1 de 4

Foxboro FBM202 P0916AC Thermocouple/mV Input Module

Foxboro FBM202 P0916AC Thermocouple/mV Input Module

Solo queda(n) 10 artículo(s) en stock
  • Fabricante: Foxboro

  • Número de producto: FBM202

  • País de origen:Francia

  • Tipo de producto: Thermocouple/mV Input Module

  • Pago: Transferencia bancaria, Western Union

  • Peso: 159g

  • Dimensiones: 102 mm x 45 mm x 104 mm (H x W x D)

  • Puerto de envío: Xiamen

  • Garantía: 12 meses

Cantidad
Ver detalles completos

Description

The Foxboro FBM202 P0916AC is a DIN rail-mounted passive termination assembly designed to interface eight isolated thermocouple/mV analog input signals with an FBM202 module within the Foxboro I/A Series and Foxboro Evo DCS platforms. The P0916AC termination assembly incorporates a 4-wire 100 ohm platinum RTD (IEC 751, Class B) to provide cold-junction reference temperature compensation for accurate thermocouple measurements. Each input channel on the associated FBM202 module provides galvanic isolation from other channels and ground, supporting standard thermocouple types B, E, J, K, N, R, S, T, and millivolt input signals. Signal processing involves per-channel Sigma-Delta A/D conversion, upscale thermocouple burnout detection, and configurable integration periods. The P0916AC termination assembly connects to the baseplate-mounted FBM202 module via a removable Type 2 termination cable, conveying field signals to the module and communicating via the redundant 2 Mbps module Fieldbus to Fieldbus Communication Modules or Control Processors.

Features

  • Eight-channel field I/O feedthrough connection with channel-to-channel galvanic isolation
  • Integrated 4-wire 100 ohm platinum RTD (IEC 751, Class B) for reference junction compensation
  • Compression screw terminal connections accepting 0.2 to 4 mm2 (24 to 12 AWG) field wiring
  • Polyvinyl chloride (PVC) housing construction rated for -20 to +50 degC operating temperatures
  • Passive feedthrough interface supporting Type 2 termination cables up to 30 m in length
  • DIN rail mounting design compatible with 32 mm and 35 mm DIN rails
  • High-accuracy performance utilizing per-channel Sigma-Delta A/D conversion on the FBM202

Applications

  • Thermocouple signal interfacing for DCS temperature loops
  • Process temperature monitoring with cold junction compensation
  • Millivolt input processing for industrial automation systems
  • Replacement and upgrade of Foxboro 100 Series FBM02 field wiring setups

Ordering Information

Part Number Description Material Connection Type
P0916AC Eight-channel thermocouple/mV passive feedthrough TA with RTD PVC Compression
P0916AD Eight-channel thermocouple/mV passive feedthrough TA with RTD PVC Ring Lug
P0916XH Eight-channel thermocouple/mV passive feedthrough TA with RTD PA Compression
P0917JL Eight-channel thermocouple/mV passive feedthrough TA with RTD PA Ring Lug
P0928CN Baseplate-mounted TA for two sets of eight thermocouple/mV channels PC/ABS Compression

Technical Specifications

Category Specification Parameter / Value
General Manufacturer Foxboro by Schneider Electric
  Part Number P0916AC
  Compatible Module FBM202 (P0926EQ)
Input Specifications Channels 8 isolated thermocouple/mV input channels
  Input Range -10.5 to +69.5 mV dc (0 to 64000 raw counts); Full range: 71.419 mV (65535 raw counts)
  Thermocouple Types B, E, J, K, N, R, S, T and other millivolt signals
  Differential Input Impedance 10 Mohm
  Burnout Detection Full upscale value
  Common Mode Voltage Up to 30 V ac or 60 V dc
Accuracy & Performance Millivolt Input Accuracy +0.03% of span (+-27 uV) at 25 degC
  RTD Channel Accuracy +0.03% of span
  RTD Reference Junction Conformity +-0.25 degC
  Thermocouple Conformity +0.25 degC
  Accuracy Temperature Coefficient +-50 ppm/degC
  RTD Reference Junction Measurement Accuracy +-0.50 degC (using RTD internal to Foxboro TAs)
  Reference Junction Type 4-wire 100 ohm platinum RTD (IEC 751, Class B)
Electrical Isolation Channel Isolation Galvanic isolation per channel; withstands 600 V ac for 1 minute between channel and ground or channel to channel
Environmental Operating Temperature (PVC TA) -20 to +50 degC (-4 to +122 degF)
  Storage Temperature -40 to +70 degC (-40 to +158 degF)
  Relative Humidity 5 to 95% (noncondensing)
  Altitude -300 to +3,000 m (-1,000 to +10,000 ft) operating
  Contamination Class G3 (Harsh) per ISA Standard S71.04
Mechanical TA Material Polyvinyl Chloride (PVC)
  Termination Type Compression screw terminals
  Compression Accepted Wiring Sizes Solid/Stranded: 0.2 to 4 mm2 / 24 to 12 AWG; Stranded with Ferrules: 0.2 to 2.5 mm2
  Weight (Compression TA) 159 g (0.35 lb) approximate
  Dimensions (Compression TA) 125 mm x 76 mm x 72 mm (4.93 in x 2.99 in x 2.83 in)

Connections/Interfaces

Connector Pin / Terminal Function
Field Termination Compression Screw Direct connection for 8 two-wire thermocouple/mV analog input field signals
Internal RTD Connection Connections to the integral 4-wire 100 ohm platinum RTD for reference junction compensation
Cable Interface 25-pin D-subminiature connector linking to the FBM baseplate via Type 2 cable

Installation Guidelines

  • DIN Rail Mounting: Mount the P0916AC termination assembly on standard 32 mm or 35 mm DIN rails.
  • Cable Connection: Connect the 25-pin D-subminiature end of the Type 2 termination cable to the TA and the 37-pin D-subminiature end to the FBM202 baseplate slot.
  • Field Wiring: Insert field wiring into compression screw terminals accepting 0.2 to 4 mm2 (24 to 12 AWG) solid or stranded conductors.
  • Hazardous Area Limits: Ensure field wiring voltages do not exceed 30 V ac or 60 V dc to prevent electrical safety code violations and shock hazards.
  • Environmental Enclosure: Install in appropriate enclosures when operating in Class G3 harsh environments to comply with environmental ratings.

Compliance and Certifications

  • UL/UL-C: UL/UL-C listed as suitable for use in Class I, Groups A-D, Division 2, temperature code T4 hazardous locations.
  • ATEX / CENELEC: CENELEC (DEMKO) certified EEx nA IIC T4 for use in Zone 2 potentially explosive atmospheres.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Foxboro FBM202 P0916AC Thermocouple/mV Input Module

What is the Foxboro P0916AC used for?

The Foxboro P0916AC is a DIN rail-mounted compression termination assembly used to interface eight thermocouple or millivolt input signals to a Foxboro FBM202 module in I/A Series and Foxboro Evo DCS systems.

Which module is compatible with the P0916AC termination assembly?

The P0916AC termination assembly is specifically designed to connect with the Foxboro FBM202 Thermocouple/mV Input Module.

How does the device handle reference junction compensation?

The device includes an integral 4-wire 100 ohm platinum RTD (IEC 751, Class B) directly on the termination assembly for cold-junction temperature compensation.

What wire sizes are supported by the module terminals?

The compression terminals on the P0916AC accept solid or stranded conductors from 0.2 to 4 mm2 (24 to 12 AWG), and stranded conductors with ferrules from 0.2 to 2.5 mm2.

What hazardous area certifications apply to the P0916AC?

The P0916AC is UL/UL-C listed for Class I, Division 2, Groups A-D (T4) and CENELEC (DEMKO) certified as EEx nA IIC T4 for Zone 2 locations.

Envío exprés global

  • Entrega estándar: 4-6 días hábiles vía DHL, FedEx y UPS.
  • Envío exprés: Despacho el mismo día para pedidos en stock realizados antes de las 2:00 PM (GMT+8).
  • Cobertura mundial: Servicio en más de 150 países, incluyendo entrega rápida a Arabia Saudita y Emiratos Árabes Unidos.

Devoluciones y Garantía

  • Garantía de 30 días: Se aceptan devoluciones de productos en stock en su embalaje original y sellado de fábrica.
  • Garantía de 12 meses: Cada componente industrial cuenta con nuestra garantía técnica profesional.

Los pedidos se procesan y entregan de lunes a viernes (excepto festivos).


Para conocer la elegibilidad completa, las tarifas de reposición y los detalles de devoluciones internacionales, por favor consulte nuestro sitio oficial Política de Reembolso y Devoluciones .

TECHNICAL SPECIFICATIONS

Country of origin
Francia

Productos vistos recientemente

Conocimientos técnicos

¿Qué es un VFD? Variadores de frecuencia que realmente marcan la diferencia

Un VFD convierte la red eléctrica de frecuencia fija en voltaje y frecuencia controlados para que los motores de CA se adapten a la carga real, reduciendo el consumo de energía de bombas y...

¿Qué es un PLC? Los controladores que aún hacen funcionar la planta industrial

Los PLC siguen controlando la planta: los ciclos de escaneo, las E/S y los lenguajes IEC 61131-3 determinan si las máquinas mantienen un comportamiento determinista. Así funcionan los controladores,...

Lo que realmente se necesita para aprender automatización industrial en 2026

Aprender automatización industrial ahora implica dominar los PLC, las redes y los sistemas de protección, no solo los robots. Esta guía presenta las habilidades, los obstáculos y las trayectorias...

Modernización de las HMI Bailey INFI 90 Symphony que se ejecutan en OpenVMS Alpha

Una guía práctica para reemplazar estaciones de operación Bailey Symphony obsoletas que funcionan con OpenVMS Alpha. Compara la emulación de Alpha, la migración de OpenVMS a x86, la reimplementación...

Por qué los datos de mantenimiento son esenciales para la fiabilidad industrial

Los datos de mantenimiento conectan las órdenes de trabajo, las señales de los sensores, el historial de los activos, los costos y los conocimientos de los técnicos. Cuando se utilizan correctamente,...

Actuadores eléctricos diseñados para sustituir sistemas de potencia fluida: una guía práctica de automatización industrial

Este artículo explica cómo los actuadores eléctricos integrados, como la serie e-Actuator de SMC, están transformando el control de movimiento industrial al reemplazar los sistemas neumáticos e...