Product Overview
The 034N0083 (034N0083), also designated as Type CPCE 15, is a high-precision hot gas bypass regulator designed to adapt compressor capacity to actual evaporator load. By bypassing hot gas from the high-pressure side of the refrigeration system to the low-pressure side, the 034N0083 prevents excessively low suction pressure and evaporator icing. This regulator is a critical component for maintaining stable evaporation temperatures in commercial refrigeration, air conditioning, and liquid chiller units. Its robust mechanical design ensures reliable operation in demanding environments, protecting the compressor from short-cycling and ensuring consistent cooling performance even under low-load conditions.
Technical Configuration
The 034N0083 architecture is engineered for precise pressure modulation and durability:
-
CPCE Series Engineering: Specifically designed for injection between the thermostatic expansion valve and the evaporator, often used in conjunction with a liquid-gas mixer (LG).
-
Direct-Acting Diaphragm: The 13.5 mm actuator system responds instantly to suction pressure changes, providing smooth, modulating control without abrupt steps.
-
Wide Thermal Range: Capable of operating in ambient conditions from -40 to 50 Celsius (-40 to 122 Fahrenheit), making it suitable for both cold storage and high-temperature mechanical rooms.
-
Pressure Rating: Rated for a Maximum Working Pressure (MWP) of 18 bar (260 psig), providing a significant safety margin for standard HCFC and HFC refrigerant systems.
Technical Specifications
| Feature |
Specification |
| Model |
034N0083 (CPCE 15) |
| Brand |
Danfoss |
| Product Type |
Hot Gas Bypass Regulator |
| Actuator System |
13.5 mm |
| Max Working Pressure |
18 bar (260 psig) |
| Ambient Temperature |
-40 to 50 Celsius |
| Max Media Temp |
140 Celsius |
| Regulation Range |
0 to 6 bar (Factory Setting 0.4 bar) |
| Net Weight |
0.95 kg |
| Shipping Weight |
1.5 kg |
Technical FAQs
How does the CPCE 15 prevent compressor overheating?
The 034N0083 bypasses hot gas to the evaporator inlet rather than directly to the suction line. This ensures that the hot gas is mixed with liquid refrigerant from the expansion valve, which desuperheats the gas before it reaches the compressor, preventing high discharge temperatures.
Can the 034N0083 be used with modern low-GWP refrigerants?
The CPCE 15 is compatible with most standard HCFC and HFC refrigerants. However, always verify that the specific refrigerant’s pressure-temperature characteristics fall within the 18 bar MWP and that the lubricant used is compatible with the regulator's internal seals.
What is the function of the 13.5 mm actuator in this regulator?
The 13.5 mm actuator refers to the diameter of the internal bellows/diaphragm assembly. This specific sizing allows for high-sensitivity regulation, ensuring that even small fluctuations in suction pressure trigger the necessary bypass flow to maintain system equilibrium.
Engineering & Installation Guide
-
System Integration: For optimal performance, the CPCE 15 should be installed in a bypass line between the discharge line and the distributor at the evaporator inlet. Utilizing a Danfoss LG liquid-gas mixer at the point of injection is highly recommended to ensure thorough mixing of hot gas and liquid refrigerant.
-
Adjustment Procedure: The regulator is factory-set to open at a suction pressure of 0.4 bar. To adjust the setpoint, remove the protective cap and turn the setting screw. Clockwise rotation increases the opening pressure, while counter-clockwise rotation decreases it. Perform adjustments in small increments while monitoring suction pressure gauges.
-
Brazing Safeguards: During installation, the regulator body must be wrapped in a wet cloth or heat-sink paste. Excessive heat during brazing can damage the internal diaphragm and the 13.5 mm actuator system, leading to calibration drift or external leaks.