1 von 1

Beckhoff EL3164 EtherCAT Terminal

Beckhoff EL3164 EtherCAT Terminal

Nur noch 10 Artikel auf Lager verfügbar
  • Hersteller: BECKHOFF

  • Produkt-Nr.: EL3164

  • Herkunftsland:Deutschland

  • Produkttyp: EtherCAT Terminals

  • Zahlung: T/T, Western Union

  • Gewicht: 65g

  • Abmessungen: 12 mm x 100 mm x 68 mm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

Designed for high-precision analog acquisition within EtherCAT networks, the EL3164 analog input terminal processes signal voltages ranging from 0 to 10 V. This four-channel module features a single-ended design configuration, converting analog process signals with 16-bit resolution (including sign) for transmission to the higher-level automation controller. Built for industrial environments, it features integrated Distributed Clocks (DC) to ensure highly synchronized microsecond-level timing across the control system.

The EL3164 EtherCAT terminal integrates configurable software options to optimize signal quality, including selectable FIR and IIR digital filters, along with limit value monitoring capabilities. This compact 12 mm module communicates directly via the E-bus to leverage high-speed data transfer rates, making it an ideal choice for testing, assembly, and plant automation applications.

Features

  • Four independent, single-ended analog input channels in a single compact housing
  • Standard signal voltage range of 0 to 10 V
  • High-resolution 16-bit analog-to-digital conversion (including sign)
  • Supports Distributed Clocks (DC) for precise synchronization across the network
  • Software-configurable digital filters (FIR/IIR) and integrated limit value monitoring
  • Electrical isolation of 500 V between the E-bus and the input signal channels
  • Standard compact design with status indication LEDs for fast diagnostic troubleshooting

Applications

  • Heavy industrial process monitoring and automation control loops
  • Precision machine building and high-speed motion synchronization
  • Data acquisition setups, calibration platforms, and automated test benches
  • Automated HVAC control, water distribution, and environmental monitoring infrastructure

Technical Specifications

Manufacturer Beckhoff
Part Number / Model EL3164
Number of Inputs 4 (single-ended)
Signal Voltage Range 0 to 10 V
Resolution 16 bit (incl. sign)
Conversion Time approx. 100 us
Internal Resistance > 200 kOhm
Input Filter Limit Frequency 5 kHz
Dielectric Strength max. 30 V
Measuring Error < +/-0.3 % (relative to full scale value)
Distributed Clocks Yes
Current Consumption E-bus typ. 130 mA
Electrical Isolation 500 V (E-bus / signal voltage)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Protection Rating IP20
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight approx. 65 g

Connections and Interfaces

Conductor Type Connection Cross-Section (Metric) Connection Cross-Section (AWG)
Solid Wire (s) 0.08 to 2.5 mm² AWG 28 to 14
Stranded Wire (st) 0.08 to 2.5 mm² AWG 28 to 14
With Ferrule (f) 0.14 to 1.5 mm² AWG 26 to 16
Stripping Length 8 to 9 mm

Installation Guidelines

  • Mounting: Snap directly onto a standard 35 mm DIN rail (conforming to EN 60715). Ensure the locking mechanism is engaged.
  • Shielding and Grounding: Connect the cable shield directly to the grounding busbar or ground terminal to minimize electromagnetic noise on the analog inputs.
  • Wiring: Toolless wiring can be performed on solid or ferruled wires using the integrated spring-clamp terminals. For stranded wires without ferrules, actuate the clamp using a small screwdriver.
  • Environmental: Install in a dry, clean cabinet environment with an ambient operating temperature between 0 and +55 degC. Ensure ventilation clearance as required by system architecture guidelines.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc
Loading product navigation…

What is the signal voltage range for the Beckhoff EL3164?

The EL3164 processes single-ended analog voltage signals within the range of 0 to 10 V.

Does the EL3164 support Distributed Clocks (DC)?

Yes, the EL3164 terminal supports Distributed Clocks, allowing highly precise synchronization with other network components.

What is the measurement resolution of this module?

The EL3164 provides a high measurement resolution of 16 bits, which includes the sign bit.

What is the typical current consumption of the EL3164 from the E-bus?

The module typically draws 130 mA from the E-bus power supply.

What ATEX hazardous area classification does the EL3164 have?

The module is certified with ATEX marking II 3 G Ex nA IIC T4 Gc, making it suitable for Zone 2 hazardous locations.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie SPS-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...