1 of 1

Emerson SS6501T01 DeltaV SIS Redundant CSLS Assembly - Copper

Emerson SS6501T01 DeltaV SIS Redundant CSLS Assembly - Copper

Only 1 item(s) left in stock
  • Manufacturer: Emerson

  • Product No.: SS6501T01

  • Country of origin:United States

  • Product Type: Process Safety Instrumented System Logic Solvers

  • Payment: T/T, Western Union

  • Weight: 1850g

  • Dimensions: 174 mm x 137 mm x 249 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Emerson SS6501T01 DeltaV SIS Redundant CSLS Assembly - Copper is a Safety Integrity Level 3 (SIL 3) capable logic solver module designed for process safety applications within the DeltaV SIS system. It integrates I/O processing, safety logic execution, and diagnostics into a single redundant logic solver assembly using Emerson Electronic Marshalling technology. The SS6501T01 connects directly to standard copper Ethernet infrastructure for redundant Safety Network Port (SNP) communications on the Local Safety Network (LSN).

The module supports execution of safety instrumented functions (SIF) with deterministic execution rates independent of system size. Operating in lock-step mode, the redundant CSLS pair provides bumpless switchover upon fault detection without process disturbance. Integrated HART I/O capabilities pass field diagnostics directly to the logic solver and support partial stroke testing for digital valve controllers. The unit mounts via DIN rail latching and interfaces with up to 8 CHARM baseplates (supporting up to 96 individually configurable LS CHARM channels).

Features

  • SIL 3 rated for both simplex and redundant operating architectures.
  • Redundant logic solver pair operating in lock-step execution.
  • Integrated support for up to 96 local LS CHARM I/O channels per assembly.
  • Redundant Safety Network Ports (SNP) for copper twisted-pair Ethernet LSN connections.
  • Integrated HART protocol support for embedded field diagnostics and partial stroke testing.
  • Automatic online sensing and auto-configuration within the DeltaV SIS database.
  • Continuous diagnostic self-testing with automatic alarm generation.
  • Sequence of Events (SOE) time stamping with resolution of less than 1 ms.
  • Class 1, Div 2 / Zone 2 hazardous location rating with G3 conformal coating.
  • Snap-together DIN rail latching mechanism.

Applications

  • Emergency Shutdown Systems (ESD)
  • Burner Management Systems (BMS)
  • Fire and Gas Systems (F&G)
  • High Integrity Pressure Protection Systems (HIPPS)
  • Critical process safety instrumented functions up to SIL 3

Ordering Information

Description Model Number

Redundant CSLS Assembly - Copper (Includes CSLS Carrier, 

2 CSLSs, 2 Power Modules, 

2 single Safety Network Ports for twisted copper, 2 Power Plugs)

SS6501T01

Technical Specifications

Parameter Specification
Manufacturer Emerson
Model SS6501T01
Product Type Redundant CSLS Assembly - Copper
Input Power (Redundant) +24 V DC +/-10% at 12.5 A maximum
CSLS Power Requirement +24 V DC +/-10% at 325 mA max (simplex); 575 mA max (redundant)
Power Module Output to LS CHARMs +6.3 V DC +/-3% at 4 A maximum
Heat Dissipation 18 W maximum per carrier with redundant CSLS pair
Number of I/O Channels 96 channels (up to 48 output channels max)
Maximum CSLSs per System 1600
Maximum CSLSs per SZ Controller 16
I/O Update Rate 50 ms
Communication Ports Redundant 10/100BASE-TX RJ45 copper twisted-pair (SNP)
LSN Distance Limit 100 m
Operating Temperature -40 to 70 degC (-40 to 158 degF)
Storage Temperature -40 to 85 degC (-40 to 185 degF)
Relative Humidity 5 to 95%, non-condensing
Protection Rating IP 20
Environmental Rating ISA-S71.04-1985 Class G3 Conformal Coating
Shock 10 g half-sine wave for 11 ms
Vibration 1 mm Peak-to-Peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz
Mounting DIN rail latch to vertical oriented T-type rail

Installation Guidelines

  • Mount the CSLS carrier vertically at the top of the T-type DIN rail using the integrated rail latches.
  • Install a DIN rail stop (VE4054DRS) to secure the assembly in position.
  • Connect dual 24 V DC field power feeds to the redundant power connections on the carrier.
  • Attach copper twisted-pair Ethernet cables (10/100BASE-TX) to the primary and secondary Safety Network Ports (SNP) with a maximum cable distance of 100 meters.
  • Attach up to eight CHARM baseplates below the carrier assembly and install bus termination at the end of the physical bus.
  • Ensure cabinet installations meet IP20 requirements and maintain adequate spacing for cooling.

Compliance and Certifications

  • Safety Integrity Level: SIL 3 Capable (IEC 61508)
  • EMC Standard: EN 61326-1
  • FM (USA): Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2: AEx ec IIC Gc T4 / AEx ec nC IIC T4 / AEx ec [ic] IIC Gc T4 / AEx ec ic IIC Gc T4
  • cFM (Canada): Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2: Ex ec IIC Gc T4 / Ex ec nC IIC Gc T4 / Ex ec [ic] IIC Gc T4 / Ex ec ic IIC Gc T4
  • ATEX: II 3G Ex ec IIC T4 Gc / II 3G Ex ec [ic] IIC T4 Gc / II 3G Ex ec ic IIC T4 Gc / II 3G Ex ec nC IIC T4 Gc (EN60079-0, EN60079-7, EN60079-15)
  • IECEx: II 3G Ex ec IIC T4 Gc / II 3G Ex ec [ic] IIC T4 Gc / II 3G Ex ec ic IIC T4 Gc / II 3G Ex ec nC IIC T4 Gc (IEC60079-0, IEC60079-7, IEC60079-15)
  • Marine: IACS 10, ABS Certificate of Design Assessment, DNV Marine Certificate
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Emerson SS6501T01 DeltaV SIS Redundant CSLS Assembly - Copper

What is the channel capacity of the module?

The module supports up to 96 individually configurable local channels using LS CHARMs, with a maximum limit of 48 output channels.

What network interface is used for safety communication?

The module utilizes redundant copper Safety Network Ports (SNP) supporting 10/100BASE-TX Ethernet over twisted-pair cabling up to 100 meters.

Does replacing one logic solver in a redundant pair disrupt process operations?

No. When one card of a redundant pair is removed or fails, switchover to the partner card is completely bumpless without process disturbance.

What is the environmental temperature limit for operation?

The operating temperature range for the assembly is from -40 degC to 70 degC.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

OpenVMS Alpha da ishlayotgan Bailey INFI 90 Symphony HMI larini zamonaviylashtirish

OpenVMS Alpha asosida ishlayotgan eskirgan Bailey Symphony operator stantsiyalarini almashtirish bo‘yicha amaliy qo‘llanma. Unda Alpha emulyatsiyasi, OpenVMS x86 ga ko‘chirish, OPC platformasini...

Nima uchun texnik xizmat ko‘rsatish ma’lumotlari sanoat ishonchliligi uchun muhimdir

Texnik xizmat ko‘rsatish ma’lumotlari ish buyurtmalari, sensor signallari, aktivlar tarixi, xarajatlar va texnik mutaxassislarning bilimlarini bog‘laydi. To‘g‘ri ishlatilganda, u rejalashtirish,...

Suyuqlik quvvat tizimlarini almashtirish uchun mo‘ljallangan elektr aktuatorlar: Amaliy sanoat avtomatizatsiyasi qo‘llanmasi

Ushbu maqola SMCning e-Actuator seriyasi kabi integratsiyalashgan elektr aktuatorlarining sanoat harakatini boshqarishda an’anaviy pnevmatik va gidravlik tizimlarni qanday almashtirayotganini...

Sanoat avtomatlashtirish ilovalari uchun OpenPLC yordamida matematik amallar bajarish

Ushbu maqola PLC tizimlari sanoat avtomatlashtirishida qo‘shish, ayirish, ko‘paytirish, bo‘lish, modulo va darajaga ko‘tarish kabi asosiy matematik amallarni qanday bajarishini tushuntiradi. Unda...

FBD PLC dasturlashda ilg‘or Boolean mantiqi: asosiy mantiqdan tashqari amaliy sanoat ilovalari

Maqola PLC dasturlashda asosiy AND, OR va NOT amallaridan tashqari bir nechta ilg‘or Boolean mantiq funksiyalarini tushuntiradi. Unda haqiqat jadvallari, multiplexerlar, impuls generatorlari va...

PLC dasturlashda Boolean mantiqi: FBD mantiq eshiklarini tushunish

Boolean mantiq har bir PLC dasturining asosidir. Oddiy mashina boshqaruvlaridan tortib murakkab sanoat avtomatlashtirish tizmlarigacha, mantiqiy eshiklar boshqaruvchilarning o‘zgaruvchan kirishlar va...