1 von 1

ABB AI845 3BSE023675R1 S800 I/O Analog Input Module

ABB AI845 3BSE023675R1 S800 I/O Analog Input Module

Nur noch 2 Artikel auf Lager verfügbar
  • Hersteller: ABB

  • Produkt-Nr.: 3BSE023675R1

  • Herkunftsland:Schweden

  • Produkttyp: Analog Input Modules

  • Strichcode: 85389091

  • Zahlung: T/T, Western Union

  • Gewicht: 250g

  • Abmessungen: 25 x 12 x 10 cm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

The AI845 with product ID 3BSE023675R1 is an 8-channel analog input module designed for the S800 I/O distributed system architecture. This hardware unit interfaces standard 0 to 20 mA or 4 to 20 mA current signals from field transmitters directly to the central processing controller. It incorporates dedicated HART routing capabilities per channel, enabling bi-directional communication with smart instruments over existing analog loops without altering regular process variable transmission. It provides dual-channel hardware redundancy options when paired with appropriate terminal units, maintaining active signal paths and system availability during single module exceptions.

Features

  • Provides 8 single-ended current tracking input channels supporting 0 to 20 mA or 4 to 20 mA signals.
  • Integrates channel-by-channel HART pass-through communication for asset management systems.
  • Supports hot-swapping and fully redundant configurations for uninterrupted process data acquisition.
  • Features integrated diagnostic routines to supervise open-circuit monitoring and out-of-range signal states.
  • Utilizes compact electrical termination setups using standard S800 Module Termination Units.

Applications

  • High-availability process loop telemetry inside petrochemical refining and power generation units.
  • Dual-fault tolerant interface links interfacing safety parameters with distributed control systems.
  • Asset management integration utilizing remote HART diagnostic mapping protocols.

Technical Specifications

Parameter Value
Manufacturer ABB
Model AI845
Product ID 3BSE023675R1
Series S800 I/O
Product Type Analog Input Module
Number of Channels 8 single-ended channels (redundancy supported)
Input Range 0 to 20 mA / 4 to 20 mA
Input Impedance 250 ohms
Resolution 12-bit A/D conversion
HART Protocol Support Yes, pass-through per channel
Power Requirements 24 V DC internal consumption
Degree of Protection IP20
Operating Temperature 0 to +55 degC
Storage Temperature -40 to +70 degC
Country of Origin Sweden (SE)
Weight 0.25 kg

Connections/Interfaces

Terminal Pin Function
1 Channel 1 Signal Input (+)
2 Channel 2 Signal Input (+)
3 Channel 3 Signal Input (+)
4 Channel 4 Signal Input (+)
5 Channel 5 Signal Input (+)
6 Channel 6 Signal Input (+)
7 Channel 7 Signal Input (+)
8 Channel 8 Signal Input (+)
9 to 16 Channel Signal Return / Common Ground (0V)

Installation Guidelines

  • Baseplate Insertion: Verify that the Module Termination Unit (such as TU844 or TU845) is secured onto the DIN rail before engaging the module body. Disconnect primary electrical feeds, align the plastic guide tabs, and apply uniform vertical force until the side retention latches click home.
  • Shielding Protocol: Terminate the outer metal mesh of twisted-pair instrument wires using the ground bars situated on the enclosure entry frame. Maintain single-point earth terminations at the control cabinet wall to eliminate low-frequency ground-loop feedback.
  • Redundant Configuration: To execute redundant module deployments, both units must reside in an identical, paired-slot termination cluster. Map the master/backup hierarchy inside the control programming software to handle hot-standby functions.
  • Cable Separation Routing: Route low-current operational signals in separate wiring ducts isolated from variable speed drives, bulk contactor control blocks, and heavy three-phase power buses by a minimal clear air threshold of 30 cm.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB AI845 3BSE023675R1 S800 I/O Analog Input Module

Does this module supply transmitter loop power directly to 2-wire instruments?

This module acts as a current-sinking input device. Loop voltage for 2-wire transmitters must be supplied through an external 24 V DC distribution block or specialized module termination units containing integrated auxiliary distribution.

What happens to the process variable measurement if one module in a redundant pair fails?

The backplane interface switches the active signal processing path to the standby partner within milliseconds without interrupting the data stream or generating process value spikes.

Can standard 0 to 5 V or 0 to 10 V voltage inputs connect to this card?

No. This module is exclusively designed to evaluate current loop paths within the 0 to 20 mA or 4 to 20 mA operational signal ranges.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Color pattern
Weiß
Country of origin
Schweden
Power source
Gleichstromversorgung

Kürzlich angesehene Produkte

Technisches Wissen

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...