1 de 1

8965480000 | Weidmuller | Transducteur de température ACT20X-2HTI-2SAO-S

8965480000 | Weidmuller | Transducteur de température ACT20X-2HTI-2SAO-S

Il ne reste que 10 article(s) en stock
  • Fabricant : Weidmuller

  • N° de produit : 8965480000

  • Pays d'origine :Allemagne

  • Type de produit : Transducteur de température

  • Paiement : Virement bancaire, Western Union

  • Poids : 1200g

  • Dimensions : 119.2 mm x 22.5 mm x 113.6 mm

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Processing temperature sensor signals from hazardous areas is the primary function of the Weidmuller 8965480000 ACT20X-2HTI-2SAO-S, a highly reliable 2-channel intrinsically safe temperature transducer. This module isolates, converts, and transmits temperature signals from RTD and thermocouple sensors located in Ex Zone 0, 1, or 2 to the safe area. It features dual-channel density in a compact 22.5 mm housing, providing active or passive 4-20 mA current outputs compatible with standard PLC and DCS analog input cards.

Key Features

  • Dual-Channel Isolation: Two independent, galvanically isolated channels maximize channel density on the DIN rail.
  • Intrinsically Safe Inputs: Certified for direct connection to temperature sensors in Zone 0, 1, and 2 hazardous locations.
  • Universal Sensor Support: Configurable for Pt100, Pt500, Pt1000, Ni100 RTDs, and thermocouple types J, K, T, E, R, S, B, N, L, and U.
  • Comprehensive Diagnostics: Integrated alarm functions detect line interruption, short circuits, supply voltage failure, and internal device errors.
  • FDT/DTM Configuration: Easily parameterized using standard FDT/DTM software via the front-facing service interface.

Industrial Applications

  • Chemical Processing: Monitoring reactor vessel temperatures in explosive atmospheres.
  • Oil & Gas: Temperature measurement on offshore platforms, pipelines, and storage tank farms.
  • Power Generation: Exhaust gas and bearing temperature monitoring in hazardous turbine enclosures.
  • Water & Wastewater: Digester and chemical treatment plant temperature telemetry.

Technical Specifications

Parameter Specification
Manufacturer Weidmuller
Article Number (SKU) 8965480000
Model Code ACT20X-2HTI-2SAO-S
Number of Channels 2
Supply Voltage 19.2 to 31.2 V DC
Power Consumption ≤ 1.4 W
Input Types RTD (Pt100, Pt500, Pt1000, Ni100), Thermocouples (J, K, T, E, R, S, B, N, L, U)
Output Signal 4 to 20 mA (Active or Passive)
Step Response Time ≤ 400 ms (current input), ≤ 1 s (temperature input)
Nominal Switching Voltage ≤ 125 V AC / 110 V DC
Continuous Current ≤ 0.5 A AC / 0.3 A DC
Connection Type Screw connection
Clamping Range 0.5 mm² to 2.5 mm²
Flammability Rating V-0
Protection Degree IP20
Operating Temperature -20 to +60 degC
Humidity 0 to 95% (non-condensing)
Dimensions (H x W x D) 119.2 mm x 22.5 mm x 113.6 mm
Weight 0.180 kg
Shipping Weight (Calculated) 1.200 kg

Connections and Interfaces

Terminal Block Terminal Pin Function / Circuit Assignment
Hazardous Area (Input) 11, 12, 13, 14 Channel 1: RTD (2, 3, or 4-wire) / Thermocouple Input
21, 22, 23, 24 Channel 2: RTD (2, 3, or 4-wire) / Thermocouple Input
Safe Area (Output & Power) 41, 42 Channel 1: 4 to 20 mA Analog Output (Active/Passive)
51, 52 Channel 2: 4 to 20 mA Analog Output (Active/Passive)
31 (+), 32 (-) Device Power Supply (19.2 to 31.2 V DC)

Empirical Engineering Insights

Alternative Models & Compatibility

The ACT20X-2HTI-2SAO-S is the dual-channel variant within Weidmuller's ACT20X intrinsically safe signal converter family. If only a single channel is required, the ACT20X-HTI-SAO-S (single-channel version) can be utilized to reduce hardware costs. Configuration profiles created in the FDT/DTM "WI-Manager" software are fully interchangeable between single and dual-channel models, simplifying commissioning when scaling up system architectures.

Application Pitfalls & Engineering Notes

When mounting multiple ACT20X modules side-by-side on a DIN rail, thermal management is critical. Although the device is rated up to +60 degC, dense installations with continuous 24V DC supply can lead to localized heat build-up. It is recommended to maintain a 5 mm ventilation gap between adjacent modules if the ambient cabinet temperature regularly exceeds 50 degC. Additionally, ensure the loop resistance of the passive output configuration does not exceed the maximum load limits specified for your DCS analog input card.

Commissioning & Wiring Tips

For thermocouple inputs, always ensure that the cold junction compensation (CJC) is correctly configured in the DTM software. If using internal CJC, ensure the terminal block connections are tight and shielded from direct drafts or external heat sources, which can induce measurement drift. For RTD inputs, utilizing a 3-wire or 4-wire connection configuration is highly recommended to automatically compensate for lead wire resistance over long field runs.

Installation Guidelines

CRITICAL WARNING

De-energize all power sources before mounting, wiring, or configuring the device. Ensure strict separation between intrinsically safe (Ex i) field wiring and non-intrinsically safe safe-area wiring in compliance with EN/IEC 60079-14. Failure to maintain physical separation can compromise the explosion protection barrier.

1

Mount the ACT20X module vertically onto a standard TS 35 DIN rail, ensuring the locking foot securely clicks into place.

2

Connect the hazardous area temperature sensor wiring to the blue Ex-input terminals (11-14 and 21-24) using shielded, twisted-pair cables.

3

Wire the safe-area analog outputs (41-42 and 51-52) and the 24 V DC power supply (31-32) to the black terminals.

4

Connect the configuration interface to a PC running Weidmuller WI-Manager (FDT/DTM) to set the sensor type, range, and alarm thresholds.

Loading product navigation…

Can the ACT20X-2HTI-2SAO-S be configured without a PC?

No, this model requires a PC running FDT/DTM software (such as Weidmuller WI-Manager) and a compatible USB interface cable connected to the front service port for parameterization.

What happens to the output signal if a sensor wire breaks?

The module features configurable sensor error detection. In the event of a line interruption or short circuit, the 4-20 mA output can be programmed to go upscale (>= 21.5 mA) or downscale (<= 3.5 mA) to signal a fault to the DCS.

Does this device support both active and passive analog outputs?

Yes, the ACT20X-2HTI-2SAO-S supports both active (where the module powers the loop) and passive (where the receiving DCS/PLC card provides loop power) 4-20 mA configurations.

Is galvanic isolation provided between the two channels?

Yes, complete galvanic isolation is maintained between the input channels, the output channels, and the power supply, preventing ground loops and signal interference.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d’origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître les conditions d’éligibilité complètes, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
Allemagne

Produits récemment consultés

Connaissances techniques

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l'intégration IDS/IPS...

Guide des préhenseurs robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés du gecko et des pinces souples de qualité alimentaire aux outils d'entrepôt...

Retour en arrière : comment les premiers moteurs électriques ont transformé l'exploitation minière souterraine

Des compresseurs à courant continu entraînés par corde aux wagonnets de mine alimentés par batterie, les premières opérations minières ont marqué un tournant dans l’électrification industrielle. Cet...

Factory I/O : un outil moderne de simulation PLC pour la formation à l'automatisation industrielle

Factory I/O révolutionne l'enseignement des automates programmables industriels (API) en proposant des simulations industrielles 3D immersives pour les étudiants, les ingénieurs et les équipes de...

Programmation des cycles de mouvement à axe unique sur un servo-variateur CMZ

Ce tutoriel examine comment la fonctionnalité PLC intégrée dans un servo-variateur CMZ SBD peut exécuter des programmes de mouvement autonomes, y compris la logique de référencement, le contrôle de...