Executing precise process loop control within a unified automation chassis, the Mitsubishi Electric Q62HLC operates as a dedicated two-channel proportional-integral-derivative (PID) controller. This high-speed module interfaces directly with the MELSEC Q Series PLC backplane, eliminating the communication lag typical of external standalone controllers. Capable of handling thermocouple, current, and voltage inputs alongside analog control outputs, the unit provides direct closed-loop feedback processing for demanding industrial thermal, pressure, and flow systems.

Features

  • Dual-Channel Control: Two independent PID loops with dedicated auto-tuning and self-tuning algorithms.
  • Universal Input Architecture: Direct connection for thermocouples (types B, E, J, K, N, R, S, T), micro-voltage, and standard analog current signals.
  • High-Speed Loop Execution: Extremely fast sampling cycle of 25 ms per channel, allowing control over rapid physical process changes.
  • Integrated Analog Outputs: Direct 4-20mA or voltage control outputs to interface cleanly with control valves, actuators, and drives.
  • Native PLC Backplane Integration: Map control loop parameters directly into CPU memory registers without custom communication block configurations.

Applications

  • Precision plastic extrusion, thermoforming, and blow-molding temperature regulation.
  • Industrial heat-treatment furnaces requiring multi-zone PID cascade control.
  • High-speed flow-rate and pressure regulation loops in chemical dosing and water-treatment processes.
  • Environmental chamber control with simultaneous heating and cooling loop processing.

Technical Specifications Table

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number Q62HLC
Control Channels 2 Channels (Independent PID execution)
Thermocouple Input Types B, E, J, K, N, R, S, T
Analog Input Range Voltage/Current (Direct sensor configuration)
Analog Output Channels 2 Channels (Current/Voltage control outputs)
Sampling Cycle 25 ms per channel
Occupied I/O Points 16 Points (Assigned on the Q-series PLC bus)
Internal Current Consumption 0.27 A (at 5 VDC backplane bus)
External Supply Voltage 24 VDC (+10% / -15%)
Operating Temperature Range 0 to 55 degC
Module Weight 0.25 kg
Shipping Weight (Calculated) 1.00 kg (Includes protective industrial packaging)
Dimensions (Calculated) 98 mm x 27.4 mm x 90 mm (H x W x D)

Connections and Interfaces

Terminal Pin Number Terminal Name / Signal Association
Terminal 1 Channel 1 Temperature / Micro-voltage Input (+)
Terminal 2 Channel 1 Temperature / Micro-voltage Input (-)
Terminal 3 Channel 1 Current Input (I+)
Terminal 4 Channel 1 Control Analog Output (+)
Terminal 5 Channel 1 Control Analog Output (-)
Terminal 10 Channel 2 Temperature / Micro-voltage Input (+)
Terminal 11 Channel 2 Temperature / Micro-voltage Input (-)
Terminal 12 Channel 2 Current Input (I+)
Terminal 13 Channel 2 Control Analog Output (+)
Terminal 14 Channel 2 Control Analog Output (-)
Terminal 17 External Power Supply Input (24 VDC)
Terminal 18 External Power Supply Common (0V GND)

Empirical Engineering Insights

Alternative Models & Compatibility

Unlike the Q64TCRT thermal regulation modules, which execute standard temperature profiling on a slower 500ms cycle, the Q62HLC is a high-speed controller designed for 25ms loop response. It incorporates direct physical analog current/voltage outputs rather than transistor outputs. Consequently, logic written for the Q64 series cannot be directly copied; the buffer memory structure of the module must be re-mapped inside the GX Works software environment.

Application Pitfalls & Engineering Notes

Operating the loop controller on a highly dynamic physical actuator requires careful configuration of the derivative action (D-gain). Due to the rapid 25ms sampling time, high-frequency electrical noise on input terminals can propagate into violent fluctuations in the control outputs. If your control variable exhibits high high-frequency jitter, engage the integrated input filter parameters to stabilize the PID feedback loops before committing to fine-tuning adjustments.

Commissioning & Wiring Tips

The Q62HLC terminal block contains a factory-calibrated Cold Junction Compensation (CJC) resistor mounted directly on the lower terminals. Replacing terminal blocks between modules without matching the calibrated CJC resistor can introduce ambient thermal offsets of several degrees Celsius. Always ensure that the physical terminal block remains paired with its original serial-numbered electronic module to avoid field-drift during startup.

Installation Guidelines

CRITICAL WARNING: Verify that all primary control cabinet power is fully de-energized and lock-out tag-out (LOTO) protocols are active before engaging terminal block connections or inserting the module on the MELSEC Q series base unit. Failure to fully isolate the system can result in immediate physical damage to the module backplane and risk control signal disruption.
1
Insert the bottom mounting hook of the module into the guide notch of the base unit.
2
Pivot the module firmly forward against the base unit to snap the top retention latch in place.
3
Secure the module to the base plate using the top integration screw (torque range 0.36 to 0.48 N-m).
4
Attach external 24 VDC auxiliary power to terminals 17 and 18, and use shielded twisted-pair cables for analog signal paths.

What is the key functional difference between the Q62HLC and standard temperature control modules?

The module operates at an ultra-fast sampling rate of 25 ms per channel and includes integrated analog output loops. Standard temperature modules typically run on a 500 ms cycle and use pulse outputs to control solid-state relays.

Does the Q62HLC require a separate analog output module?

No, it features built-in dual-channel analog control outputs, allowing direct connection to modulating control valves or motor speed drives.

Why is the Cold Junction Compensation (CJC) resistor critical on the terminal block?

The CJC resistor calculates ambient temperature drift at the connection terminals. Each resistor is factory-calibrated to its physical module; swapping terminal blocks between modules introduces temperature measurement errors.

What happens if external 24 VDC power is lost to the module?

The module will trigger an external power supply interruption fault code, stop PID processing, and force the analog control outputs to their configured safe-state or minimum value.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Egyesült Államok

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...