • Mounting: Mount the terminal vertically on standard 35 mm DIN rails (EN 60715) within an IP20-rated enclosure or control cabinet.
  • Wiring: Keep maximum cable lengths on the M-Bus segment below 300 meters. Use shielded twisted-pair (STP) cabling for optimal noise immunity.
  • Grounding: Connect the shield connection point directly to a low-impedance functional ground or DIN rail clamp.
  • Ventilation: Ensure a clearance of at least 30 mm above and below the terminal block to maintain normal operating temperatures between 0 and 55 degC.
Loading product navigation…

What is the primary function of the Beckhoff KL6781?

The Beckhoff KL6781 acts as a single-channel M-Bus master terminal within a Beckhoff Bus Terminal system, enabling direct integration of M-Bus compliant utility meters (water, gas, electricity, heat) without external level converters.

How many M-Bus devices can be connected to the KL6781 terminal?

The KL6781 supports up to 40 standard M-Bus loads, assuming each connected device consumes a standard current of 1.5 mA.

What software is used to configure the KL6781?

Configuration is handled in TwinCAT using the official TwinCAT PLC M-Bus library, which contains dedicated function blocks for communicating with the meters.

Is the KL6781 protected against field wiring faults?

Yes, the module is short-circuit proof and features 500 V electrical isolation between the inner K-bus electronics and the external M-Bus physics.

What is the maximum cable length supported by the M-Bus line on the KL6781?

The terminal supports a maximum M-Bus cable length of up to 300 meters.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Almanya

Son Görüntülenen Ürünler

Teknik bilgi

Sıvıların Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Uygulamalı Eğitim

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...