1 trong số 1

Yokogawa AAI835-S03 CENTUM VP Analog I/O Module

Yokogawa AAI835-S03 CENTUM VP Analog I/O Module

Only 20 item(s) left in stock
  • Manufacturer: Yokogawa

  • Product No.: AAI835-S03

  • Country of origin:Nhật Bản

  • Product Type: Analog I/O Module

  • Payment: T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Description

The Yokogawa AAI835-S03 (Replaced by AAI835-S53) is a high-reliability analog input/output module belonging to the CENTUM VP distributed control system (DCS) series. Operating with standard 4 to 20 mA industrial instrumentation loops, this module provides 4 isolated input channels and 4 isolated output channels. The specific suffix layout designates this hardware as a standard type built without built-in explosion protection. To assure continuous loop execution across hazardous environments, the device is configured with an ISA Standard G3 chemical corrosion-resistant conformal coating option alongside an extended temperature endurance qualification spanning from -20 to 70 degC. Each field pathway is completely isolated from the system backplane and neighboring channels, allowing for direct installation in dual-redundant system architectures.

Features

  • Part of the CENTUM VP process control platform supporting dual-redundant configurations.
  • Complete channel-to-channel and field-to-system electrical isolation.
  • Integrated transmitter power supply capabilities built directly into the current input loops.
  • Enhanced durability featuring ISA Standard G3 conformal coating for aggressive atmospheres.
  • Extended ambient thermal design qualified for operation from -20 up to 70 degC.
  • Supports digital data overlays via native HART communication.

Applications

  • Simultaneous valve positioning control and flow transmitter monitoring.
  • High-integrity loops demanding channel-to-channel isolation to prevent ground loop faults.
  • Distributed control layouts situated in corrosive environmental conditions or unconditioned areas.
  • Critical process sectors requiring continuous operation via dual-redundant I/O configurations.

Ordering Information

Model/Suffix Code Option Specification
AAI835 Analog I/O Module (4 to 20 mA, 4-channel input/4-channel output, Isolated channels)
-S Standard type
0 (5) With no explosion protection
3 With ISA Standard G3 option and temperature (-20 to 70 degC) option

Technical Specifications

Items Specifications
Manufacturer Yokogawa
Model AAI835-S03 (Replaced by AAI835-S53)
Number of I/O channels 4-channel input / 4-channel output, isolated channels
I/O signal Input: 4 to 20 mA; Output: 4 to 20 mA
Allowable input current 25 mA
Withstanding voltage

Between input and system: 500 V AC, for 1 minute


 

Between input channels: 500 V AC, for 1 minute


 

Between input/output and system: 500 V AC, for 1 minute


 

Between input/output channels: 500 V AC, for 1 minute

Input resistance

Power ON: 290 Ohm (at 20 mA) to 450 Ohm (at 4 mA)


 

Power OFF: 500 kOhm or larger

Allowable load resistance Output: 0 to 750 Ohm (200 to 750 Ohm when operating between 60 to 70 degC in an ER bus node unit)
Circuit-open detection Output: Less than 0.65 mA
Accuracy Input: ±16 uA; Output: ±48 uA
Data update period 10 ms
Transmitter power supply 15.0 V or higher (at 20 mA); 29.3 V or less (at 0 mA)
Temperature drift ±16 uA / 10 degC
Maximum current consumption 360 mA (5 V DC), 450 mA (24 V DC)
Weight 0.3 kg
External connection Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)
HART communication Available

Installation Guidelines

  • Mount the module securely within its allocated slot on the CENTUM VP node backplane, ensuring complete seating of the rear multi-pin connections.
  • External barriers must be observed: A Zener barrier is not allowed to be connected with this module; use an isolation barrier if implementing intrinsically safe field layouts.
  • When using a MIL connector cable for field distribution, verify that the application withstanding voltage limits match the electrical boundaries of the chosen cable assembly.
  • Maintain clean air boundary lanes within the marshaling cabinet to ensure ambient conditions remain inside the -20 to 70 degC operational constraints.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Yokogawa AAI835-S03 CENTUM VP Analog I/O Module

Does the module support the connection of external Zener barriers?

No, a Zener barrier is not allowed to be connected with this module. An isolation barrier must be used instead when the device is deployed in intrinsically safe applications.

What are the exact channel isolation capabilities of this device?

The module features complete isolation between the field circuits and the internal system logic, as well as galvanically isolated pathways between each individual input and output channel, rated at 500 V AC for 1 minute.

How does the allowable load resistance change under high operating temperatures?

The standard allowable load resistance for the output channels is 0 to 750 Ohm. However, when the module is used in ambient temperatures from 60 to 70 degC inside a conforming ER bus node unit, the allowable load resistance adjusts to a window of 200 to 750 Ohm.

What happens to the module input resistance when the system is powered down?

When the power is ON, the input resistance varies dynamically from 290 Ohm (at 20 mA) to 450 Ohm (at 4 mA). When the power is OFF, the input resistance switches to a high impedance state of 500 kOhm or larger.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Country of origin
Nhật Bản

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...