Bently Nevada 136711-02 3500/61 RTD/TC I/O Module with Internal Barriers and Internal Terminations

Bently Nevada 136711-02 3500/61 RTD/TC I/O Module with Internal Barriers and Internal Terminations

Stokta sadece 6 adet kaldı
  • Üretici: Bently Nevada

  • Ürün No.: 136711-02

  • Menşei ülke:Amerika Birleşik Devletleri

  • Ürün Türü: RTD/TC I/O Module

  • Barkod: 8537101190

  • Ödeme: T/T, Western Union

  • Ağırlık: 460g

  • Boyutlar: 24.4 mm x 241.3 mm x 163.1 mm (W x H x D)

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

The Bently Nevada 136711-02 is a non-isolated RTD/TC I/O module with internal barriers and internal terminations designed for processing temperature transducer inputs within the 3500 Machinery Protection System. Installed in a full-height rear slot directly behind the 3500/61 Temperature Monitor main module, it accepts input signals from up to six Resistance Temperature Detector (RTD) or Thermocouple (TC) transducers. The 136711-02 channels conditioned signals and +4 to +20 mA proportional recorder outputs through integrated internal barriers to support intrinsically safe machinery monitoring applications in industrial environments.

Features

  • Provides internal zener barriers and internal termination wiring connectors for six input channels
  • Interface options configurable for 3-wire RTD, 4-wire RTD, and Thermocouple transducers
  • Integrates directly behind the 3500/61 Temperature Monitor via the 3500 system backplane
  • Routes +4 to +20 mA proportional recorder outputs for each individual channel

Applications

  • Bearing temperature monitoring in rotating machinery such as turbines, compressors, and pumps
  • Process temperature measurement using RTD and TC transducers in hazardous location areas
  • Machinery protection and condition monitoring within the 3500 system architecture

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Part Number 136711-02
Compatible Main Module 3500/61 Temperature Monitor
Module Type RTD/TC Non-Isolated I/O Module with Internal Barriers and Internal Terminations
Number of Channels Accepts 1 to 6 RTD or TC transducer signals
Input Impedance Greater than 10 Mohm for each lead input
Thermocouple Types Type E (-100 degC to +1000 degC), Type J (0 degC to +760 degC), Type K (0 degC to +1370 degC), Type T (-160 degC to +400 degC)
RTD Types 100 ohm 3-wire & 4-wire platinum (alpha = 0.00385 or 0.00392), 120 ohm 3-wire & 4-wire nickel, 10 ohm 3-wire & 4-wire copper
RTD Current Source Value 925 +-15 uA at 25 degC per transducer
Recorder Outputs +4 to +20 mA proportional to monitor full-scale (individual per channel)
Voltage Compliance (Current Output) 0 to +12 Vdc range across load (0 to 600 ohm load resistance)
Recorder Output Resolution 0.3662 uA per bit +-0.15% error at room temperature (+-0.4% error over temperature range)
Operating Temperature 0 degC to +65 degC (32 degF to +150 degF) when used with Internal Barrier I/O Modules
Storage Temperature -40 degC to +85 degC (-40 degF to +185 degF)
Rack Space Requirement 1 full-height rear slot
Dimensions (H x W x D) 241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in)
Weight 0.46 kg (1.01 lbs)

Installation Guidelines

  • Install the I/O module in a single full-height rear slot positioned directly behind the corresponding 3500/61 Temperature Monitor module.
  • Secure wiring connections to the green and blue internal termination connector headers according to transducer type wiring configurations.
  • Ensure operating ambient temperatures remain within the designated limit of 0 degC to +65 degC when internal barriers are active.

Compliance and Certifications

Certification / Standard Standard / Details
EMC Directive 2004/108/EC (EN 61000-6-2, EN 55011/CISPR 11, EN 61000-6-4)
Low Voltage Directive 2006/95/EC (EN 61010-1)
North American Hazardous Area Approval Ex nC [ia] IIC: Class I, Div 1; AEx nC [ia] IIC: Class 1, Zone 2/0 Groups A, B, C, D; T4 @ Ta = -20 degC to +65 degC
ATEX Approval II 3/(1) G, Ex nC[ia Ga] IIC T4 Gc, T4 @ Ta = -20 degC to +65 degC
Brazil Approval (3500/61 only) BR-Ex nC[nL] IIC T4, T4 @ Ta = -20 degC to +65 degC
South Africa Approval Ex nCAL [ia] IIC T4, Ex nCAL [L] IIC T4, T4 @ Ta = -20 degC to +65 degC
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 136711-02 3500/61 RTD/TC I/O Module with Internal Barriers and Internal Terminations

Which slot position does the module occupy in the chassis?

The module installs in a full-height rear slot directly behind the 3500/61 Temperature Monitor main card.

What transducer inputs can be connected to the terminals?

The module accepts up to six RTD or Thermocouple inputs, including Type E, J, K, and T thermocouples or platinum, nickel, and copper RTDs.

What temperature range is permitted for module operation?

The operating temperature range is 0 degC to +65 degC when deployed with internal barrier I/O configurations.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenir.

Siparişler Pazartesi-Cuma (resmi tatiller hariç) işlenir ve teslim edilir.


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Color pattern
Griye Çalan Beyaz
Country of origin
Amerika Birleşik Devletleri

Son Görüntülenen Ürünler

Teknik bilgi

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

OpenVMS Alpha Üzerinde Çalışan Bailey INFI 90 Symphony HMI’larını Modernleştirme

OpenVMS Alpha üzerinde çalışan eski Bailey Symphony operatör istasyonlarını değiştirmek için pratik bir rehber. Alpha emülasyonu, OpenVMS x86 geçişi, OPC’ye yeniden platform oluşturma ve aşamalı ABB...

Bakım Verileri Endüstriyel Güvenilirlik İçin Neden Vazgeçilmezdir

Bakım verileri iş emirlerini, sensör sinyallerini, varlık geçmişini, maliyetleri ve teknisyenlerin bilgi birikimini birbirine bağlar. Doğru kullanıldığında planlamayı, güvenilirliği, kestirimci...

Akışkan Güç Sistemlerinin Yerini Almak Üzere Tasarlanmış Elektrikli Aktüatörler: Uygulamalı Endüstriyel Otomasyon Rehberi