1 de 3

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Il ne reste que 4 article(s) en stock
  • Fabricant : Bently Nevada

  • N° de produit : 136719-01

  • Pays d'origine :États-Unis

  • Type de produit : Earthing I/O Module

  • Code-barres : 8537101190

  • Paiement : Virement bancaire, Western Union

  • Poids : 400g

  • Dimensions : 241 mm x 24.4 mm x 103.1 mm (H x W x D)

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

The Bently Nevada 136719-01 (part of the 3500/04-01 assembly) is an Earthing I/O Module designed for intrinsically safe (IS) ground reference management within the 3500 Machinery Protection System. Installed directly into the rear of the 3500 system rack, the 136719-01 provides the essential intrinsically safe earth connection through the 3500 system backplane to interface with internal barrier monitor I/O modules. This configuration enables safe, direct interconnection with approved field transducers—such as 3300 XL Proximitor sensors, Velomitor sensors, thermocouples, and RTDs—operating in hazardous environments without requiring external barriers or compromising system performance.

Features

  • Provides the intrinsically safe ground connection for internal barrier I/O modules via the 3500 system backplane.
  • Installs in a dedicated monitor position within the standard 3500 Machinery Protection System rack.
  • Fully integrated backplane routing eliminates the need for external zener or galvanic isolation barrier units.
  • Supports combined rack layouts hosting both internal barrier modules and standard I/O modules.

Applications

  • Intrinsically safe field wiring grounding for 3500 Machinery Protection Systems in hazardous industrial areas.
  • Turbomachinery vibration, speed, position, and temperature monitoring systems requiring IS loop protection.

Ordering Information

Part Number / Option Code Description
3500/04-AA-BB 3500/04 Internal Barrier System
A: I/O Module Type 01 Earthing I/O Module
B: Agency Approval

00 None

01 North American Hazloc

02 Multi (CSA, ATEX, IECEx)

136719-01 Earthing I/O Module (Spare Part)
138257-01 Earthing Module Front Panel (Spare Part)

Technical Specifications

Specification Category Parameter / Value
Manufacturer Bently Nevada
Module Type Earthing I/O Module (3500/04 IS Earthing Module)
Dimensions (H x W x D) 241 mm x 24.4 mm x 103.1 mm (9.50 in. x 0.96 in. x 4.06 in.)
Weight 0.201 kg (0.443 lb.)

Installation Guidelines

  • Rack Slot Allocation: The 136719-01 IS Earthing Module requires a dedicated monitor position in the rack, which limits a standard 19-inch rack to 13 monitor positions.
  • Positioning: Locate the IS Earthing Module in a rack position that allows easy access for routine online maintenance. When positioned between internal barrier I/O modules, allow a minimum of two rack positions to facilitate online access.
  • Requirement: Any 3500 rack containing internal barrier I/O modules must be equipped with a 3500/04-01 IS Earthing Module to provide the backplane IS earth path.
  • Wiring Separation: Route hazardous area field wiring above the 3500 rack and safe area wiring below to maintain a minimum physical separation of 50 mm (2 in).

Compliance and Certifications

Standard / Approval Type Certificate / Standard Level
FCC Complies with Part 15 of FCC Rules
EMC Directive European Community Directive 2014/30/EU; EN 61000-6-2, EN 61000-6-4
Electrical Safety European Community Directive 2014/35/EU; EN 61010-1
Marine Classification DNV GL rules for classification; ABS Rules Part 1
cNRTLus Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, D; T4 @ Ta = -20 degC to +65 degC
ATEX / IECEx II 3 G; Ex nA nC ic IIC T4 Gc; Ex ec nC ic IIC T4 Gc; T4 @ Ta = -20 degC to +65 degC
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Which chassis slot does the earthing module occupy in the rack?

The module installs into a dedicated monitor position on the 3500 rack backplane, reducing available monitor slots to 13.

Does the earthing module require software configuration?

The module acts as a passive backplane ground reference interface and does not require independent software programming.

Can standard and internal barrier modules coexist in the same chassis?

Standard and internal barrier modules can reside in the same chassis provided the earthing module establishes backplane IS ground.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats Arabes Unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Color pattern
Argent
Country of origin
États-Unis

Produits récemment consultés

Connaissances techniques

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

Modernisation des IHM Bailey INFI 90 Symphony fonctionnant sous OpenVMS Alpha

Un guide pratique pour remplacer les postes opérateur vieillissants Bailey Symphony fonctionnant sous OpenVMS Alpha. Il compare l’émulation Alpha, la migration vers OpenVMS x86, la refonte basée sur...

Pourquoi les données de maintenance sont essentielles à la fiabilité industrielle

Les données de maintenance relient les ordres de travail, les signaux des capteurs, l’historique des actifs, les coûts et les connaissances des techniciens. Lorsqu’elles sont bien exploitées, elles...

Actionneurs électriques conçus pour remplacer les systèmes de puissance fluidique : guide pratique de l’automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle des mouvements industriels en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour des applications d’automatisation industrielle

Cet article explique comment les systèmes API réalisent des opérations mathématiques essentielles telles que l’addition, la soustraction, la multiplication, la division, le modulo et l’exponentiation...