1 trong số 1

KS2702 | BECKHOFF | 2-Channel Solid State Relay Output Terminal

KS2702 | BECKHOFF | 2-Channel Solid State Relay Output Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KS2702

  • Country of origin:Đức

  • Product Type: Bus Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 6.8 cm x 1.2 cm x 10.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Product Overview

The KS2702 (KS2702) is a 2-channel digital output terminal designed for the Beckhoff Bus Terminal system, featuring solid state relay (SSR) technology. Configured with two independent make contacts, this terminal is engineered to switch both AC and DC voltages ranging from 0 to 230 V. Because it utilizes electronic switching rather than mechanical contacts, the KS2702 offers significantly faster switch-off times (down to 0.05 ms) and a much higher service life, making it ideal for high-cycle applications such as controlling small solenoids, contactor coils, and signal indicators. The "KS" designation indicates a pluggable wiring level, allowing for rapid module replacement without disconnecting the individual field wires—a critical feature for minimizing downtime in continuous manufacturing processes.

Technical Configuration

The hardware architecture of the KS2702 is optimized for versatile power switching. It supports a steady load current of 0.3 A per channel and can handle brief peak currents up to 1.5 A (100 ms) to accommodate the inrush characteristics of inductive loads. The terminal provides superior electrical safety with 2500 V AC isolation (1 minute) and integrated surge voltage protection that triggers at 400 V AC. For system diagnostics, the module is designed for "plug-and-play" integration into the K-bus process image as two output bits, requiring no manual addressing. Its magnesium and polycarbonate construction is validated by DNV GL and ATEX certifications, ensuring reliable performance in marine, offshore, and hazardous industrial environments.

Technical Specifications

Feature Specification
Model KS2702
Brand BECKHOFF
Origin Germany
Number of Outputs 2 x make contacts (Solid State Relay)
Nominal Voltage 0 to 230 V AC/DC (DC to 100 Hz)
Max. Output Current 0.3 A steady load per channel
Peak Current 1.5 A (100 ms) / 0.5 A (20 s)
Switch-off Time 0.05 to 0.1 ms
Contact Resistance typ. 2.1 Ohms
Electrical Isolation 2500 VAC (1 min), 500 V (K-bus/field)
Leakage Current (OFF) << 1 mA
Dimensions (L x W x H) 68 mm x 12 mm x 100 mm
Operating Temperature 0 to +55 Celsius

Technical FAQs

What are the advantages of the KS2702 over a standard mechanical relay terminal?

The KS2702 uses electronic switching, which eliminates mechanical wear and contact arcing. This results in an almost unlimited number of switching cycles and much faster switch-off times (0.05 ms compared to several milliseconds for mechanical relays), which is vital for high-speed automated sequences.

Does the KS2702 require a minimum load to function?

No, unlike some AC-only Triac outputs, the solid state technology in the KS2702 can switch very small loads down to the micro-ampere range, making it suitable for interfacing with high-impedance electronic inputs as well as power loads.

What is the benefit of the pluggable wiring level?

The KS-series terminals allow the entire wiring block to be removed from the terminal housing. If a module needs to be replaced, the technician can simply unplug the wires as a single block and plug them into the new module, eliminating the risk of wiring errors and significantly speeding up maintenance.


Engineering & Installation Guide

  • Inductive Load Protection: While the terminal is rated for inductive loads and includes 400 V surge protection, switching large inductive loads (like large solenoid valves) can still generate significant heat and EMI. For long-term reliability, it is best practice to install an external RC snubber (for AC) or a freewheeling diode (for DC) directly across the load.

  • Thermal Management: With a typical contact resistance of 2.1 Ohms, the terminal generates heat when carrying the maximum 0.3 A current ($P = I^2 \times R$). Ensure the control cabinet has sufficient vertical airflow, especially when multiple KS2702 modules are mounted side-by-side and operating at high duty cycles.

  • Wiring and Stripping: Use the spring-actuated terminals for a vibration-proof connection. Strip the wires to exactly 9–10 mm. For stranded wires, the use of ferrules (0.14 to 1.5 mm²) is highly recommended to ensure all strands are securely captured in the pluggable connector.

  • Hazardous Area Compliance: For ATEX Zone 2 ("Ex nA") applications, ensure the terminal is installed in an IP54-rated enclosure. The pluggable wiring level must be secured, and the system must be de-energized before removing or inserting the terminal to prevent sparking.

 

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Trắng xám
Country of origin
Đức

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...