BECKHOFF KS4021 Bus Terminal 1-Channel Analog Output 4-20 mA

BECKHOFF KS4021 Bus Terminal 1-Channel Analog Output 4-20 mA

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KS4021

  • Country of origin:Đức

  • Product Type: Bus Terminal

  • Payment: T/T, Western Union

  • Weight: 80g

  • Dimensions: 6.8 cm x 1.2 cm x 10.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Product Overview

The KS4021 (KS4021) Bus Terminal processes analog control signals in the range between 4 and 20 mA with a 12-bit resolution. Designed for harsh industrial environments such as chemical processing, water treatment plants, and power generation facilities, this single-ended analog output module transmits signals with galvanic isolation to the actuator level. Its compact, high-efficiency design directly addresses industrial downtime risks by utilizing pluggable wiring levels, which allow for rapid field replacement without disconnecting individual terminal wires. Operating on the proven Beckhoff K-bus system, the module ensures reliable, real-time data communication back to the central PLC or IPC controller.

Technical Configuration

The KS4021 features a single-ended circuit topology, optimizing it for space-constrained control cabinets where individual channel routing is required. It receives power directly from the 24 VDC power contacts, though it supports an alternative 15 VDC supply via a KL9515 power supply terminal to accommodate specialized system architectures.

The process image utilizes 1 x 16-bit data, with an optional 1 x 8-bit control and status byte for advanced diagnostics. It requires zero hardware configuration or address settings, enabling pure plug-and-play integration into the TwinCAT engineering environment. The terminal housing features a double slot and key connection system for robust side-by-side DIN rail mounting.

Technical Specifications

Parameter Specifications
Model KS4021
Brand BECKHOFF
Origin Germany
Technology Single-ended
Number of Outputs 1
Power Supply 24 VDC via power contacts (alternative 15 VDC with KL9515)
Signal Current 4 to 20 mA
Load Resistance Less than 500 Ohm
Output Error Less than +/-0.1 % (relative to end value)
Resolution 12 bit
Conversion Time Approx. 1.5 ms
Electrical Isolation 500 V (K-bus to signal voltage)
Current Consumption (Power Contacts) Typ. 30 mA + load
Current Consumption (K-bus) Typ. 60 mA
Dimensions (L x W x H) 6.8 cm x 1.2 cm x 10.0 cm
Weight 0.08 kg
Operating Temperature 0 to +55 deg C
Storage Temperature -25 to +85 deg C
Relative Humidity 95 %, no condensation
Protection Rating IP20
Approvals / Markings CE, UL, ATEX, DNVGL
Ex Marking II 3 G Ex nA IIC T4 Gc

Product FAQs

What is the practical difference between the KS4021 and the KL4021?

The primary difference lies in the housing design. The KS4021 features a pluggable wiring level, allowing the entire terminal block electronics to be swapped out while leaving the field wiring intact. The KL4021 uses fixed wiring terminals where cables must be individually disconnected during service.

How does the module handle output errors if the load resistance exceeds 500 Ohm?

If the total loop resistance exceeds 500 Ohm, the internal digital-to-analog converter will saturate. This prevents the module from driving the full 20 mA current, resulting in an inaccurate output signal and triggering an error status bit in the PLC process image.

Does this terminal require manual configuration in TwinCAT?

No manual address or parameter configuration is required on the hardware itself. The K-bus automatically detects the module type and position upon system startup, mapping the 16-bit output data directly into the controller configuration.


Field Installation and Wiring Instructions

  • Pluggable Terminal Block Operation: To release or insert individual wires, use a standard slot screwdriver to actuate the integrated tension clamp mechanism. Strip all signal wires to exactly 9 to 10 mm. Ensure the connection cross-section matches the specification (AWG 28 to 16 for solid or stranded wires).

  • Shielding and Noise Mitigation: For industrial environments with high electromagnetic interference (EMI), always use shielded twisted-pair cables for the 4 to 20 mA loop. Ground the cable shield at only one end—ideally at the entry point of the control cabinet—to prevent ground loops.

  • ATEX Zone 2 Safety Mandates: When installing the module in hazardous areas marked II 3 G Ex nA IIC T4 Gc, the terminal must be mounted inside an IP54 rated enclosure conforming to EN 60079-15. Do not disconnect or insert the pluggable wiring levers while the system is energized.

 

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Trắng xám
Country of origin
Đức
Power source
Nguồn điện DC

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...