The Danfoss 060G1367 is a precision-engineered pressure transmitter designed for reliable monitoring in industrial process control. Utilizing an industry-standard 4 - 20 mA current output, this transmitter ensures robust signal integrity and noise immunity, making it an essential component for automated hydraulic circuits, water treatment facilities, and climate control systems. Built for performance in demanding environments, the 060G1367 features an IP65-rated enclosure and provides high measurement stability across a temperature range of -40 deg C to 100 deg C, effectively minimizing system downtime through accurate, consistent pressure feedback.
Technical Configuration
The 060G1367 is built to integrate seamlessly into existing industrial automation frameworks while maintaining high measurement fidelity.
Signal Architecture: The current-loop output (4 - 20 mA) provides inherent diagnostic capability; the factory-set clipping levels (3.6 mA low / 22.4 mA high) allow control systems to immediately detect open-loop or short-circuit faults.
Mechanical Durability: The unit features a G-type pressure connection, designed for high-pressure industrial manifolds. With an overload pressure capacity of 8 bar, it is optimized for mid-range pressure monitoring where reliability under transient pressure spikes is required.
Installation Connectivity: The angular Pg 11 connector simplifies installation in tight industrial cabinets, with Pin 1 assigned to the positive supply and Pin 2 for the common signal path.
Technical Specifications
Feature
Specification
Model
060G1367
Brand
Danfoss
Output Signal
4 - 20 mA
Max Overload
8 bar
Accuracy (Max)
0.5 % FS
Ambient Temp
-40 to 100 deg C
Enclosure
IP65
Electrical Conn.
Angular Pg 11
Weight
1.5 kg (Shipping)
FAQs
Why is this transmitter described as "Gauge (relative)"?
A relative pressure reference means the sensor measures pressure in comparison to the current ambient atmospheric pressure. This is the standard for most industrial applications where process pressure must be understood relative to the local environment, rather than a perfect vacuum.
Can the 060G1367 be adjusted for zero point or span?
No, this model is factory-calibrated for high-precision output. It does not include manual adjustment screws. This design choice prevents accidental calibration drift and ensures long-term reliability in industrial settings where frequent recalibration is impractical.
Is this transmitter suitable for hazardous (intrinsically safe) zones?
No, the 060G1367 is not designated as intrinsically safe. It should not be installed in hazardous or explosive atmospheres unless the installation is protected by an approved intrinsic safety barrier that complies with local industrial safety regulations.
Engineering Guidelines and Best Practices
Loop Resistance: Since this is a 4 - 20 mA device, ensure that the total resistance of the control loop (including the transmitter, wires, and input impedance of the receiver) does not exceed the limit required to maintain the necessary voltage at the transmitter terminals.
Shielding: Use high-quality, shielded, twisted-pair cables for the signal loop to protect against electromagnetic interference from nearby variable frequency drives (VFDs) or motors. Always ground the shield at the control panel end only to avoid ground loops.
Pressure Spikes: While the transmitter handles up to 8 bar of overload pressure, ensure that the hydraulic system is equipped with properly sized pressure relief valves to prevent rapid pressure oscillations or "water hammer" effects that could exceed the rated overload limit.
Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.
Retours et garantie
Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d’origine scellé en usine.
Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.
Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).
Pour connaître les conditions d’éligibilité complètes, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel
Politique de remboursement et de retour
.
Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés du gecko et des pinces souples de qualité alimentaire aux outils d'entrepôt...
Des compresseurs à courant continu entraînés par corde aux wagonnets de mine alimentés par batterie, les premières opérations minières ont marqué un tournant dans l’électrification industrielle. Cet...
Factory I/O révolutionne l'enseignement des automates programmables industriels (API) en proposant des simulations industrielles 3D immersives pour les étudiants, les ingénieurs et les équipes de...
Ce tutoriel examine comment la fonctionnalité PLC intégrée dans un servo-variateur CMZ SBD peut exécuter des programmes de mouvement autonomes, y compris la logique de référencement, le contrôle de...
Ce tutoriel explore la mise en service d'un système de mouvement servo à un seul axe utilisant un variateur CMZ SBD, couvrant l'installation matérielle, la mise à l'échelle de l'axe, la configuration...
Ce tutoriel explique comment les automates programmables Mitsubishi FX s'intègrent avec les variateurs de fréquence FR-D700 et les panneaux HMI pour le contrôle avant/arrière des moteurs. Il couvre...
Choisir une sélection entraîne un rechargement complet de la page.