Description

The KS4004 analog output terminal is designed to generate highly accurate analog signals within the range of 0 to 10 V. Engineered as part of the Beckhoff KS series, this 4-channel module features a pluggable wiring level that permits swift replacement during maintenance without disconnecting active field wiring. The terminal processes electrical signals with a resolution of 12 bits and transfers them, electrically isolated, to the process level. The power required to operate the module is drawn directly from the K-bus, eliminating the need for separate external power contacts.

This single-ended output terminal is optimized for compact control cabinets where high-density analog output signals and quick-disassembly capabilities are critical. With built-in short-circuit protection and an exceptionally low output error margin, the KS4004 guarantees stable command signal delivery to actuator drives, control valves, and other analog-driven field devices in complex process environments.

Features

  • Four analog output channels with a 0 to 10 V signal range.
  • Pluggable connection level for easy installation and tool-free module swap-outs.
  • Internal power supply driven directly via the Beckhoff K-bus interface.
  • Short-circuit proof outputs designed to handle loads greater than 5 kOhm.
  • High-accuracy performance with a relative output error of less than +/-0.1 % of the full-scale value.
  • No address or hardware configuration required prior to deployment.

Applications

  • Industrial positioning systems and actuator control loops.
  • Variable frequency drive (VFD) speed reference signaling.
  • HVAC dampers and climate control system modulation.
  • Standard machine building and process plant automation.

Technical Specifications

ManufacturerPart Number / ModelTechnologyNumber of OutputsPower SupplySignal VoltageLoadOutput ErrorResolutionConversion TimeElectrical IsolationCurrent Consumption K-BusCurrent Consumption Power ContactsBit Width in Process ImageOperating TemperatureStorage TemperatureRelative HumidityVibration and Shock ResistanceEMC Immunity and EmissionProtection RatingDesignMaterialInstallationDimensions (L x W x H)Weight
BECKHOFF
KS4004
Single-ended
4
Via the K-bus
0 to 10 V
> 5 kOhm (short-circuit proof)
< +/-0.1 % (relative to end value)
12 bit
Approx. 2 ms
500 V (K-bus/signal voltage)
Typ. 85 mA
None (no power contacts)
Output: 4 x 16 bit data (optional 4 x 8 bit control/status)
0 to +55 degC
-25 to +85 degC
95 %, no condensation
Conforms to EN 60068-2-6 / EN 60068-2-27
Conforms to EN 61000-6-2 / EN 61000-6-4
IP20 (variable installation position)
Terminal housing with pluggable wiring level
Polycarbonate
35 mm DIN rail (conforming to EN 60715) with lock
6.8 cm x 1.2 cm x 10.0 cm
0.085 kg

Connections and Interfaces

Wiring MethodSolid Wire Cross-SectionStranded Wire Cross-SectionFine-Wire Cross-SectionStripping Length
Connection Property Specification
Spring actuation by screwdriver
0.08 to 1.5 mm² (AWG 28 to 16)
0.08 to 1.5 mm² (AWG 28 to 16)
0.14 to 1.5 mm² (AWG 26 to 16)
9 to 10 mm

Installation Guidelines

  • Mount the module vertically or horizontally on a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking slide mechanism snaps securely into place.
  • To prevent electromagnetic interference on sensitive 0-10 V analog lines, use shielded cables and connect the shield to a low-resistance ground terminal near the entry point of the control panel.
  • Ensure that no field wiring is connected when plugging or unplugging the terminal wiring level to avoid transient electrical spikes.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc
Loading product navigation…

What is the primary difference between Beckhoff KS and KL series terminals?

The KS series terminals (such as the KS4004) feature a pluggable connection level that can be detached from the housing. This allows the terminal electronics to be replaced without disconnecting the pre-wired terminal blocks.

Does the KS4004 require an external power supply connection?

No, the KS4004 does not use external power contacts. It is powered internally via the standard Beckhoff K-bus, consuming typically 85 mA.

What is the output voltage and channel capability of the KS4004?

The KS4004 provides 4 analog output channels, each capable of outputting a 0 to 10 V signal with 12-bit resolution.

Is the analog output protected against short circuits?

Yes, the analog outputs on the KS4004 are short-circuit proof for loads greater than 5 kOhm.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...