Designed for decentralized automation without control cabinet enclosures, the Beckhoff EP2028-0032 EtherCAT Box provides high-capacity control over eight digital actuator channels directly within harsh operating environments. This rugged IP67-rated device processes binary control signals from the automation controller to actuate heavy industrial loads such as solenoid valves, DC contactors, and signaling lamps. Equipped with high-power M12 output interfaces and a robust 7/8-inch power system, this module is engineered to handle up to 2.8 A per channel with a combined sum current of 16 A, making it an excellent choice for demanding field installations where high electrical load density and extreme reliability are required.

Features

  • Rugged Enclosure: Fully encapsulated IP65/66/67 construction enables direct machine mounting without protective enclosures.
  • High Output Current: Individual channels support loads up to 2.8 A, optimized for heavy-duty ohmic, inductive, and lamp loads.
  • Comprehensive Diagnostics: Individually short-circuit proof outputs with quick-response current limiting (typical 15 A short-circuit current).
  • Industrial Power Distribution: Features a high-capacity 5-pin 7/8-inch power configuration for feed and downstream loop-through connections.
  • Standardized Fieldbus Connection: Shielded screw-type M8 interfaces ensure reliable, high-speed EtherCAT communication.

Applications

  • Direct control of high-current hydraulic and pneumatic valve manifolds.
  • Decentralized tooling and actuator control on robotic end-effectors.
  • Automobile assembly lines and press shops with high electromagnetic and vibration levels.
  • Conveyor systems, sorting machinery, and automated material handling equipment.

Technical Specifications Table

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Number EP2028-0032
Protocol EtherCAT
Number of Outputs 8 digital outputs (1 output per M12 connector)
Nominal Output Voltage 24 V DC (-15% / +20%)
Max. Output Current 2.8 A per channel (Sum current limit: 16 A)
Load Compatibility Ohmic, inductive, lamp load
Bus Interface Connection 2 x M8 socket, shielded, screw-type
Output Connections M12 x 1, 5-pin, A-coded
Power Feed / Downstream Connectors 1 x 7/8" plug (5-pin) / 1 x 7/8" socket (5-pin)
Current Consumption (from US) Typically 130 mA
Auxiliary Power Current (UP) Typically 20 mA + connected load
Electrical Isolation 500 V
Switching Response Times Typical TON: 200 us, TOFF: 200 us
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP65/66/67 (conforms to EN 60529)
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Interface Type Pin / Terminal Assignment Circuit Description
M8 EtherCAT Ports (IN/OUT) 4-pin, shielded, screw connection Transmit/Receive pairs for high-speed network integration.
M12 Output Ports (1-8) 5-pin, A-coded (1 active output per connector) Switched 24 V DC output signal to actuator, earth ground, and common return.
7/8" Power Input Feed 5-pin male connection Primary feed for control electronics (US) and auxiliary load supply voltage (UP).
7/8" Power Downstream Link 5-pin female connection Daisy-chain output to downstream modules (maximum 16 A total current loop).

Empirical Engineering Insights

Alternative Models & Compatibility

The EP2028-0032 variant is functionally distinct from standard low-current EtherCAT boxes (such as the EP2028-0002). While the -0002 variant utilizes M8 power cabling and supports up to 0.5 A per channel, the -0032 utilizes a heavy-duty 7/8-inch power system to deliver up to 2.8 A per channel. These two variants are not directly drop-in compatible in terms of physical wiring systems. Upgrading to the -0032 requires transitioning to 7/8-inch power cables to support the higher current capacities.

Application Pitfalls & Engineering Notes

When switching inductive loads close to the 2.8 A channel maximum, the accumulated heat within the encapsulated housing must be closely monitored. In high-density installations, avoid placing adjacent high-duty cycle modules within dead air spaces. Although the continuous sum current rating is robustly set at 16 A, continuous duty near this threshold in elevated ambient temperatures can trigger localized thermal monitoring faults.

Commissioning & Wiring Tips

Ensure that all M12 and M8 connector interfaces are torqued exactly to OEM torque requirements (0.6 Nm for M12, 0.4 Nm for M8) using a calibrated torque wrench. Undertightening compromises the IP67 sealing, permitting ingress of moisture or coolant, whereas overtightening will fracture the internal plastic threads. To avoid communication drops, always use dual-shielded industrial Ethernet cables for the M8 EtherCAT connections to isolate high-frequency noise from adjacent high-power switching conductors.

Installation Guidelines

CRITICAL WARNING: De-energize all primary (US) and auxiliary (UP) power supplies before performing installation, wiring, or maintenance on this EtherCAT Box. Failure to completely isolate the power supply can result in terminal damage, severe electrical shock, or permanent destruction of connected downstream modules.
  1. 1 Mount the module on a flat, vibration-resistant surface using two M4 bolts inserted through the designated mounting holes.
  2. 2 Connect the shielded M8 EtherCAT network cables to the IN and OUT ports, ensuring correct key alignment.
  3. 3 Secure the A-coded M12 cables to the output ports, ensuring that unused ports are sealed with IP67 protective caps.
  4. 4 Attach the 5-pin 7/8-inch power feed, tighten the coupling ring, and verify the ground connection back to the central machine busbar.
Loading product navigation…

What is the maximum output current rating for the EP2028-0032?

Each of the 8 digital output channels supports up to 2.8 A individually. The continuous sum current rating across all channels combined is 16 A, utilizing the robust 7/8-inch power feed.

Can this EtherCAT Box be used with standard M8 power connectors?

No, this specific high-current variant uses a 5-pin 7/8-inch plug for the power feed and a 5-pin 7/8-inch socket for downstream power distribution, differing from standard M8 modules.

How does the module handle short circuits?

Each of the 8 channels is individually short-circuit proof. If a short circuit occurs, it is limited to a typical current of 15 A and can be diagnosed via the TwinCAT control software.

ارسال سریع جهانی

  • تحویل استاندارد: ۴-۶ روز کاری از طریق DHL، FedEx و UPS.
  • ارسال فوری: ارسال همان روز برای سفارش‌های موجود در انبار که قبل از ساعت ۲:۰۰ بعدازظهر (GMT+8) ثبت شده‌اند.
  • پوشش جهانی: خدمات به بیش از ۱۵۰ کشور، شامل تحویل سریع به عربستان سعودی و امارات.

بازگشت کالا و گارانتی

  • ضمانت ۳۰ روزه: بازگشت کالا برای محصولات موجود در انبار با بسته‌بندی اصلی و مهر کارخانه پذیرفته می‌شود.
  • گارانتی ۱۲ ماهه: هر قطعه صنعتی با گارانتی فنی حرفه‌ای ما پشتیبانی می‌شود.

سفارش‌ها از دوشنبه تا جمعه پردازش و تحویل داده می‌شوند (به جز تعطیلات رسمی).


برای شرایط کامل واجد شرایط بودن، هزینه‌های بازگردانی و جزئیات بازگشت بین‌المللی، لطفاً سیاست رسمی ما را مشاهده کنید سیاست بازپرداخت و بازگشت کالا .

TECHNICAL SPECIFICATIONS

Country of origin
آلمان

محصولات مشاهده‌شده اخیر

دانش فنی

عملگرهای الکتریکی طراحی شده برای جایگزینی سیستم‌های نیروی سیال: راهنمای عملی اتوماسیون صنعتی

این مقاله توضیح می‌دهد که چگونه عملگرهای الکتریکی یکپارچه، مانند سری e-Actuator شرکت SMC، در حال تحول کنترل حرکت صنعتی با جایگزینی سیستم‌های سنتی پنوماتیک و هیدرولیک هستند. این مقاله به بهبود دقت...

عملیات ریاضی با استفاده از OpenPLC برای کاربردهای اتوماسیون صنعتی

این مقاله توضیح می‌دهد که چگونه سیستم‌های PLC عملیات ریاضی اصلی مانند جمع، تفریق، ضرب، تقسیم، مدول و توان را در اتوماسیون صنعتی انجام می‌دهند. نشان می‌دهد که چگونه این بلوک‌های عملکردی سیگنال‌های خام...

منطق بولی پیشرفته با برنامه‌نویسی FBD PLC: کاربردهای عملی صنعتی فراتر از منطق پایه

این مقاله چندین تابع پیشرفته منطق بولی را که در برنامه‌نویسی PLC فراتر از عملیات پایه AND، OR و NOT استفاده می‌شوند، توضیح می‌دهد. همچنین نحوه استفاده از ابزارهایی مانند جداول صحت، مالتی‌پلکسرها،...

منطق بولی در برنامه‌نویسی PLC: درک گیت‌های منطقی FBD

منطق بولی پایه و اساس هر برنامه PLC است. از کنترل‌های ساده ماشین تا سیستم‌های پیچیده اتوماسیون صنعتی، دروازه‌های منطقی تعیین می‌کنند که کنترل‌کننده‌ها چگونه به ورودی‌ها و شرایط عملیاتی متغیر پاسخ...

راهنمای جامع فایروال‌های صنعتی و تقسیم‌بندی شبکه OT

فایروال‌های صنعتی نقش حیاتی در امنیت سایبری OT ایفا می‌کنند و با استفاده از تقسیم‌بندی، کنترل ورودی/خروجی و ادغام IDS/IPS مطابق با اصول IEC 62443، از شبکه‌های PLC، DCS و SCADA محافظت می‌کنند.

راهنمای گیره‌های رباتیک: از جابجایی ظریف تا اتوماسیون سنگین

گیره‌های رباتیک مدرن فراتر از فک‌های مکانیکی سنتی در حال پیشرفت هستند. از سیستم‌های چسبنده الهام‌گرفته از گکوی، گیره‌های نرم با درجه‌بندی غذایی تا ابزارهای انبار مجهز به هوش مصنوعی، فناوری‌های...