1 trong số 3

ADV551-P50 S2 Yokogawa CENTUM VP Digital Output Module

ADV551-P50 S2 Yokogawa CENTUM VP Digital Output Module

Only 10 item(s) left in stock
  • Manufacturer: Yokogawa

  • Product No.: ADV551-P50 S2

  • Country of origin:Nhật Bản

  • Product Type: Digital Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 200g

  • Dimensions: 130 mm X 32.8 mm X 107.5 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Product Overview

The Yokogawa ADV551-P50 S2 (ADV551-P50 S2) is a high-density 32-channel digital output module designed for the CENTUM VP distributed control system (DCS). This current sink module is heavily utilized in large-scale industrial plants, including petrochemical refineries, power generation plants, and water treatment facilities, where continuous and reliable valve actuation, relay switching, and indicator control are critical. By supporting advanced features like pulse width and time-proportioning output functions, the module delivers highly versatile control over field elements. The robust isolation barrier between field signals and internal system logic prevents electrical surges from migrating to the controller backplane, minimizing hardware faults, protecting process assets, and ensuring maximum uptime in critical process operations.

Suffix Breakdown

The system designation code for the ADV551-P50 S2 module identifies its precise hardware configuration, functional capabilities, and design revision:

  • ADV551: Base model for the 32-channel, 24 V DC, Isolated Digital Output Module.

  • -P: Equipped with pulse width output and time-proportional output functions alongside standard status outputs.

  • 5: Standard configuration without localized status LED displays on the front panel and with no specialized explosion protection.

  • 0: Basic design type.

  • S2: Style code representing the hardware revision level, ensuring modern component updates and seamless backward compatibility in CENTUM VP cabinets.

Technical Specifications

Parameter Metric Certified Specification Value
Model ADV551-P50 S2
Brand Yokogawa Electric Corporation
Origin Japan
Number of Output Channels 32 channels (isolated, 16 channels per common)
Output Format Current sink
Rated Applied Voltage 24 V DC
Maximum Load Current 100 mA per channel (at 26.4 V DC)
Output Response Time 3 ms or less (status output); 10 ms or less (mixed output)
Isolation Voltage Output to System: 2 kV AC for 1 minute; Between Commons: 500 V AC for 1 minute
Current Consumption 700 mA (at 5 V DC); 60 mA (from 24 V DC external supply)
Termination Options Pressure clamp terminal, dedicated cable (AKB331), or MIL connector cable
Net Weight Approx. 0.20 kg

Technical FAQs

  • Q: What are the differences between the output functions of the ADV551-P50 S2?

    A: The module supports three output modes: standard status output (simple ON/OFF control), pulse width output (one-shot pulse generation ranging from 8 ms to 7200 s), and time-proportioning output (duty cycle-modulated output used for proportional control of heating or dosing systems).

  • Q: How are the 32 output channels grouped and isolated within the module?

    A: The 32 channels are split into two isolated groups of 16 channels, with each group sharing a common minus (-) return line. This dual-common architecture provides 500 V AC galvanic isolation between the two groups, protecting the module against cross-channel electrical noise or ground-loop faults.

  • Q: Is an external power supply required to drive the digital outputs?

    A: Yes. Because the module utilizes a current sink output format, you must connect an external 24 V DC power supply (operating within a 20.4 to 26.4 V DC range) to drive the field loads. The internal electronics draw up to 60 mA from this external field supply.


Engineering & Installation Guide

  • External Power Supply Redundancy: When wiring the external 24 V DC field supply to the terminal block, use a redundant diode-ORed power supply configuration. This prevents a single power supply failure from de-energizing all 32 digital output channels, which could cause process interlocks to trip.

  • Flyback Diode Protection for Inductive Loads: When using the current sink outputs of the ADV551-P50 S2 to switch inductive field elements (such as solenoid valves or mechanical relays), always install a flyback diode (freewheeling diode) in parallel across the load. This clamps high-voltage inductive spikes generated during de-energization, preventing progressive degradation of the module's internal output transistors.

  • Proper Connection and Cable Routing: Ensure the dedicated AKB331 cable or MIL connector cable is securely locked into the module's front connector. Route this signal cabling inside the cabinet through dedicated wire ducts separated from high-voltage AC distribution buses by at least 10 cm to eliminate capacitive noise coupling.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Trắng xám
Country of origin
Nhật Bản
Power source
Nguồn điện DC

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...