1 -ın, -in, -un, -ün (bağlama göre değişir) 3

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Stokta sadece 2 adet kaldı
  • Üretici: Emerson

  • Ürün No.: KJ3002X1-BG2

  • Menşei ülke:Amerika Birleşik Devletleri

  • Ürün Türü: Input Card

  • Barkod: 8537101190

  • Ödeme: T/T, Western Union

  • Ağırlık: 200g

  • Boyutlar: 8.1cm x 7.9cm x 8.8cm

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

The Emerson KJ3002X1-BG2 is a Thermocouple, mV Card developed for the DeltaV scalable process system. This interface component enables the direct conversion of low-level analog millivolt signals from temperature sensors and standard voltage sources into structured digital data for process automation loops. Operating on local bus infrastructures, the KJ3002X1-BG2 interfaces field temperature variables with central system controllers across diverse hazardous industrial plant architectures.

Features

  • Integrates a dedicated rotary keying mechanical mechanism to guarantee hardware alignment between interface units and field terminal blocks.
  • Features integrated diagnostic capability and electrical isolation design tailored for low-amplitude sensor signal routing.
  • Contains internal electrical path tracing optimized for direct field thermocouple and millivolt sensor hookups without external conversion hardware.

Applications

  • High-temperature process furnaces and process vessel monitoring.
  • Thermal monitoring infrastructures in industrial processing environments.
  • Continuous temperature multi-channel data acquisition within distributed control topologies.

Technical Specifications

Parameter Specification
Manufacturer Emerson Process Management
Manufacturing Origin Austin, Texas
Part Number D803060X012
LocalBus Power Rating 12 VDC at 350 mA
Field Circuit Rating 5.5 VDC at 0.6 mA/channel
Terminal Block Key Position B2
Ambient Temperature Limit 0 to 60 degC
Relative Humidity Bounds 5 to 95% Non-Condensing
Enclosure Rating IP 20
Operational Shock Resistance 10g half Sinewave for 11 msec
Operational Vibration Limit 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz
Environmental Gaseous Protection ISA-S71.04-1985 Airborne Contaminants Class G3

Connections/Interfaces

Mechanical Alignment Component Assignment Function
Terminal Block Key Position B2 Ensures hardware compatibility between the I/O card and the specific field terminal block

Installation Guidelines

  • Field Power Disconnection: All field power supplied to the device, either at the field terminal or as bussed field power through the carrier, must be completely removed before disconnecting or removing the unit.
  • Energized Maintenance Conditions: This unit may be removed or inserted while system power is energized under the following conditions: Only one unit at a time may be removed with system power energized. It must be used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power.
  • Inductance Limitations: The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance) must be utilized.
  • Fuse Handling: A terminal block fuse may NOT be removed with field power energized for non-sparking circuits.
  • Hardware Adjustments: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.

Compliance and Certifications

  • ATEX Certification Number | Nemko No. 02ATEX431U |
  • ATEX Code | II 3 G EEx nL IIC T4 |
  • FM Approval | Class I Division 2 Groups A, B, C, D Hazardous Locations, Temperature Rating T4 |
  • CSA Certification | LR87534 |
  • CE Mark | Certified |
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Can this device be hot-swapped while the system is powered?

Yes, a single unit may be removed or inserted while system power is energized, provided it is used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power, and the primary circuit wiring inductance is less than 23 uH.

What are the requirements for handling terminal block fuses?

A terminal block fuse must not be removed while field power is energized for non-sparking circuits.

Does the device require regular maintenance or calibration?

No, the device contains no user serviceable parts, must not be disassembled, and does not require calibration.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Color pattern
Siyah
Country of origin
Amerika Birleşik Devletleri
Power source
DC Güç

Son Görüntülenen Ürünler

Teknik bilgi

Sıvıların Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Uygulamalı Eğitim

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...